ENMET CP-60 Скачать руководство пользователя страница 8

CP-60

 

 

ENMET  

5

 

 

3.4 Sensor/Transmitter Connection 

Sensor/Transmitters are connected to the 

CP-60

 control unit with two or three-conductor wiring, use the correct oiltight fitting.  

Size of wire depends on the distance between the sensor/transmitter and the control unit. 

See Recommended Wire Gauge Table below. 

2 Wire for Sensors/Transmitter 

 

3 Wire for Sensors/Transmitter 

Position 

Function 

Position 

Function 

1, V+ 

Power +24 

V

DC

 

1, V+ 

Power +24 

V

DC

 

2, G 

Not Used 

2, G 

Power Ground 

3, Sig 

Signal/Return to Ground 

3, Sig 

Signal 

 

Recommended Wire Gauge 

Distance from Sensor to Control Unit 

Recommended Wire Gauge 

5000 feet 

24 AWG 

Greater then 5000 feet 

Contact Factory 

 

N

OTE

: Sensor Location 

Gases have different densities.  Some are heavier than air and concentrate at the bottom of a space.  Some are lighter than air 
and gather at the top.  Consider the density of the gas you want the sensor to detect when you install the sensor.  Some 
examples are given below. 

Heavier than Air Gas 

Sensor Location 

Bottled LP (liquefied petroleum) 

Interior wall; 18-24" from floor. 

  D

N

OT

 

locate directly above or beside gas appliances (ovens, 

heaters). 

 

Avoid locating anywhere near a vent or window or near an outside 
doorway. 

Propane 
Butane 
Gasoline 
Trichloroethylene 
Vaporized hydrocarbons 
Hydrogen sulfide 

Lighter than Air Gas 

Sensor Location 

Natural gas (methane) 

Near ceiling. 

  D

N

OT

 

locate directly above appliances where it is subject to direct 

exposure to heat or steam. 

Ammonia 
Hydrogen 

Same Density as Air Gas 

Sensor Location 

Carbon Monoxide 

4-6 feet above the (generally uniform) floor. 

  D

N

OT

 

locate in direct air currents of windows, doors, or vents. 

If you have a question involving the location of a unit or sensor, please contact your distributor or 

ENMET

 personnel.  A 

technician will analyze the question and recommend a location. 

 

Содержание CP-60

Страница 1: ...ENMET PO Box 979 Ann Arbor MI 48106 0979 www enmet com Manual Part Number 80003 501 MCN 423 07 15 09 CP 60 OPERATION AND MAINTENANCE MANUAL...

Страница 2: ...utputs 7 4 0 Operation 8 4 1 Normal Operation Condition 8 4 2 Alarm Conditions 8 4 3 Alarm Latching 8 4 4 Audio Defeat 8 4 5 Display 9 4 6 Operational Menu 9 4 7 Fault Indications 9 5 0 Maintenance 10...

Страница 3: ...on Menu Flow Chart 9 Figure 8 CP 60 Maintenance Menu Flow Chart 10 List of Tables Table 1 Relay Factory Default Failsafe Settings 7 Table 2 Default Relay Links 14 Reference Information NOTE important...

Страница 4: ...d Keep the items packing material and carton As Is Within 5 days of receipt notify the carrier s local office and request immediate inspection of the carton and the contents After the inspection and a...

Страница 5: ...CD with backlight The numerical values of gas concentrations and other information are displayed Visual Alarms Indicators On either sides of the display A red alarm LED for each sensor transmitter ins...

Страница 6: ...cts for each of four alarm relays and for the contacts of a fault relay Output Terminals There are two for each of the 4 20 mA outputs Figure 2 CP 60 Interior Features Relays 1 2 3 are programmed to a...

Страница 7: ...not ENMET s responsibility The CP 60 should be powered through appropriately sized circuit breakers See Section 6 0 Technical Data Upon supplying power to the CP 60 The green power on LED is lit The d...

Страница 8: ...r and gather at the top Consider the density of the gas you want the sensor to detect when you install the sensor Some examples are given below Heavier than Air Gas Sensor Location Bottled LP liquefie...

Страница 9: ...Ch 1 3 System Alarm 2 Relay 6 Ch 1 3 System Fault J16 Connector Transmitter 1 4 20mA Input Channel 1 J18 Connector Transmitter 2 4 20mA Input Channel 2 J19 Connector Transmitter 3 4 20mA Input Channel...

Страница 10: ...ilsafe Settings Factory Default Settings Position Failsafe Alarm Non Failsafe Alarm Gas Alarm 1 J5 Relay 1 NO Normally Open Normally Closed Channel 1 J5 Relay 1 COM Common Common J5 Relay 1 NC Normall...

Страница 11: ...value in the non alarm direction See example below The Alarm 1 differential value is the delay of the CP 60 staying in alarm condition until after the measured reading has returned past the alarm poi...

Страница 12: ...on occurs When a transmitter is not connected to an active channel of the CP 60 When a connected Sensor Transmitter reading falls out side of its operation parameters See sensor transmitter manual S S...

Страница 13: ...Changes digit indicated by underscore cursor Locks underscored digit and moves cursor to next digit See Section 5 3 7 for changing password instructions O S MAINTENANCE MENU Set Alarm1 Alarm 1 Select...

Страница 14: ...he SELECT switch Ch mAXmter 4mA 0000 is displayed Press the SELECT switch that moves the cursor one digit to the right when the last digit is accepted the display move to the full Scale mA Xmtrs menu...

Страница 15: ...k in the correct indicator ALARM 1 STD is displayed Press the OPTION switch to toggle between STD and DIFF select the correct indicator Press the SELECT switch to lock in the correct indicator IF STD...

Страница 16: ...cated by underscore cursor Locks underscored character and moves cursor to next digit DIFF S O S Changes character indicated by underscore cursor Locks underscored character and moves cursor to next d...

Страница 17: ...ect digit Press the SELECT switch which locks the digit in place and moves the cursor one digit to the right Continue this process until the four digit password is complete When a valid password is in...

Страница 18: ...isplay is transferred to the Calibration portion of the menu If an invalid password is inserted you are returned to the Enter Maint Menu display After entering a valid password Press the OPTION switch...

Страница 19: ...u position Press the SELECT switch to resume the operational display Press the OPTION switch to reenter the maintenance menu at the Calibration position Example Exit Maintenance Menu Flow Chart 5 3 Ch...

Страница 20: ...ure 20 to 36 inHg 68 to 133 kPa Mechanical Dimensions 11 x 9 x 6 inches 28 x 23 x 16 cm Weight 8 lbs 3 6 kg Material Engineered thermoplastic with hinged front cover Non magnetic hardware Strain relie...

Страница 21: ...aused by the improper use of the product The purchaser indemnifies and saves harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others of this...

Страница 22: ...ult in processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a mi...

Страница 23: ...OD Check one K VISA MasterCard______________________ ________ ________ Card number Expiration Card Code K American Express______________________ ________ ________ Card number Expiration Card Code Name...

Отзывы: