Section 15
00-02-0831
2013-03-21
-
7 -
Installation of the Volume Cell
Install the volume cell with reference to the level at which you wish the pump to start and stop.
Secure the volume cell with a substantial bracket that will not allow the cell to float or tilt when
the water level rises. Install the DF755 well above the highest water level and in a position that
allows access for adjustment or repairs.
NOTE: Periodically operate the pump manually until the water level
reaches a point approximately ½ in (13mm) below the bottom of the
Volume Cell. This automatically recharges the unit, and compensates for
normal absorption of air into water. Small electric air pumps are available
to automatically charge the system continuously.