General

One of the common faults faced in industrial plants is over-heating and burning of
3 phase motors due to the phase failure. “Thermic-magnetic device” which is an
essential element in motor protection is generally too slow due to both its electro-
mechanical structure and the use of high current setting range to assure demarrage
without tripping. Being designed to eliminate the above disadvantages, MKC-03A
(with neutral connection ), MKC-04A (without neutral connection) Phase Failure
Devices react within 0.2 seconds (fixed) against the following faults and take the
motor out of service.

PHASE FAILURE and PHASE SEQUENCE DEVICES

MKC-03A, MKC-03L, MKC-04A

A4946 / Rev.2

Dimensions

PRECAUTIONS FOR INSTALLATION AND SAFE USE

Failure to follow those instructions will result in death or serious injury.
  Disconnect all power before working on equipment.
  When the device is connected to the network, do not remove the front panel.
  Do not try to clean the device with solvent or the like. Only clean the device
  with a dried cloth.
  Verify correct terminal connections when wiring.
  Electrical equipment should be serviced only by your compedent seller.
  Mount device to the panel.

Technical Data

Rated Voltage (Un)

: Please look at labels on the device.
: 3 phase and neutral 220-230 VAC
  4 wire star connection (for MK-03/03P, MKC-03/03A/03P)
: 3 phase 380 VAC
  3 wire delta connection 

(for MK-04/04P, MKC-04/04A/04P, MKC-03L)

                                       : 3 phase 220 V AC

  3 wire delta connection (for MKC-04/04P)

Auxiliary Supply Voltage : 190-260 V AC (for only MKC-03L)
Operating Range

: (0.9-1.1) x Un

Rated Frequency

: 50/60 Hz

Output Contacts

: 1 C/O with 8A, 250 VAC, 2000 VA, Cos

j

=1

  1 C/O with 0.5A, 125 V AC, 62.5 VA, Cos

j

=1 (for only MKC-03L)

Warning LEDs

: LED Output, normally ON (OFF for any fault)

                         

  *LED PTC turns ON when motor winding temperature exceeds 110 

o

C

Tripping Time

: 0.2 s

Ambient Temperature :-5 °C to +50 °C
Protection Class

: IP 20

Dimensions

: Type PK 25 (MKC-03A, MKC-03L, MKC-04A)
  Type PK 28 (MKC-03A, MKC-04A)

Installation

: Surface mounting or on the

                                  

  mounting rails

Weight

: 0.2 kg

Terminal Cable Crosssections: (for PK-28)

4mm² (12AWG) solid conductor
6mm² (10AWG) stranded rigid conductor
2x2.5mm² (14AWG) solid conductor

(for PK-25)
4mm² (12AWG) solid conductor
2,5mm² (14AWG) stranded rigid conductor
2x1,5mm² (2x16AWG) solid conductor

Function Diagram

Fixed unbalance value

Hysterisis

L1

L2

L3

Output Relay

TD = Tripping time

TD

TD

Wrong Phase sequence

2. Phase Sequence

When the phase sequence is correct (L1, L2, L3 in clockwise direction) the output

relay is activated; however, if the sequence is changed by any reason, the output

relay switches OFF immediately.

The voltage asymmetry causes the rise in motor temperature and a reduction of
the rated motor power.

1. Voltage Unbalance (Not Adjustable)

MK-04 includes no neutral connection.

When the neutral-phase voltage unbalance is greater than 40% (fixed), the output

relay is activated and switched OFF the motor. Devices that have fixed voltage

unbalance between 5%-15% can be producted for special order.

Unbalanced voltage may occured when;

    The mains are loaded with unbalanced distribution,

    One of the 3-phase of motor has lost. In this case, some amount of voltage which

produced by other phases will be inducted on the lost phase. Amount of this value

depends on both the motor type and amount of load.

   Output relay is activated when a phase has lost or an unbalanced phase-neutral

value, which is occured with any reason, is smaller than the Asymetrical value which

is defined for the device. If this unbalanced voltage exceeds the adjusted Asymetrical

value, output will release itself and motor will be Switched-off.

    In Applications; a proper device must be used regarding to the inducted voltage

value in two-phase which are remained after the other one has lost.

No responsibility is assured by the manufacturer or any of its subsidiaries

for any consequences arising out of the use of this material.

TYPE PK28

48 mm

34 mm

90 mm

35.3 mm

59.7 mm

45.4 mm

61.8 mm

36 mm

TYPE

 PK25

35 mm

90 mm

45 mm

62 mm

58 mm

32 mm

48 mm

35 mm

Connection Diagrams PK-25

Connection Diagrams PK-28

Vin (L-L)

L1

L2

L3

L1

L2

L3

Un

1 2 3

A1

A2

A2

A1

NC C NO

(0.5 A, 125 V AC)

MKC-03L

L1

L2

L3

L1 L2 L3

Sistem

N

MKC-04A

1 2 3

T1

M

3 ~

C1

T1

Stop

T1

N

M

3 ~

Start

L1
L2
L3
N

C1

L1 L2 L3

MKC-03A

1 2 3

N

T1

Stop

Start

C1

C1

T1

Stop

T1

N

M

3 ~

Start

L1
L2
L3
N

C1

3

2

1

N

L1

L2

L3

MKC-03A

1 2 3

L1 L2 L3

L1

L2

L3

System

N

T1

M

3 ~

MKC-04A

T1

Stop

Start

C1

V

Ref

V

Ref

= 380 VAC

x 100

asymmetry % =

-

V

L12

V

L31

L31

L12

V

L23