OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR

MODEL NO : EVC600i

AVR can be mounted directly on the  generator, switchgear or control panel that conforms to the
mounting specification.
All voltage readings are to be taken with an average-reading voltmeter. Meggers and high-potential test
equipment must not be used with AVR connected to generator. Use of such equipment could damage
the AVR.

5. WIRING

1. V - V

- V

: Sensing Input Voltage.

output voltage 220Vac

output voltage 400Vac

2. F+. F- : Excitation Output

3. Power Input:

For 400 Vac system

For 220 Vac system

4. S1 - S2:

0

220

380

Sensing Input is between

&

(220Vac) or

(400VAC). For 2 Phase sensing one phase is

connected to

terminal of AVR and second

phase is connected to

or

as explained

below:-
- For generator

, connect

sensing phase to terminal

.

- For generator

, connect

sensing phase to terminal

.

The sensing should be connected

Line to Line

from generator output. Refer Figure 3 & 4.

.

Connect the brushless exciter field to terminals F+
and F-. Be sure to observe polarity.

AVR power input is between X1

& V0.

X1 is connected to

Neutral of generator & V0 to V Phase of generator.

, X1 is connected to U Phase

& V0 toV Phase of generator. Refer to Figure
3 & 4.

Current compensation input.

Current Transformer(CT) secondary current = 5A,
0.8 PF.

V

V

V

V

V

V

V

V

0

220

380

0

220

380

220

380

External Voltage Adjustment.

If an external voltage adjust control is being used,
connect a 100 K / 1 watt potentiometer to
terminals

and

as shown in Figure 3 & 4.

If not in use then let VR1 & VR2 left open.

: Analog Voltage Input.

Fully isolated analog voltage from PF controller or
any other type of Digital (PLC) controller can be
injected into AVR for variation of generator output
voltage. Analog voltage range is ± 5VDC maximum
and can be connected to A1 & A2 terminals for
at least 10 % variation in terminal voltage.

When 60Hz operation, AVR response

time needs to be reduced. For that turn ON Switch1
so that extra fixed response time is now added with
STAB POT setting such that no over or under shoot
of voltage occurs during loading-unloading of
generator at 60Hz.

: When 50Hz operation, no need to

decrease response time as STAB POT setting is
proper for optimum stability of generator with
minimum over-under shoot of Voltage during
loading - unloading of generator.

For 60 Hz operation of UFRO

For 50 Hz operation of UFRO

5. VR1 - VR2:

VR1

VR2

6. A1 - A2

7. DIP SWITCH:
a) SW1 - ON:

SW1 - OFF

b) SW2 - ON:

SW2 - OFF:

6. ADJUSTMENT

All trimmer build in back of the AVR board, except
the

Trimmer. The trimmers include

as shown in Figure

2. For

Trimmer refer to Figure 1

The generator output can be altered by
adjustment of the

trimmer on the AVR board,

or by the external trimmer (100K ohm 1W) if fitted.

a) The terminals

and

must be left

unconnected if no hand trimmer is required.

O/L

DROOP,

TRIM, UFRO, STAB and VOLT

O/L

1. VOLT: Voltage Adjustment.

VOLT

Vset is factory set for 400 Vac , If Vset is
disturbed and set value is not known then
proceed as below :

VR1

VR2

.

Connect a voltmeter to generator output voltage

terminals.
d) Start the generator set and run on no load at
nominal frequency 50 - 53 Hz or 60 - 63 Hz.
e) If the red Led is illuminated, refer to the under
frequency roll off adjustment.
f)  Carefully turn volt trimmer clockwise until
required voltage is reached.

Stability Pot is factory set for optimum performance
& is advisable not to disturb. But if required then
with the generator in ON Condition, rotate STAB
POT clockwise direction till voltage start oscillating
fast.

b) Before starting the generator, please turn the

trimmer on the AVR board fully anti-

clockwise.
c)

VOLT

2. STAB: Stability Adjustment.

Page 3 of 7

Updated 26Jan 2015

Содержание EVC600i

Страница 1: ...ation Output Voltage Output Current Terminal V V for 220 Vac Terminal V V for 400 Vac Voltage 180 to 250 Vac Frequency 50 Hz or 60 Hz 180 300 Vac 300 520 Vac Recommend 9 24 1 Maximum 90 Vdc 220 Vac Ma...

Страница 2: ...1 X2 F F V 220 V 380 VR A2 A1 S2 S1 1 VR2 O L O L LED FUSE 8 Amps V 0 4 X 4 4 mm X1 X2 F F V220 V380 37 5mm H V0 175 mm 129 mm 143 mm 104 mm ENGGA DROOP UFRO TRIM STAB VOLT www engga com cn Model EVC6...

Страница 3: ...e is 5VDC maximum and can be connected to A1 A2 terminals for at least 10 variation in terminal voltage When 60Hz operation AVR response time needs to be reduced For that turn ON Switch1 so that extra...

Страница 4: ...set the frequency roll off proceed as follows a Adjust the prime mover RPM to the desired frequency compensation corner frequency roll off point b If UFRO LED is ON adjust the back panel trimmer antic...

Страница 5: ...SE 8 Amps Exciter Field Armature Stator Wire W N V U 5 Vdc CT 5A IN 100K 1W V0 X1 Figure 3 Connection Diagram for 400 Vac Operation Page 5 of 7 Note All doted lines are optional connections SW1 ON Inc...

Страница 6: ...USE 8 Amps Exciter Field Armature Stator Wire W V U 5 Vdc CT 5A IN 100K 1W V0 X1 Figure 4 Connection Diagram for 200 Vac Operation Page 6 of 7 O L O L LED Note All doted lines are optional connections...

Страница 7: ...rational Test Page 7 of 7 X2 F F V220 V380 VR A2 A1 S2 S1 1 VR2 2 1 FUSE 8 Amps V0 X1 220V100W LAMP 230Vac 50Hz O L O L LED Note All doted lines are optional connections SW1 ON Increase in Response Ti...

Отзывы: