  Functional tests

     

A )  Use the ITK to check if the RSD is working as desired. When the RSD is 

engaged (turned to OFF position) , all the relays except the MID will be 

open. Only the MID relay will be closed. Hence effectively isolating the 

home from the PV, battery and generator. 

B )  In order to check if the RSD is functioning as required, open the ITK 

and manoeuvre to the Enpower page.

C )  Turn the RSD rotary handle to OFF position. 
D )  In the ITK’s Enpower page, click on  “View Live details”.
E )  In the view live details page, the relay status should be as shown in 

Figure 6 below. The MID relay should be closed and all other relays 

should be in open position.

F )  When RSD handle is shifted to ON position, the Enpower goes back 

into functioning normally as it was.

6

Figure 6: ITK checking of Relay status 

  Instructions for initiating Rapid Shut down and 

Enpower System shut down

     

       Rapid shut down of the system can be initiated by turning the handle 

of the RSD to the OFF position. With this one step the entire Enphase 

system (PV arrays , Encharge battery, Generators connected to 

Enpower)  is shut down and the regulatory requirement for rapid shut 

down are also met.

       NOTE: 

For more details of the RSD switch options and wiring instruc-

tions, please refer to Enpower R2 QIG or the Ensemble R2 design guide

8

  Complete the installation by affixing the labels

     

A )  In order to identify the Rapid shut down switch the following label (in 

Figure 7) needs to be pasted at a distance of not more than 3ft (1m) 

from the RSD, as mandated by the NEC code. 

7

Figure 7: Label for identifying the RSD 

Figure 8: Sticker for showing portions of PV array which will be shut down using RSD

I/O - 1

(24V, 1A)

I/O - 2 

(24V, 1A)

Gen - I/O

(24V, 1A)

NO1 NO2

NC1 NC2

NO3

RSD 

NC3 NC4

AC Combiner 

PV/Storage

Generator

B )  In order to earmark the parts of the array which will be shut down 

by using the RSD the following sticker (Figure 8)  needs to be pasted 

in the location specified by the Authority having jurisdiction or at a 

distance of not more than 3ft (1m) from from the RSD, as mandated 

by the NEC code.

Dry Contact Terminals

RSD Terminals to 

be connected

NC3

     Terminal 1

           Terminal 1

     Terminal 2

           Terminal 2

NC4

     Terminal 1

           Terminal 3

     Terminal 2

           Terminal 4

Figure 5: Connecting wires from RSD and Enpower

MID

EC1 L1

EC1 L2

NFT L1

NFT N

Closed

Open

Open

Open

Open

Cable Header  

Assembly 

(refer Fig 2a)

12 AWG 

wires

Содержание EP200G-NA-02-RSD

Страница 1: ...F Repeat steps D and E to complete wiring of other 3 terminals of NC3 and NC4 2021 Enphase Energy All rights reserved Enphase the Enphase logo Enpower smart switch Encharge storage system Envoy Combiner Microinverter Installer Toolkit Enlighten and other trademarks or service names are trademarks of Enphase Energy Inc Data subject to change 10 18 2021 2 1 200 5 15 5 1 2 3 SEE NOTE 6 COLOR RING STE...

Страница 2: ...the RSD A Identify a location which is near the Enpower smart switch to mount the RSD Please note that Enpower and RSD cannot be more than 200 ft apart B There are 2 mounting points on the back plate of the enclosure They are marked by red boxes in Figure 4 below C Installers can use any type of mounting as long as they are not exceeding the diameter of each fixing point D It is recommended that i...

Страница 3: ...s shut down and the regulatory requirement for rapid shut down are also met NOTE For more details of the RSD switch options and wiring instruc tions please refer to Enpower R2 QIG or the Ensemble R2 design guide 8 Complete the installation by affixing the labels A In order to identify the Rapid shut down switch the following label in Figure 7 needs to be pasted at a distance of not more than 3ft 1...

Страница 4: ...e only with the IQ Envoy or Envoy S metered communications gateway properly fitted with USB hub USB radios and production and Consumption PCS CTs The Envoy is required for operation of the Enpower Earlier versions of the Enphase Envoy commu nications gateway are incompatible NOTE The Enphase Enpower is intended to operate with an Internet connec tion through the Envoy Failure to maintain an Intern...

Отзывы: