Entes EVM-05C Скачать руководство пользователя страница 2

2

VOLTAGE MONITORING

EVM-05C

SP Menu (Set points)

    

‘‘High’’ Setpoints can be adjusted for each phase-neutral or

phase-phase voltages separately.
If the voltage of phase-neutral or phase-phase is under the high
set value (Hi),output 1 relay is not activated,output 1 LED is on
and Hi LEDs are off.
If any voltage of the phase-neutral or phase-phase exceeds the
high set value, Hi LED blinks, output 1 relay activates at the end
of adjusted time(Hi Ond), Output 1 LED turns off and Hi LED turns
on continously.
If all phase-neutral or phase-phase voltages are below the high
set value (Hi) as a hysteresis(Hi Hys), output 1 relay releases at
the end of the adjusted time (Hi Ofd), output 1 LED turns on and
Hi LED turns off.

Specific Functions of Buttons:

While the device shows the Instantaneous value, pressing:

:Displays max. Voltage value set .

:Displays min. Voltage value set.

SET

+

SET

+

If the Latch function is selected ON, relay activates when the
value exceeds the adjusted value.Even if the voltage is below
the set value, output relay remains activated until pressing
these buttons at the same time.

ESC

+

Provides transition between VL-L and VL-N voltages.

:Displays max. Phase-phase voltage, while VL-L
 LED is on.
 Displays max. Phase-neutral voltage, while VL-N
 LED is on.

:Displays min. Phase-phase voltage, while VL-L LED
is on.
Displaying min. Phase-neutral voltage, while VL-N
LED is on.

General Information

Low Set points can be adjusted for each phase-neutral or phase-
phase voltages separately.
If the voltage of phase-neutral or phase-phase is over the low
set value (Lo),output 2 relay is not activated,output 2 LED is on
and low LEDs are off.
If any voltage of the phase-neutral or phase-phase is under the
Low set value, Low LED blinks,output 2 relay activates at the
end of adjusted time(Lo Ond),output 2 LED turns off and low
LEDs turn on continously.
If all phases-neutral and phase-phase voltages are over the low
set value (Lo) as a hysteresis(Lo Hys), output 2 relay releases
at the end of the adjusted time (Lo Ofd), output 2 LED turns on
and Low LEDs turn off.

       Low Voltage values are adjusted for each phase and phase-
phase voltages separately.However  Lo Hys(hysteresis), Lo
ond(delay time) and Lo ofd  are same values for all phase-neutral
and phase-phase voltages.

When the connection type of  system is entered, Lo L-1,Lo L-2
Lo L-3 and Lo Hys values change automatically according to the
new connection.

 Lo Hys:10 V, Lo L-1:180 V, Lo L-2:175 V, Lo L-3:170 V is
adjusted in star connection.If the connection type is changed
to the delta connection, the device calculates these values as
phase-phase voltage.

Lo L-1: L1-L-2 phase phase voltage:311 V
Lo L-2: L2-L-3 phase phase voltage:303 V
Lo L-3: L3-L-1 phase phase voltage:294 V
Lo Hys :17 V

Hi Hys:10 V, Hi L-1:250 V, Hi L-2:255 V, Hi L-3:260 V in star
connection.If the connection type is changed to the delta
connection, the device calculates these values as phase-
phase voltage.

Hi L-1: L1-L-2 phase phase voltage:433 V
Hi L-2: L2-L-3 phase phase voltage:441 V
Hi L-3: L3-L-1 phase phase voltage:450 V
Hi Hys :17 V

      

High Voltage values are adjusted for each phase-neutral

and phase-phase voltages separately. However  Hi Hys(hysteresis),
Hi ond(delay on time) and Hi ofd (delay off time) are same values
for all phase and phase-phase voltages.
When the connection type is set, Hi L-1,Hi L-2, Hi L-3 and Hi Hys
values change automatically according to the new connection.

EVM - 05C is designed to measure the phase-phase voltage, phase-
neutral voltage  and the frequency of system.
It contains 2 output relays to warn the user against under/over voltage
and frequency.
Out 1 relay changes position according to the max.voltage or
max.frequency value set.
Out 2 relay changes position according to the min.voltage or min.frequency
value set.
The device contains the features of Instantaneous trip, Latch function
and adjustable delay time.
Network connection can be used with neutral or without neutral by
selecting 

star

 or 

delta connection

 in setup menu.

Application of EVM-05C

1-)

 It can measure voltage for each phase and frequency in 3 phase 

systems with neutral and without neutral.

2-)

 You can observe the existence of phases by following the L1-L2-L3

 

LEDs on the device.

3-)

 Min and max. values measured are recorded and displayed.

4-)

 It warns the user through Output 1 and Output 2 relays when the 

measured voltage and frequency values exceed the set value.

5-)

 It warns the user through Output 2 relay and LED caution by turning

on and off when there is a false phase sequence,

6-)

 Voltage transformer ratio can be adjusted between 1 … 4000.

7-)

 A password can be arranged from pin menu in order to prevent 

change of the setting by unauthorized person.

Note:

Example:

Note:

Example:

The voltage value for set points can be adjusted 0…300 V in
star connection and 0...500V in delta connection

If the set point value is set to zero (0) for any phase, the
warning is cancelled for the related phase.

Note:

SP Hi Menu (High Setpoint)

SP Lo Menu (Low Setpoint)

Содержание EVM-05C

Страница 1: ...ury Disconnect all power before working on equipment When the device connected to the network do not remove the front panel Do not try to clean the device with solvent or the like Only clean the devic...

Страница 2: ...connection Lo Hys 10 V Lo L 1 180 V Lo L 2 175 V Lo L 3 170 V is adjusted in star connection If the connection type is changed to the delta connection the device calculates these values as phase phas...

Страница 3: ...ase in delta connection The voltage value can be adjusted 0 300 V in star connection and 0 500 V in delta connection If the value is set to zero 0 the low voltage warning is cancelled The max voltage...

Страница 4: ...one until SAU SEt yES is displayed Press SET button while SAU SEt yES is displayed SET Enter 3rd digit value by scrolling UP DOWN buttons If you set 3rd digit value incorrect you can set again by pre...

Страница 5: ...the end of the adjusted delay time Frq Ofd The hysteresis value can be adjusted 0 20 Hz The frequency of the system is measured from L 1 If the frequency of system is under the high set value Frq Hi o...

Страница 6: ...ttons If you set 3rd digit value incorrect you can set again by pressing ESC button Press SET button SET Enter decimal digit value by scrolling UP DOWN buttons If you set decimal digit value incorrect...

Страница 7: ...TEM Con The menu that is selected the connection type of system Two connection type is defined in the device If the system is 3 phases with neutral we should select the Star connection If the system i...

Страница 8: ...ET button for 3 secs Find Pin menu by scrolling UP DOWN buttons Press SET button Pin Act is displayed SET SET SET SET Press SET button Enter 1st digit value by scrolling UP DOWN buttons If you set 1st...

Отзывы: