Device Connection
Make the MODBUS connection of the device and make the Ethernet connection. The device’s
supply voltage range is 85-265 VAC/DC. Supply the device with a suitable voltage within the supply
range.
PC
Micro USB
Ethernet
85-265 VAC / DC
Digital I/O
RS-232
RX TX
RS-485
A(+)B(-)
GND
LED Indicators
Status LED
Red - On:
The device is energized but IP has not been received yet, so you will not be able to access
the WEB interface.
Green - ON:
The device is energized and IP has been received. You could connect to the WEB
interface.
White Flasher:
Reset factory settings (In progress)
Yellow - ON:
USB connected.
Red and Blue Sequential Flasher:
Device has malfunction. Please contact ENTES Customer Service.
Ethernet LED
ON:
Connection is ON
Flasher:
Connection is ON, communication is available.
OFF:
Connection is OFF
Digital Input LED
ON:
Digital input ON
OFF:
Digital input OFF
Digital Output LED
ON:
Digital output ON
OFF:
Digital output OFF
Setting Interface
In order to configure the device settings from the web interface, it must be connected to the
computer with a micro USB cable. Then you could access the interface via http://usb.entes or
192.168.7.1. The device’s password is the last 4 digits of the MAC ID. You could check the device’s
connection status to GSM on this interface.
Attention
• Modbus adresses of all devices connected to the modem must be different from each other and
the serial port settings must be same. (Baudrate, parity, data bit, stop bit)
• Make sure the accuracy of serial communication line terminals (A-B-GND) between the data
receiving devices and the device..
• Energized ETMO-02 models do not allow to read any address other than the first two different
addresses.
• Make sure the IP settings of the device are suitable for your network structure (subnet mask,
gateway address, DNS, IP address).
• If there is any firewall at your network, make sure the communication port (502 or 700) is available.
IT Instructions:
Share this information with your IT authorized or technical personnel responsible for internet access.
If you wish to access any ENTES service via static IP address by your internet provider (TCP server,
static IP communication);
Give access authorization over default port 502 or the relevant port you configured.
Interface
Operating Range
Supply
85-265 VAC/DC
Digital Input
5-30 VDC
Digital Output
5-30 VDC