4. Commands
Command
Function
Description
1
2
N.O. AUTOMATIC
CLOSING
Permanently closing the contact enables automatic closing.
1
3
N.O. OPENING
With DIP1=ON, closing the contact activates an opening opera-
tion.
STEP-BY-STEP
With DIP1=OFF, closing the contact activates an opening or clos-
ing operation in the following sequence: opening-stop-closing-
opening.
N.B.: if automatic closing is enabled, the stop is not permanent
but has a duration set with the TC trimmer.
1
4
N.O. CLOSING
The closing operation starts when the contact is closed.
1
8
N.C. REVERSAL
SAFETY
CONTACT
Opening the safety contact triggers a reversal of the movement
(reopening) during the closing operation.
1
9
N.C. STOP
Opening the safety contact stops the current operation.
1
9
N.O. OPERATOR
PRESENT
CONTROL
Opening of contact 1-9 enables the operator present function.
- opening with operator present 1-3 [with DIP1=ON];
- closing with operator present 1-4.
N.B.: any safety devices, automatic closing and plug-in cards in
the AUX1, AUX2 and RDX housings are disabled.
1
G1
N.C. REVERSAL
SAFETY
CONTACT
Opening the safety contact triggers a reversal of the movement
(reopening) during the closing operation.
PRG
N.O. TRANSMITTER
STORAGE AND
CANCELLATION
WARNING: the storage module
MUST BE
inserted.
Transmitter storage:
- press the PRG key (the SIG LED turns on),
- proceed with transmission from the transmitter to be stored
(the SIG LED flashes),
- wait 10 s for storage to be completed (the SIG LED turns off).
Transmitter cancellation:
- press the PRG key for 3 s (the SIG LED flashes),
- press the PRG key again for 3 s (the SIG LED flashes faster).
SETTINGS
RESET
WARNING: the storage module must
NOT
be inserted.
- press the PRG key for 4 s (the IN LED flashes),
- press the PRG key within 4 sec for another 2 sec (the IN LED
comes on).
The SETTINGS RESET deletes all the remote software settings
made using the MD2 display module. After SETTINGS RESET it
is possible to adjust the control panel directly.
WARNING: if the MD2 display module is disconnected from the
control panel, a SETTINGS RESET must be performed.
Warning: make a jumper for all NC contacts if not in use. The terminals with the same
number are equal.