enLighten Vico BL06 Series Скачать руководство пользователя страница 1

Mounting

 

1. 

Remove diffuser cover; 

2. 

Turn knobs to release and remove the gear tray. For emergency units, carefully unplug the green 
indicator cable 

(see picture right);

 

3. 

Feed mains cables into fitting and mount luminaire base to ceiling using the mounting brackets; 

4. 

Hang gear tray onto luminaire base using the hanging clips; 

5. 

Connect mains wiring to terminal block 

 

see 

Wiring 

section

6. 

Emergency Models Only - plug green indicator cable into driver. Ensure correct polarity is maintained 
by keeping the raised imprint & ink mark away from driver 

(see picture right)

7. 

Emergency Models Only - connect plug from battery cable to driver & record date of          
commissioning on battery; 

8. 

 Adjust microwave sensor settings as required 

 

see 

Microwave Sensor Settings 

section. 

9. 

Secure the gear tray and diffuser onto the base. 

 

Wiring

 

              

Standard model                Emergency model 

 Non-switched         Emergency model 

switched

 

The emergency light 
requires permanent 

electrical supply and permanent 
active must not be switched. 
The permanent active 

and 

switched 

active have to be energised for the 
fitting to illuminate. If the switched 
active is turned off then the battery 
will charge but the fitting will not 
illuminate in normal mode. 

 

Emergency Models: Indicator & Simulation of Normal Power Supply Failure

 

Red LED 

ON

  =  Charging 

Red LED 

OFF

 = Battery fully charged 

Green LED 

ON  

=  Mains supply active 

Green LED 

OFF 

=  Mains supply failure 

TEST BUTTON   

Press & hold the Test button to simulate normal power supply failure. This will trigger emergency mode 

switching LED supply from 240V supply to battery. Releasing the button will restore normal power to the luminaire.  

2. & 6. 

The raised imprint  

and ink marking should be  
facing away from the driver. 

7. 

Battery Plug 

Permanent/ Unswitched 

 

Active

 

Permanent/    Earth     Neutral   Switched

 

Unswitched                                        Active

 

    Active

 

Live        Earth    Neutral

 

Earth    Neutral

 

Loop

 

 

If neither the green nor the red LED is on, check the mains wiring and ensure that the green indicator cable is connected in the correct polarity.  

Continued next page

 

Vico

 

LED Batten

 

Installation Instructions   

 

BL06xx, BL12xx, BL15xx models                     

 

NEW

:

 Half-power option available by changing the dip-switch on the driver. 

Maximum timer setting changed to 10 minutes

 

 

NOTE: ALL ELECTRICAL WORK MUST BE CARRIED OUT BY A LICENSED 
ELECTRICIAN AS PER THE LATEST AS 3000 WIRING REGULATIONS. 

WARNING: ALL MAINTENANCE, SUCH AS BATTERY CHANGE ON THIS LUMINAIRE, TO BE 
PERFORMED BY A QUALIFIED PERSONNEL ONLY. DE-ENERGIZE ALL SUPPLIES BEFORE 
MAINTENANCE.

 

• 

This luminaire contains non-user replaceable lamps. Do not touch LEDs during installation or mainte-
nance or put gear tray facing downwards onto surface. Warranty void if LED damage found. 

• 

All entry points should be sealed properly to maintain the IP65 rating of the fitting. Warranty void if 
water damage found.

 

 

It is the responsibility of the installer to ensure the following to avoid premature battery failure: 

• 

Emergency fittings should be installed within 3 months after purchase as extended storage may 
shorten the battery life. 

• 

After connecting the battery, mains power should be supplied to the fitting within 7 days.  