5. Electrical connections

The voltage and current ratings including cable sizes must comply with national regulations. 

The system dimensioning must be done by a qualified electrical designer.

A combined device with residual current circuit breaker and over current protection (RCBO) is 

integrated.

A label set of RCBO testing instructions is included in the delivery. Attach a language specific 

label on the installation box hatch.

6 8

7

L

N

L

N

QF1

PE

P1

The default setting for the earthing system is TN network.

Do not connect Ensto One Apartment chargers to an IT network.

Supply 

Cu 2.5 - 10 mm²

EVH161-ACRM0 / EVH321-ACRM0

• 

Fixed charging cable

EVH161-A2RM0 / EVH321-A2RM0
EVH161-ASRM0 / EVH321-ASRM0

• 

Separate charging cable

PE

L N

TN network

5.1. Power supply

Содержание One Apartment EVH161-A2RM0

Страница 1: ...ENG Ensto One RAK132_ENG 6 4 2021 2020 Ensto Installation Manual...

Страница 2: ...A2RM0 EVH161 ASRM0 EVH321 ASRM0 internal circuit example 20 14 EVH161 A2RMD internal circuit example 21 15 EVH163 A2RM0 EVH323 A2RM0 EVH163 ASRM0 EVH323 ASRM0 internal circuit example 22 16 Dimension...

Страница 3: ...rovided in this Installation Manual in no way exempts the installer or user from responsibility to follow all applicable safety regulations This Installation Manual is a part of the product and must b...

Страница 4: ...k Separate charging cable not included 3 Charger features Available features depend on the charger model Mode 3 Type 2 socket with protective flap Plug holder Fixed charging cable 4 color LED indicate...

Страница 5: ...on Remove the charger from its package Do not scratch the surface of the charger after removal from the package When selecting installation site take into account the following The charger is suitable...

Страница 6: ...cable is pre assembled on the bottom of the charger If you need to open additional cable entries you have to disassemble the charger Installation steps when cable routing is from alternative cable en...

Страница 7: ...t for cable 8 17mm RMM32B Membrane gasket for cable 12 24mm 2 Open the needed cable entries with a step drill bit 3 Prepare the cable entries with suitable accessories 4 Remove the included cable glan...

Страница 8: ...erial suitable screws 2 Fasten the upper screw 1270 mm measured from the ground surface The plug holder will be at a height of 1200 mm 4 3 Wall mounting When selecting the installation location make s...

Страница 9: ...ncluded 3 EVH161 ACRM0 EVH321 ACRM0 Be careful not to damage the fixed charging cable 7 Pull the electrical cables approx 150mm through the cable glands 8 Cut the supply cable leads in suitable length...

Страница 10: ...nt protection RCBO is integrated A label set of RCBO testing instructions is included in the delivery Attach a language specific label on the installation box hatch 6 8 7 L N L N QF1 PE P1 The default...

Страница 11: ...1 A2RMD Separate charging cable Domestic socket Supply Cu 2 5 10 mm EVH163 A2RM0 EVH323 A2RM0 EVH163 ASRM0 EVH323 ASRM0 Separate charging cable Note Connect these charger models to a 3 phase supply ot...

Страница 12: ...n also make changes to the settings with Ensto Charger Control Application You can download the application from Google Play or App Store Please see instructions in chapter 21 Ensto Charger Control Ap...

Страница 13: ...pen your EV Manager in a web browser Google Chrome or Firefox 2 Select the charger you want to change to Authorized operating mode Note The charger must have connection to the internet 3 Select Edit t...

Страница 14: ...torque 2 2 4 Nm PE tightening torque 2 5 3 0 Nm Additional Electric Features EVH161 A2RMD Domestic socket Output current 10 A Electricity is not available if the charging cable is connected to the ch...

Страница 15: ...5m Mode3 Type 2 socket Mode3 Type 2 socket Charging sta tus indication 4 color LED Green Ready Blue Charging Red Error Yellow Internal maintenance Use access Free access RFID ISO IEC 14443A ISO IEC 15...

Страница 16: ...Not available D Domestic socket Not available M MID class kWH meter Not available R RCBO Fixed charging cable 2 Type 2 socket T2 S Type 2 Shutter socket T2S Home A Apartment 1 phase 3 3 phase Max cha...

Страница 17: ...Charger s power supply capacity meets electrical planning cable size protective devices Review local electrical design plan The PE cable screw is tight The power supply conductors L1 L2 L3 N and PE ar...

Страница 18: ...color green blue red are functioning Use a car simulator Create fail and charge Red at bootup green at idle and blue while charging Make sure the PE cable screw is tight Test that the voltage between...

Страница 19: ...ENG 6 4 2021 19 32 12 EVH161 ACRM0 EVH321 ACRM0 internal circuit example Note All signal wires must be at a sufficient distance from the power wires or protected with insulating shield plastic spiral...

Страница 20: ...20 32 13 EVH161 A2RM0 EVH321 A2RM0 EVH161 ASRM0 EVH321 ASRM0 internal circuit example Note All signal wires must be at a sufficient distance from the power wires or protected with insulating shield pl...

Страница 21: ...RAK132_ENG 6 4 2021 21 32 14 EVH161 A2RMD internal circuit example Note All signal wires must be at a sufficient distance from the power wires or protected with insulating shield plastic spiral Supply...

Страница 22: ...22 32 15 EVH163 A2RM0 EVH323 A2RM0 EVH163 ASRM0 EVH323 ASRM0 internal circuit example Note All signal wires must be at a sufficient distance from the power wires or protected with insulating shield pl...

Страница 23: ...n is off no lights on Issue Corrective action Mains voltage does not exist in the supply connectors L1 L2 L3 Ensure proper power supply The circuit breaker QF1 is off Turn the QF1 on 16 Dimension draw...

Страница 24: ...disposed of properly according to local recycling guidelines The charger s cardboard packing is suitable for recycling Dispose of the plastic wrap with the household waste or according to local recycl...

Страница 25: ...h technology is used for the wireless connection You can pair your mobile device to several chargers but it can be connected only to one charger at a time The range in free space is approximately 5m 2...

Страница 26: ...ces 5 Select from Available Devices the charger you want to pair with your mobile 6 If the pairing fails the first time try again starting from step 1 7 When the pairing is completed you can find your...

Страница 27: ...letter E on the ENSTO logo for a long time In the installer menu available features depend on the charger model 21 3 1 Self test The charger performs a self test automatically at start up During the...

Страница 28: ...m only if it is absolutely necessary When the Dynamic Host Configuration Protocol DHCP is not used please consult your local IT network administrator in case you have any questions NTP Network Time Pr...

Страница 29: ...gistrate in https www research net r 25YZMS8 lang en 21 3 8 Offline current The maximum charging current in case the connection to the Dynamic Load Management DLM server is interrupted 21 3 10 Overcur...

Страница 30: ...device RCBO Turn on the protection device RCBO If the error occurs again contact service E07 The charger was unable to identify the current carrying capacity of the charg ing cable The charging cable...

Страница 31: ...ripped the system s protection device RCBO Turn on the protection device RCBO If the error occurs again contact service E19 The vehicle has performed an opera tion that is not supported by the charg e...

Страница 32: ...e n s t o c o m Ensto Chago Oy Ensio Miettisen katu 2 P O Box 77 FIN 06101 Porvoo Finland Tel 358 204 76 21...

Отзывы: