Entes PS-722 Скачать руководство пользователя страница 2

Mounting (Figure 2)

- PS-722 can be mounted on DIN rails which comply with EN50022 standards.
- Mount the device vertically. When mounting the device, it is recommended that the DC output side stays 
on top side.
- Mind the device’s ventilation when mounting the device. After the mounting, it is recommended to leave a 
1 cm space between PS-722 and devices next to it.

4- Technical Properties:

Input

Nominal input voltage 

 

100-240 VAC / 130-320 VDC

Input voltage range 

 

85-265V AC / 110-350V DC

Frequency 

 

 

45-65 Hz / 0 Hz

Current consumption (@72W) 

0.8 -1.7A AC (±10%)

Inrush 

current 

  <20A

Internal 

fuse 

  3.15A

Estimated opening time after                  

Nominal Voltage   

 

<2 s 

(@220V AC - 72W)

Mains bufftering   

 

>20 ms  (@220V AC - 72W)

Transient surge

Voltage 

protection 

  Varistor

Line ragulation 

 

 

<1%  

(@24V DC) 

Output

Nominal output voltage 

 

24V DC (± 1% ) 

Output voltage range 

 

21.6 - 27.6V DC

Nominal output current 

 

3A DC (<55°C)

Maximum output current 

 

4A DC

Efficiency 

   >83% 

@85V 

AC

 

 

   >86% 

@265V 

AC

Residual fluctuation 

 

<30 mV @220V AC

Overload protection 

 

max. 4.4A  (@25°C, @220 VAC)

Short circuit protection 

 

Hysteresis turn off

Thermal protection 

 

>55°C 

Series 

connection 

  Yes 

Parallel connection  

 

Yes (by connecting ORing diode)

Load regulation 

 

 

< 1%

Indicators 

Output OK 

  

 

LED

General Information

Operating Temperature 

 

-20°C...+55°C  **  (Reduce load by 2.5% / °C over 50°C)

Humidity 

   <95% 

(@25°C)

Mounting Type 

 

 

Rail mount (EN 50022)

Rail mounting spaces 

 

1 cm horizontally, 5 cm vertically

 

 

 

 

 

(spacing between other devices)

Connection 

 

 

Terminals with fixed screws 

 

 

 

 

 

compatible with Phillips screw drives

Connection wire   

 

max. 12 AWG (4mm

2

) solid wire, 

 

 

   14 

AWG(2.5mm

2

) stranded wire 

Protection 

class 

  IP20

Pollution Degree   

 

Class 2

Overvoltage protection class  

3

Dimensions 

 

 

DIN4 (72*95*60) mm

Casing 

   Nylon 

6

Weight   

 

                  300 gr

Product Standards 

Product standard   

 

EN61204-1, EN61204-3,

 

 

 

 

    

EN61204-4, EN61204-7

SMPS transformer standard      

EN61558-1

Electric safety 

 

    

EN60950, EN61558-2-17

Insulation voltage (input/output)   

4 kV

Insulation resistance 

    

>5 MW (between input-output)

Surge voltage 

 

   

3 kV  Criterion A EN61000-4-5

Burst voltage 

 

  

4 kV  Criterion B EN61000-4-4

ESD 

Air discharge         

   

8 kV  Criterion A EN61000-4-2

Contact discharge   

  

4 kV  Criterion A EN61000-4-2 

Sag in input voltage  

  

(@220 VAC)

 

 

 

 

 

0% 20ms Criterion A EN61000-4-11

 

 

 

             

 

70% 500ms Criterion A EN61000-4-11

Other 

 

                  

EN61000 3-2, EN61000 6-2, EN55011, EN55022 

24V 72W Power Supply 

PS-722

! ATTENTION

This user manual contains information necessary for the safe and correct operation of the device. Before 
mounting the device, please read this user manual carefully and pay attention to warnings.

Safety and Warnings

! ATTENTION 

Do not open the device under any circumstances. An opened device’s warranty will become void.

! ATTENTION 

The device must be mounted only by qualified personnel with necessary precautions against 

electric shock in place. Incorrect connection may create dangerous result for people and environment. 
Incorrect connection may result in permanent damage to the performance of the device.
-  Before you energize the device or remove the device from mains, make sure that the supply cable isn’t 
connected to mains.
-  Supply input of the device must be connected according to EN60950 standards.

! A supply voltage greater than 265V AC may result in an explosion in the device or in damages to the user.

-  Device supply must be at a sufficient power capacity and must comply with security standards.
-  Cables connected to the outputs of PS-722 must be suitable for the maximum current that PS-722 can provide.
-  After device connection is finished, connection points must be protected against accidental contacts.
-  Mounting of the device must be done vertically as shown in Figure-1.

1- Introduction

1.1 Applications : 

PS-722 is a 72W high efficiency SMPS which was designed according to DIN case

standards for easy installation in panels. It can be safely used in industrial and building automation 
applications.

1.2 General Features :

-  Wide input voltage range 85-265V AC (50-60 Hz) / 110-350V DC

-  Adjustable DC output voltage 21.6 ...27.6V DC

-   72W output power (3A DC @24V DC)

-  Status notification LED

-  High efficiency operation     >86%

-   Low input voltage protection

-  Short circuit, overload protection

-  Thermal protection

-  Class 2 device, no earth connection is necessary

-  DIN4 case

-  IP20 Protection class
-  CE, EN 60950,EN 61204 

3

2

4

1

1- Input Voltage
2- DC Output
3- Setting Range of the Output Voltage
4- Output OK LED

1.3 Operation : 

The part of the device which is numbered as 1 in Figure-1 is the input voltage connection 

point of PS-722 and it is shown with L (Line) and N (Neutral) on the device body. Connect the supply voltage 
to these points. The part of the device which is numbered as 2 in Figure-1 is the DC output connection point 
of PS-722 and its polarity is shown  with + and - on the device body. PS-722 supplies adjustable DC voltage 
from these connection points. When supply voltage is applied to PS-722, the LED which is numbered as 4 
in Figure-1 will light up. When this is LED is lit, it indicates that PS-722 is working and it generates an output 
voltage. The part of the device which is numbered as 3 in Figure-1 is the DC voltage adjustment trimpot of 
the device. After the device has been energized, the output voltage is increased by turning the adjustment 
trimpot clockwise and is decreased by turning the adjustment trimpot is turned counterclockwise. This way, 
the output voltage can be adjusted in the specified range.The device will turn itself off to protect itself during 
cases of overload, overheating and shortcircuit at the output contacts. When the error state is resolved, it will 
activate itself automatically. (In case of thermal protection  power on reset is needed).

2- Block Diagram

2.1 Input (1)

- The part which is numbered as 1 in Figure-2 is the Line and Neutral supply inputs of PS-722.

- 100-240V AC input voltage can be connected by using the L and N terminals.

- 110-350V DC input voltage can be connected by using the L and N terminals.

- The device will turn itself off to protect itself during cases of overload, overheating and shortcircuit at the 
output contacts. When the error state is resolved, it will activate itself automatically.

2.2 Output (2)

- The part which is numbered as 1 in Figure-2 is the DC voltage output of PS-722.

- Positive and negative parts of the output voltage are shown with (+) and (-).

- Output voltage is 24V DC.

- Output voltage can be adjusted between 21.6-27.6V DC values by using the adjustment trimpot on the 

device.

- Device output is protected against short circuit.

- When the output is shorted circuited, device turns off completely and turns on again after the short circuit 

condition is resolved.
- The device can operate up to an ambient temperature of +55⁰C.*

PS-722 has LED indicator (Parts 4 in Figure-1).

- When there’s no energy : 

Output OK LED is off.

 

- Normal operation mode : 

Output OK LED is on.

- Short circuit : 

Output OK LED is off. If short circuit situation is resolved, the device starts to work again.

- Overload : 

If overload is drawn from device at normal temperature, Output OK LED turn off. The device 

makes blinks. When the load condition returns to normal, the device starts to opening again.

- Overh Overload : 

Device cuts the supply, doesn’t generate voltage.

- Overvoltage on Output : 

Output OK LED blinks.

3- Connection and Mounting

3.1 Wire Connection

-  AC Input (1): Under nominal load, PS-722 draws maximum 1.7A AC and minimum 0.8A AC. Wire thickness 
must be selected according to these values. Maximum 14 AWG stranded wire (2.5 mm

2

) or 12 AWG solid wire 

(4 mm

2

) can be connected to the input terminal.

- DC output (2): Output current is 3A DC. Wire thickness must be selected according to this value. Maximum 
14 AWG stranded wire (2.5 mm

2

) or 12 AWG solid wire (4 mm

2

) can be connected to the output terminal.

- In terms of complying with standards, use copper wires that can operate at 75

o

C.

ENTES Elektronik Cihazlar Imalat ve Ticaret A.S.

Adr:

 

Dudullu OSB; 1. Cadde; No:23 34776

 

Ümraniye - İSTANBUL / TÜRKİYE

Tel: 

+90 216 313 01 10 

Fax: +90 216 314 16 15

E-mail: 

[email protected] - [email protected]

Web:

 

www.entes.com.tr - www.entes.eu

Call Center Technical Support: 

0850 888 84 25

A7202/Rev.4

Figure-5