TOC1207NUEN_0512

 

                                               2/4 

 

 

 

  

Observe the following points: 
• The laws, standards and directives in force. 
• Best practice at the time of installation 
• The device operating manual. 
• An operating manual can only give general instructions. They must be interpreted in the context of 
a specific installation. 
  
The device is intended solely for use conforming to its purpose. Any repairs or modifications by the 
user  are  forbidden!  Do  not  use  with  other  devices  the  operation  of  which  could  endanger  people, 
animals or property. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

Note:

 

The signal strength between the transmitter and the receiver decreases as the distance 

increases. Where there is a line of sight connection, the range is approximately 30 m in corridors 
and 100 m in large workshops or halls. The range can be increased with an 

0

2

LINE

 repeater.

 

 
 
 

General characteristics

 

Transmission frequency

 

868.3 MHz

 

Transmission power

 

10 mW max.

 

Storage temperature

 

From -20°C to +60°C

 

Illumination

 

>100 lux on average per day

 

Conformity

 

CE

 

Degree of protection

 

IP 40 on its base

 

Range in buildings

 

Masonry

 

20m, through 3 walls at most

 

Reinforced concrete

 

10m, through 1 wall/ceiling at most

 

Plasterboard / wood

 

30m, through 5 walls at most

 

 2. Safety 

 3. Technical characteristics 

Measurement range

 

from 0°C to +40°C

 

Measurement accuracy

 

+/-0.5°C from +15°C to +25°C

 

Measurement resolution 

0.16°C

 

Temperature

 

Relative humidity

 

Measurement range

 

from 5 to 100% without 

 

Measurement accuracy from 0 to 

 

+/-5% from 30% to 70%

 

Measurement resolution 

0.4%

 

TOC1207NUEN_0512

 

                                               3/4 

 

  

  

The  sensor  is  supplied  on  a  base  which,  once  installed,  allows  a  learn  process  to  be  carried  out 
close  to  the  matched  receiver  by  separating  (using  a  small  screwdriver  to  depress  the  clips)  the 
sensor from the base; the base remaining in position. 

 

             
            Base clip 

 
 

              

 

    

4.1 Installation instructions: 

       

 Never  mount  the  sensor  in  a  metallic  casing  or  close  to  a  largely  metallic  object. 
Installation on the ground or close to the ground is not recommended 

  

  The  sensor  must  be  positioned  so  that  air  can  circulate  freely  around  it  and  within  an  area 

representative of the temperature and humidity to be measured. 

  Secure the base by gluing or screwing. 

  Place the sensor on its base until it engages. 

  

4.2 Initial use: 

        

The  devices  are  supplied  in  an  operational  state  but  will  probably  require  recharging,  following 
storage of the radio sensors in the dark.  

  Prior to first use, charge the sensor's power reserve using light with an illuminance of at least 

200 lux for 5 minutes or more. 

  Ensure that averaged across the day, the mean illuminance is 100 lux/d. 

  The sensor's operating power reserve (when fully charged) in conditions of total darkness is 4 

days. 

     

Note: The device is designed for interior use. Do not install it in locations that could be sprayed by 
water! To clean, use a damp cloth! 

  

   

 

   

10020041.xx  sensors  transmit  the  measured  temperatures  using  the  frame  described  in  the 
document Enocean Equipment Profiles EEP2.1 §A5-04-01 (consultable under 

www.enocean.com

). 

   

5.1Temperature and relative humidity measurement 

Temperature and humidity are measured every 100 seconds. A signal is sent if a change exceeds 
+/-0.5°C for the temperature or +/-2% for the humidity. 
If changes remain below this level, temperature and humidity are transmitted approximately every 
15 minutes.

 

    

 

 

5.2 Programming and LRN button:     

                          

Located  behind  the  sensor,  pressing  the  LRN 
button  causes  the  sending  of  a  frame  used  to 
identify or associate a matched receiver. 
Where  the  sensor  is  located  on  its  base,  it  must 
first  of  all  be  unclipped  from  the  base  to  allow 
access  so  that  it  can  be  placed  closed  to  the 
matched  receiver  during  the  identification  or 
association  phase  (the  receiver  having  reduced 
sensitivity during this phase). 

78 mm 

25 mm 

LRN button

 

 4. Installation and initial use 

5. Controls and functions 
ion and initial use

 