USER MANUAL
STM 550 / EMSI
–
ENOCEAN MULTISENSOR FOR IOT APPLICATIONS
© 2020 EnOcean | www.enocean.com F-710-017, V1.0
STM 550 / EMSI User Manual | v1.3 | September 2020 | Page 62/97
9.5.14
THRESHOLD_CFG2
STM 550 can reduce the reporting interval based on the acceleration sensor status and the
magnet contact status as described in chapter 2.3.
The use of these reduced reporting intervals is enabled by the THRESHOLD_CFG2 register
shown in Figure 41 below.
THRESHOLD_CFG2 (Default: 0x00)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
RFU
MC SENSOR
ACC SENSOR
Figure 41
–
THRESHOLD_CFG2 register
The encoding used by the ACC SENSOR bit field is shown in Table 23 below.
ACC SENSOR
Reporting interval reduction based on acceleration
0b00 (Default)
Disabled (No reporting interval reduction)
0b01
Reserved (Do not use)
0b10
Enabled, Reporting interval reduction if acceleration above threshold
0b11
Reserved (Do not use)
Table 23
–
ACC SENSOR bit field encoding
The encoding used by the MC SENSOR bit field is shown in Table 24 below.
MC SENSOR
Reporting interval reduction based on magnet contact status
0b00 (Default)
Disabled (No reporting interval reduction)
0b01
Enabled, Reporting interval reduction if contact is open
0b10
Enabled, Reporting interval reduction if contact is closed
0b11
Reserved (Do not use)
Table 24
–
MC SENSOR bit field encoding