A
PD MANUAL
IOM-39
11 of 36
Aug 99 R1
The
location
of
the
equipment
split
line
may
result
in
the
wire
being
disconnected
at
the
device
it
is
feeding.
The
wire
bundle
will
be
tagged
and
identified.
Confirm
correct
rotation
of
3
phase
devices
after
the
wiring
connections
has
been
completed.
Control
wire:
this
wire
is
typically
broken
near
the
split
line,
to
be
reconnected
at
either
a
enclosed
terminal
block,
junction
box
or
extended
to
a
nearby
control
panel.
Each
wire
or
wire
bundle
will
be
tagged
and
numbered
to
indicate
the
location
it
is
sent
to.
Sensor
wire
shield:
The
drain
wire
from
the
shield
must
be
grounded
(at
one
end
only).
A
ground
connection
point
is
available
for
connection
at
the
point
of
termination.
All
loose
wiring
must
be
securely
fastened
to
the
equipment
casing
upon
completion.
PIPING,
ELECTRICAL
OR
CONTROL
SERVICE
CONNECTIONS
DO
NOT
install
anything
that
will
interfere
with
equipment
access
or
the
rating
plate.
Engineered
Air
equipment
is
constructed
with
cabinet
and
floors
designed
to
prevent
water
from
entering
the
building
through
the
installed
unit.
When
ordered,
factory
installed
pipe
chases
and/or
electrical
chases
are
built
into
the
unit
floor.
Factory
chases
are
provided
with
covers
that
need
to
be
replaced
and
sealed
after
piping
and
electrical
connections
are
made.
All
penetrations
through
the
unit
walls
must
be
caulked
and
sealed
to
prevent
air
and/or
water
from
entering
the
unit.
ELECTRICAL
INSTALLATION
DO
NOT
install
anything
that
will
interfere
with
equipment
access
or
the
rating
plate.
The
unit
must
be
electrically
grounded
and
all
wiring
must
be
installed
in
accordance
with
the
National
Electrical
Code,
ANSI/NFPA
70,
and/or
the
Canadian
Electric
Code
CSA
22
‐
1
and
to
the
approval
of
the
authorities
having
jurisdiction.
THE
FLOOR
OF
THE
UNIT
HAS
BEEN
MADE
WATER
‐
RESISTANT.
DO
NOT
CUT
OR
DRILL
HOLES
IN
THE
FLOOR
OR
USE
PENETRATING
FASTENERS.
Field
wiring
diagrams,
internal
wiring
diagrams
and
operating
functions
are
included
in
the
control
cabinet.
The
power
requirements
are
indicated
on
the
rating
plate.
Where
field
wiring
of
control
circuits
is
required,
take
care
to
size
the
field
wiring
for
a
maximum
10%
voltage
drop.
The
control
circuit
ampacity
is
noted
on
the
field
wiring
diagram.
See
the
field
wiring
diagram
for
requirements
for
shielded
or
twisted
pair
wire
for
solid
state
devices.