8. Device Settings
EMK-01 device can be configured from panel screen for most of essential parameters. All settings
available at the device screen and several others are available also in software. In this chapter the
settings of the device will be completed by appropriate settings via software.
Settings
00:30
01.01.2000
English
- >
- >
- >
- >
- >
- >
At main screen, move to parameter Settings to access device various configuration sub-menu.
Some of the device parameters and functions can be enabled and configured only by PC and
software.
8.1. Language
Default language of EMK-01 is English. Select the appropriate language from the list and confirm
it. Device menu will turn immediately to the selected language.
8.2. Measurement – Main Parameters
All settings related to measuring circuits connection type, measuring transformers and type of
parameter calculation are adjusted in Measurement setting.
Measurement
00:30
01.01.2000
Connection type
Frequency
Rated voltage
Rated current
Ripple control
Voltage transformers
Current transformers
Flicker
Erase Max/Min
Averaging
Averaging period
4UN_4I
50Hz
230V
5A
- >
230V:230V
5A:5A
230V - 50 Hz
Static Window
5s
Parameter
Description
Factory setting
Setting range
Connection type
Defines the type of network and measuring circuit connection
4UN_4I
Chapter 8.2.1
Frequency
Defines the nominal system frequency
50 Hz
45 ... 75 Hz
Rated voltage
Network nominal phase voltage
230 V
1 V ... 750 kV
Rated current
Network nominal phase current
5 A
1 A ... 750 kA
Ripple control
Adjustable by software
50 Hz
50 Hz ... 3 kHz
Voltage Tr.
Primary and secondary voltage of measuring voltage transformer
230 V / 230 V
1 ... 750 kV
Current Tr.
Primary and secondary current of measuring current transformer
5 A / 5 A
1 ... 750 kA
Flicker
Settings of the nominal voltage and frequency for flicker calculation
230 V – 50 Hz
120/230 V, 50/60 Hz
Erase Max/Min
Deletes all saved maximum and minimum of measured parameters
No
Yes / No
Averaging
Type of averaging period
Static
Static / Sliding
Averaging period
Time for averaging period setting
5 s
1 ... 3600 s