![ENGGA EVC600i Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/engga/evc600i/evc600i_operation-manual_2412864001.webp)
OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR
MODEL NO : EVC600i
1. INTRODUCTION
2. ENVIRONMENTAL
3. TECHNICAL SPECIFICATION
The EVC600i Voltage Regulator is thyristor base to control the DC exciter field power of conventional
50 or 60 Hz brushless generators. The AVR circuitry includes under speed and over load protection
features. Excitation power is derived directly from the generator terminals.
-30 to 80°C (-22 to 176°F)
-40 to 80°C (-40 to 176°F)
Less than 2600 meter
<90%
2.1. Operating temperature:
2.2. Storage temperature:
2.3. ALTITUDE:
2.4. RELATIVE HUMIDITY:
Sensing Input
Power Input
Voltage Adjust Range
Field Resistance
Voltage Regulation
Output Voltage
Output Current
Terminal V -V
for 220 Vac
Terminal V -V
for 400 Vac
Voltage: 180 to 250 Vac
Frequency: 50 Hz or 60 Hz
180 - 300 Vac, 300 - 520 Vac
Recommend 9 - 24
< 1%
Maximum 90 Vdc @ 220 Vac
Maximum continuous: 8 A @ 220 Vac
10 second forcing: 10 A @ 220 Vac
0
220
0
380
Ω
±
Paralleling
Voltage Buildup
External Volts Adjustment
Thermal Drift
Analog Voltage Input
Current Compensation
Dimensions
Weight
Internal burden and adjustment for 0 to 10%
droop at 5 A, 0.8 PF, (from external CT)
4Vac, 30 Hz
At least
10% with 100k ohm 1 watt trimmer
0.05% per Degree C change in AVR ambient
In : 5A Input
At least 10 % @ P.F. = 0.8
175 mm L x 129 mm W x 37.5 mm H
530
10g
±
±5VDC, adjustable output voltage is no less than
2% for 1VDC (i.e. for ±5VDC it come out to be
±10%)
±
EVC600i
Generator Automatic Voltage Regulator
Operation Manual
Page 1 of 7
Updated 26Jan 2015