9.5.32
MAGNET_CONTACT_TX_INTERVAL
If magnet contact-controlled reporting has been enabled and the magnet contact state
matches the state configured in the THRESHOLD_CFG2 register then the resulting reporting
interval will be determined by the register MAGNET_CONTACT_TX_INTERVAL shown in Fig-
ure 64 below.
MAGNET_CONTACT_TX_INTERVAL (Default Setting: 0x003C)
Bit 15
Bit 14
…
Bit 1
Bit 0
MAGNET CONTACT INTERVAL
Figure 64
–
MAGNET_CONTACT_TX_INTERVAL register
The encoding used by the MAGNET CONTACT INTERVAL bit field is shown in Table 49 be-
low.
MAGNET CONTACT INTERVAL Magnet contact-based reporting interval
0x0000, 0x0001, 0x0002
Not supported (Do not use)
0x0003
3 seconds (minimum setting)
…
…
0x003C (Default)
60 seconds (default setting)
…
…
0xFFFF
65535 seconds (maximum setting)
Table 50
–
MAGNET CONTACT INTERVAL bit field encoding
The default reporting interval when the magnet contact state meets the defined state is 60
seconds. This can be reduced according to user requirements keeping in mind the energy
balance.