1. INTRODUCTION

1.1 About User  Manual
This User Manual is designed to help you for quick installation of  RG-6T.  Before installation
and operation, please read this section very carefully.

1.2 Precautions for Safe Use and Installation

- Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment.
- When the device is connected to the network, do not remove the back panel.
- Do not try to clean the device with solvent or the like. Only clean the device
  with dried cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- Only for rack panel mounting.
- An F type fuse must be used and its current limit value must be 6A.
- No responsibility is assured by ENTES A.S or any of its subsidiaries
  for any consequences arising out of the use of this material.

2.   GENERAL

Power Factor Controllers are used for measurement and control of power factor control units
for central reactive power compensation. The Power Factor measured by RG-6T is compared
with the set point values and in order to provide necessary compensation, Power Factor
Controller switches capacitor banks ON and OFF automatically. RG-6T is a microcontroller
relay, designed  for above application in 144x144 and 96x96 (only RG-6T) case for flush
mounting with rear plug-in connectors. 

In addition to displaying the system’s Cos

ϕ

 in Automatic

Operating Mode, RG-6T displays the RMS values of  Voltage(V) and Current (I), Active
Power (W), Reactive Power (VAr) and Apparent Power (VA) of measuring phase.

3. FRONT PANEL SPECIFICATIONS

On the front panel of RG-6T, there are warning lights, display and 3 buttons for settings.

3.1 Buttons and Lights
1. 
1,2,.........,12

: Shows the status of each capacitor steps.

2.SET Menu

: Shows the Menu options  that correspond  to the lights.

3. AUTO/MAN Light : If this light is continuously ON, RG-6T is in Automatic Mode. If it is

blinking, RG-6T is  in Manual Mode. By pressing SET button 3
seconds, you enter to Menu and change  operating Mode . (Refer
to: 5.1
)

4.  Cos

ϕ

 Light

: By pressing SET button 3 seconds ; Cos

ϕ

  Adjustment  can be made

by selecting this light. (Refer to: 5.3).
In Automatic Mode, when Cos

ϕ

  light is selected  by pressing UP

and DOWN buttons, system’s Cos

ϕ

 and ind/cap state is displayed.

(Refer to: 5.10)

5.TIME/PF Light

: By pressing  SET  button  3 seconds; you enter to Menu  and Step

Time adjustment is made by selecting this light. (Refer to: 5.4)
In Automatic Mode, when this light is selected by pressing UP  and
DOWN buttons, system’s Power Factor is  displayed. (Refer to: 5.11)

6.STEP/V Light

: By pressing  SET button 3 seconds; you enter to Menu  and Step

Number adjustment is made by selecting this light. (Refer to:5.5)
In Automatic Mode, when  this light is selected by pressing UP and
DOWN buttons phase voltage (V) is displayed. (Refer to:5.12)

7. PROGRAM/I Light: By pressing  SET button 3 seconds; you enter to Menu and Power

Sequence adjustment is made by selecting this light. (Refer to:5.6)
In Automatic Mode, when this light is selected by pressing UP and
DOWN buttons phase current (I) is displayed (Refer to:5.12)

8.C/k - W Light

: By pressing  SET button 3 seconds; you enter to Menu and Manual

C/k adjustment is made by selecting this light.(Refer to:5.7)
In Automatic Mode when this light is selected by pressing UP and
DOWN buttons, system’s Active Power (W) is displayed.
(Refer to: 5.13)

9.CTR - VAr Light

: By pressing  SET button 3 seconds; you enter to Menu and Current

Transformer Ratio adjustment is made by selecting this light.
(Refer to:5.8)

  In Automatic Mode when this light is selected by pressing UP and

DOWN buttons, system’s Reactive Power (VAr) is displayed.
(Refer to: 5.14)

10.Over V. /VA Light : By pressing  SET button 3 seconds; you enter to Menu and Protection

of Capacitor Steps Against Over Voltage function is made by selecting
this light. (Refer to:5.9)

  In Automatic Mode when this light is selected by pressing UP and

DOWN buttons, system’s Apparent Power (VA) is displayed.
(Refer to: 5.15)

11.UP Button

: To move up in the Menu.

12.SET Button

: Enter button for different settings and values.

13.DOWN Button

: To move down in the Menu.

14.Automatic
     C/k Setting

: Automatical C/k adjustment is started by pressing UP and DOWN

buttons together at the same time. (Refer to:5.2)

15. C+ Light

: This light is ON when RG-6T switches capacitor steps on.

16. NORMAL Light : This light is ON when the targeted compensation is achieved.

17. C- Light

: This light is ON when RG-6T switches capacitor steps off.

18.Insufficient
     Compensation
     Light

: This warning light is ON when insufficient  compensation  occurs.

 (Refer to:6.1.2)

19.Over
     Compensation
     Light

: This warning light is ON when over  compensation occurs.

(Refer to:6.1.3)

20.Over Voltage
     Light

: This warning light is ON when over voltage  occurs. (Refer to:6.1.1)

21.K (Kilo) Light

: When this light is ON displayed value  must be multiplied by 1000.

22.M (Mega) Light

: When this light is ON displayed value  must be multiplied by 10

6

.

4. CONNECTION DIAGRAM

Warnings:
a) 
Connection of a circuit breaker between the network and the power supply

input of the device is highly recommended.

b) Circuit breaker must be in close proximity to the device.
c) Circuit breaker must be marked as the disconnecting device for the equipment.
d) All used fuses must be FF type and the current values of the fuses must be

2A, 3A and 6A.

POWER FACTOR CONTROLLER

RG-6T

1

2

3
4
5
6
7
8
9
10

13

15

16

17

18

19

21

OVER V.

W

VAr

VA

11

14

20

M

12

22

Phase-Neutral Connection*

Phase-Phase Connection*

15

16

17

18

19

20

21

22

23

24 25

26

27

28

N

L3

L2

L1

C1

C6

C7

C12

6 A

6 A

11

12

Alarm Relay

3 A

1

2

3

4

2 A

5

6

k

l

K

L

1

RG-6T

L1

1

2

3

4

5

6

7

8

9 10 11

12 13 14

N

L3
L2