background image

 

IOM-39  

 

Aug 99 R1 

 
 
 

INSTALLATION, OPERATION 

 

 

AND MAINTENANCE MANUAL 

 

FOR 

 

PD SERIES 

 
 

PACKAGED POOL DEHUMIDIFICATION UNITS 

 

INDOOR AND OUTDOOR MODELS 

 
 

 
 

 

 

 

UNIT MODEL NO. 

 

___________________  

 

UNIT SERIAL NO. ___________________ 

 

 SERVICED 

BY: 

 

_____________________  

 TEL. 

NO: 

 

__________________________  

 

 

 

CANADIAN 

HEAD OFFICE 

AND FACTORY 

 USA 

HEAD OFFICE 

AND FACTORY 

CANADIAN 

EASTERN FACTORY 

 

 

 

 

 

1401 HASTINGS CRES. SE 

CALGARY, ALBERTA 

T2G 4C8 

Ph:  (403) 287-2590 

Fx:  888-364-2727 

 

 

32050 W. 83

rd

 STREET 

DESOTO, KANSAS 

66018 

Ph:  (913) 583-3181 

Fx:  (913) 583-1406 

 

 

1175 TWINNEY DRIVE 

NEWMARKET, ONTARIO 

L3Y 5V7 

Ph:  (905) 898-1114 

Fx:  (905) 898-7244 

 

 

SALES OFFICES ACROSS CANADA AND USA 

 

Retain instructions with unit and maintain in a legible condition. 

Please give model number and serial number when contacting 

factory for information and/or parts. 

 

www.engineeredair.com

 

Содержание PD SERIES

Страница 1: ...TORY USA HEAD OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 2590 Fx 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fx 913 5...

Страница 2: ...And Degreasing Of Water And Glycol Coils 14 Heat Transfer Fluids 14 Pool Water Piping 15 Before Start Up 15 Start Up Check List 15 Operation 19 Cooling Components 19 Refrigerant Handling 21 Compressor...

Страница 3: ...o control the relative humidity to minimize the associated problems The primary function of a pool dehumidifier PD series unit is to manage the humidity levels within the facilities This helps to redu...

Страница 4: ...lterations or where ENGINEERED AIR s installation and service requirements have not been met The foregoing warranty is in lieu of all other warranties express or implied ENGINEERED AIR specifically di...

Страница 5: ...internal damage Remove protective covers and check for internal damage Replace covers if the unit is not being assembled or installed at this time Open access doors and check for internal damage Close...

Страница 6: ...e Part 1 C S A Standard C22 1 Provincial and Local Codes and in accordance with the local authorities having jurisdiction 2 This unit shall be electrically grounded in accordance with the latest editi...

Страница 7: ...ion 5 The installation of this unit shall be in accordance with all other National State and Local Codes and in accordance with the local authorities having jurisdiction MINIMUM CLEARANCE TO COMBUSTIB...

Страница 8: ...nstructed on a structural steel base frame The unit base frame is equipped with lifting lugs specifically located to facilitate proper lifting of the unit Spreader bars must be used to keep rigging aw...

Страница 9: ...the unit As a minimum sleepers that are installed perpendicular to the length of the unit must be continuous across the width of the unit and shall be installed at the end lifting point base rails and...

Страница 10: ...ame of adjacent sections This may require personnel to work under the unit during assembly Injury or death can result from improper support or improper loading of the curb Additional temporary support...

Страница 11: ...led unit When ordered factory installed pipe chases and or electrical chases are built into the unit floor Factory chases are provided with covers that need to be replaced and sealed after piping and...

Страница 12: ...ad Amps 1 Maximum Total Length of Run 50 Ft 100 Ft 150 Ft 200 Ft 250 Ft 300 Ft 350 Ft 400 Ft 450 Ft 500 Ft 15 m 30 m 45 m 60 m 75 m 90 m 105 m 120 m 135 m 150 m 1 16 AWG 16 AWG 16 AWG 16 AWG 16 AWG 16...

Страница 13: ...coil connections when installing piping For refrigerant coils all piping is to be installed by a qualified refrigeration mechanic All refrigeration specialties shall be installed using good refrigera...

Страница 14: ...rain traps FLUSHING AND DEGREASING OF WATER AND GLYCOL COILS Coil tubing may contain material or residue from manufacturing transportation or storage To prevent possible damage to other components in...

Страница 15: ...pass any interlock or safety switches under any circumstances The start up and operation must be in accordance with safe practices Start up must be performed by qualified personnel Complete attached s...

Страница 16: ...kwards will typically have low head pressure high suction pressure and are usually noisy Screw compressors MUST be checked with a phase meter before starting If rotation is incorrect instantaneous per...

Страница 17: ...orator coil allowing the evaporator to have the most efficient moisture removal The bypass is factory set to a default value and must be field adjusted to ensure proper operation With the system runni...

Страница 18: ...possible for conditions other than low refrigerant charge to cause the sight glass to bubble Bubbling may occur when condenser fans cycles on superheat setting is too low or filter drier is plugged e...

Страница 19: ...ur wiring diagram to verify that all remote controls are properly located and correctly field wired Dehumidification systems first cool the air with an evaporator coil operating below the dew point te...

Страница 20: ...or a separate device 4 Head Pressure Control Head pressure controls are designed to maintain an adequate operating head pressure to allow the TX valve and other components to work correctly Low head...

Страница 21: ...R134a 150 psig 1040 kPa R407C 270 psig 1870 kPa R410A 370 psig 2550 kPa Caution When recovering refrigerant from a system equipped with a water cooled condenser the water valve must be manually opened...

Страница 22: ...the oil completely and add the compressor manufacturers measured oil charge for replacement compressors before placing the compressor into operation Contact the compressor manufacturer for the type a...

Страница 23: ...refrigerant into the system slowly until the system sight glass is clear The system must be at design air flow and load If the system is equipped with an Engineered Air Intercooler sight glass only r...

Страница 24: ...igerant and the rest of the circuit will be out of gas 4 To check for refrigerant in the inactive coil install a refrigerant gauge on the inactive condenser coil reheat pool heat or condenser coil and...

Страница 25: ...nt determine and fix the cause Properly remove and dispose of the contamination Properly clean and sanitize the affected area using only approved sanitizers suitable for HVAC equipment To provide a ma...

Страница 26: ...ssible without slipping in the pulley grooves Belt deflection 3 4 19mm for each foot 300mm of span between the pulleys FOR FANS EQUIPPED WITH PILLOW BLOCK BEARINGS Belt Deflection Allow 1 64 0 4mm of...

Страница 27: ...15 16 49mm 69 in lb 7 8 Nm 155 in lb 17 5 Nm 228 272 in lb 26 31 Nm 2 3 16 56mm 87 in lb 9 8 Nm 155 in lb 17 5 Nm 228 272 in lb 26 31 Nm 2 7 16 62mm 147 in lb 16 6 Nm 155 in lb 17 5 Nm 228 272 in lb...

Страница 28: ...2000 2500 3000 3500 4000 4500 Shaft DIA 11 16 3 3 2 1 1 1 1 1 1 15 16 2 7 16 3 2 2 1 1 2 11 16 2 5 16 2 2 1 1 3 7 16 3 15 16 1 1 Suggested initial greasing interval If safety permits re lubricate whi...

Страница 29: ...ease having these properties are Shell Alvania No 2 Mobil Mobilith AW2 Mobilith SHC100 Texaco Premium RB2 American Rykon Premium 2 Lubricate bearings prior to extended shutdown or storage and rotate s...

Страница 30: ...E 20 160 SAE 30 180 SAE 40 Static oil level should be at the center of the lower most roller do not overfill MOTOR LUBRICATION Refer to motor manufacturer for lubrication recommendations On motors hav...

Страница 31: ...the best service interval To clean rinse with water Shake off excess water and re install These filters do not require an oil adhesive Pleated Throwaway and or Replaceable Media Cartridge Bag Replace...

Страница 32: ...C glycol or other suitable fluid COATING MAINTENANCE Most natatorium HVAC equipment will have an epoxy interior coating Regularly inspect the coating for integrity Touch up epoxy paint is readily avai...

Страница 33: ...capacity and increased refrigerant head pressure Should this condition occur the condenser coil should be chemically cleaned or replaced Air Cooled The external surface of finned coils can be cleaned...

Страница 34: ...noted above or the maximum rated working pressure of the receiver or 90 of the receiver PRV Hot gas bypass Start to open pressure 52 psig 350 kPa 30 psig 210 kPa 105 psig 720 kPa CFC1 Cut In 290 psig...

Страница 35: ...ssor discharge temperature switch tripped Reset switch and check refrigerant charge Ice formation on evaporator coil Cold inlet temperature Raise the entering air temperature Air filters dirty Replace...

Страница 36: ...scharge Compressor 1 psig psig Compressor 2 psig psig Compressor 3 psig psig Compressor 4 psig psig Compressor 5 psig psig Compressor 6 psig psig Compressor 7 psig psig Compressor 8 psig psig Condense...