EVC800i AUTOMATIC VOLTAGE REGULATOR

Specification, Installation & Adjustment Manual

10/02/2015

Page 4 of 9

Trim [TRIM] Adjustment

Caution

Any signal connected to this input must be fully floating and earth free.

Over Excitation [O/L] Adjustment

1.

V0 - V200 - V380

2. Excitation Output F+, F- :

3. Power Input :

4. Current Compensation Input S1 and S2 :

5. External Voltage Adjustment VR1-VR2 :

6. Analog Input A+ and A- :

7. Dip Switch : SW1 - ON :

SW1 - OFF :
SW2 - ON   :
SW2 - OFF :

An auxiliary input is provided to connect to power factor controller or any other type of PLC controller and is design to
accept DC signal upto +/-5 V.

The DC signal present to this input adds to or subtracts from the AVR reference circuit input and allows the external
controller to alter the generator excitation. The TRIM control allows the user to determine how much control the external
signal has over the AVR. With the Trim control fully clockwise the external signal has full control, with the trim control
fully anti-clockwise has no control.

The AVR includes the protection circuit to remove generator excitation in the event of over excitation, this condition is
usually a result of overload and can damage the rotor component within the generator. The excitation is cut of after a
delay of 20 seconds. During this time delay the overload condition should be continuous. Clockwise rotation of the O/L
control increases the excitation trip level. An over excitation trip condition is indicated by Red LED. The generator must be
stopped to reset the overload trip condition.

: When the generator output voltage required is 220Vac, connect the

sensing input to the terminal V0 and V200. When the generator output voltage requires 400Vac, connect the sensing
input terminal V0 and V380.

Connect Brushless exciter field to terminals F+ and F-, be sure to observe polarity.

AVR power input is on P1, P2 and P3. Input can be 1 Phase or 3 Phase. 3 Phase PMG can be

connected directly to P1, P2 and P3. Without PMG, Main Winding can be used as a power input. In that case for 400V
system connect U to P1 and N to P2. For 200V system connect U to P1 and W to P2. If auxiliary winding is there, then
that can also be used to power the AVR.

Current transformer of In:1A is connected to this terminal for parallel

operation.

If remote adjustment is required then connect a 100K/1W potentiometer to

terminal VR1 and VR2. VR1 and VR2 are left unconnected if remote pot not in use

5Vdc from external controller is connected to A+ and A-

Increases response time. Can be used for 60 Hz machine to increase the response time

(Slow response) or with 220V system when slow response is needed.

Response as per STAB pot set

60 Hz

50 Hz. As per STAB pot set

Sensing Input Terminal

±

WIRING

Содержание EVC800i

Страница 1: ...puts provide reactive power sharing controls Specification Installation Adjustment Manual DESCRIPTIONS Sensing Input Power Input Output Built up Voltage Voltage Regulation Response Time V V for 220 Vac V V for 400 Vac 350 to 480Vac 50 60Hz PMG 160 to 250 V 3 Ph 50 to 400 Hz Main Winding 160 to 250 V 1 Ph Auxillary 160 to 250 V 1 Ph Voltage 180 Vdc on Input of 200 Vac Current Continuous 8 Amps Resi...

Страница 2: ...e running the generator ensure that the suitable voltmeter is available to measure generator output voltage 2 Turn the VOLTS control fully anti clockwise and turn the external hand trimmer if fitted to its Midway position 3 Turn the STAB control to its Midway position 4 Start the generator set and run at no load condition at nominal frequency e g 50 or 60 Hz 5 If UFRO LED is ON refer to the UFRO s...

Страница 3: ...he V Hz Characteristics thus aiding engine speed recovery The dwell function introduces a time delay between the recovery of voltage and recovery of speed The purpose of the time delay is to reduce the generator KW below the available engine KW during the recovery period thus allowing the speed recovery Again this control is only functional below the knee point i e if the speed stays above the kne...

Страница 4: ...conds During this time delay the overload condition should be continuous Clockwise rotation of the O L control increases the excitation trip level An over excitation trip condition is indicated by Red LED The generator must be stopped to reset the overload trip condition When the generator output voltage required is 220Vac connect the sensing input to the terminal V0 and V200 When the generator ou...

Страница 5: ...m 129 mm 143 mm 104 mm VR A2 A1 S2 S1 1 VR2 FUSE 8 Amps 4 X 4 4 mm F F V220 V380 38mm H V0 175 mm 129 mm 143 mm 104 mm ENGGA DROOP UFRO TRIM STAB VOLT www engga com cn Model EVC800i Sensing Input V V for 220 Vac 180 to 250Vac 50 60Hz 0 220 V V for 400 Vac 350 to 480Vac 50 60Hz Power Input 160 to 250Vac Output 180Vdc 8A 0 380 Outline Drawing The Drawing For Trimmer F F V 220 V 0 V 380 P3 P2 P1 1 2 ...

Страница 6: ...VR A2 A1 S2 S1 1 VR2 FUSE 8 Amps Exciter Field Armature Stator Wire W N V U 5 Vdc CT 5A IN 100K 1W V0 Connection Diagram with PMG Operation Note All doted lines are optional connections SW1 ON Increase in Response Time OFF Response as per STAB pot Set SW2 ON 60 HZ OFF 50 HZ P3 P1 1 2 ON P3 P2 P1 PMG O L O L LED DIP DWELL ...

Страница 7: ...0 V380 VR A2 A1 S2 S1 1 VR2 FUSE 8 Amps Exciter Field Armature Stator Wire W N V U 5 Vdc CT 5A IN 100K 1W V0 Connection Diagram with Auxiliary Winding Note All doted lines are optional connections SW1 ON Increase in Response Time OFF Response as per STAB pot Set SW2 ON 60 HZ OFF 50 HZ P3 P1 1 2 ON O L O L LED DIP DWELL ...

Страница 8: ... Amps Exciter Field Armature Stator Wire W N V U 5 Vdc CT 5A IN 100K 1W V0 Connection Diagram with Main Winding Note All doted lines are optional connections SW1 ON Increase in Response Time OFF Response as per STAB pot Set SW2 ON 60 HZ OFF 50 HZ P3 P1 1 2 ON O L O L LED DIP DWELL Connection option for 400V system Connection option for 200V system ...

Отзывы: