8.
Restore mains power to the unit;
9.
Recycle battery. Contact your local battery recycler for details
on how to recycle the LIFEPO4 batteries.
Half Power Switch
In areas where there is less light required, the full and standby power can be
set to half.
Default setting: Full power
.
Microwave Sensor Settings
The microwave sensor inside the diffuser is an active motion detector
that emits a high frequency electro-magnetic wave (5.8GHz) and
receives its echo. If it is necessary to check or adjust microwave sensor
settings to suit the local conditions, remove the diffuser.
Detection Area
Sensitivity can be adjusted to suit local conditions.
If the sensor detects motion outside the desired detection area, reduce
detection area setting to a lower value.
Default setting: 100%.
Hold Time
Refers to the time the luminaire remains at 100% after motion is no
longer detected.
Recommended value: 30 seconds for stairwells/
corridors, 90 seconds for car park parking bays.
enLighten recommends to use permanently-on fittings in car park
driveways.
The microwave sensor is inside the diffuser
→
Standby Level / Twilight Ratio
Refers to the illumination level after motion is no longer detected. Light
can also be set to permanently-on.
Default setting: 20%.
Twilight Time
Refers to the time period the luminaire remains at standby level before
switching off.
Recommended value:
Infinity
- fitting remains at
standby level during periods of no occupancy.
Battery Replacement
This luminaire requires a change of battery when it no longer meets its
rated duration of operation i.e. 90 minutes after receiving full charge.
Follow the below instructions to carry out battery replacement:
All electrical work must be carried out by a licensed electrician.
1.
Isolate unit from mains power;
2.
Remove diffuser and release gear tray;
3.
Unplug battery plug from driver;
4.
Remove battery from battery holder;
5.
Insert new battery into battery holder, note the date of
commissioning on the battery;
6.
Plug battery cable into driver;
7.
Secure gear tray and diffuser onto luminaire base;
NOTE
: The light must be operated within its specified operating parameters and in accordance with our warranty requirements.
These documents are available on our website.
Twilight Time
Dipswitch
→
7
8
Time
I
ON
ON
0
seconds
(no standby)
II
OFF
ON
90
seconds
III
ON
OFF
3
minutes
IV
OFF
OFF
Infinity
(always in 20% standby)
Hold Time
Dipswitch
→
3
4
Time
I
ON
ON
5
seconds
II
OFF
ON
30
seconds
III
ON
OFF
3
minutes
IV
OFF
OFF
10
minutes
Standby Level / Twilight Ratio
Dipswitch
→
5
6
Standby light output
I
ON
ON
20%
II
OFF
OFF
100%
(light permanently
-
on/sensor
disabled)
Detection Area
Dipswitch
→
1
2
Range
I
ON
ON
100%
II
OFF
ON
75%
III
ON
OFF
50%
IV
OFF
OFF
25%
Half power switch
Operating mode
I
ON
Half power
II
OFF
Full power
Push lever down and
slide battery out
The battery is in a battery holder on the gear tray.