Page 33 of 78                  Article no.: 1080621023                  2022_02_14                  Subject to technical change! Errors excepted. 

6.1   Direct mounting (ball valve and T-piece)   

 

 

 

 

 

-

 

Remove the blind plug / old temperature sensor and gasket / old O-ring. Clean 

connection surfaces. 

-

 

Slide the O-ring off the temperature sensor and insert it to the bottom of the 

threaded opening of the ball valve or the T-piece. 

-

 

Hold the temperature sensor at the screw only and insert it into the ball valve or 

the T-piece and screw tightly. 

-

 

In doing so the plastic clip is locked in the first crimp (viewed from the top of 

the protective sheath) and must not be moved.

 

 

 

 

 

 

6.2   Direct mounting of the 6 mm temperature sensors of the 

SensoStar

 

Important note:

  

Close the shut-off valves and make sure that no hot water can escape upon removal of 

the blind plug or the old temperature sensor! 

-

 

Prepare both temperature sensors: Push the O-ring into the first crimp (seen from 

the top of the protective sheath). 

-

 

Insert the temperature sensors into the measuring point of the connection piece, 

and ball valve or T-piece, and tighten using the coupling nuts.  

-

 

Reopen all ball valves and check installation points for leakage. 

-

 

Protect the installation points (meter and temperature sensors) against 

manipulation by securing with the seals and sealing wires. 

7   Start of Operation 

-

 

Slowly open the shut-off valves. 

-

 

Check that there are no leaks.  
 

Check the following points:  

-

 

Are all shut-off valves open? 

-

 

Is the meter of the right size? 

-

 

Is the heating (heating/cooling) system clear (dirt filters not clogged)? 

-

 

Is the temperature sensor installed in the flow sensor correctly sealed to the flow sensor? 

-

 

Does the directional arrow on the connection piece / flow sensor match the actual direction of flow? 

-

 

Is a flow volume displayed? 

-

 

Is a plausible temperature difference displayed? 

When the meter is functioning properly, attach the seals to the exterior temperature sensors and the flow sensor 

(required to protect against manipulation). 

 

8   Display  

The calculator has a liquid crystal display with 8 digits and special characters. The values that can be shown are 

divided into five display loops. All data is retrieved using the push-button next to the display. 

At the start you are automatically in the main loop (1st level). 

By pressing the push-button longer than 4 seconds you change to the next display loop. Keep the push-button 

pressed until you reach the desired information loop. 

By pressing the push-button briefly each time you can scan all the information within a loop. 

After 2 minutes of non-use of the push-button, the display will automatically be deactivated. 

 

 

Содержание EMMETI SensoStar CH-T2-18768-00

Страница 1: ...desanstalt Istituto nazionale di metrologia tedesco Osservare le normative nazionali relative alla misurazione delle frigorie Osservare le prescrizioni tecniche relative all installazione delle apparecchiature elettriche Lo strumento è conforme ai requisiti della Direttiva 2014 30 UE del Consiglio europeo sulla compatibilità elettromagnetica La garanzia e la validità della verifica prima decadono ...

Страница 2: ...anto di riscaldamento deve essere installato lo strumento Installazione nel circuito di uscita Installazione nel circuito di ingresso 3 2 Pittogrammi identificativi della versione del misuratore di energia termica iscrizioni sullo strumento Misuratore di energia termica per applicazioni di riscaldamento Misuratore di energia termica per applicazioni di raffrescamento 4 Installazione del contatore ...

Страница 3: ...nuova guarnizione con la superficie liscia verso l alto Lubrificare la filettatura esterna del contatore d acqua con del grasso siliconico per uso alimentare Verificare che l OR nella bocca d uscita del contatore d acqua sia posizionato correttamente Avvitare a mano e poi continuare ad avvitare con una chiave a gancio fino al completo arresto Ruotare l unità elettronica in modo che possa essere le...

Страница 4: ...installato senza adattatore Installazione del contatore d acqua modello MSH M60 in raccordo monotubolare Scaricare le tubazioni seguendo la normale procedura Chiudere le valvole di intercettazione Aprire la valvola di scarico più vicina per diminuire la pressione Svuotare le sezioni di tubo chiuse Verificare che la direzione della freccia coincida con la direzione del flusso controllare sul raccor...

Страница 5: ...ate Se necessario pulirle con un detergente adatto Lubrificare la filettatura esterna del contatore d acqua e l OR del grasso siliconico per uso alimentare Posizionare il misuratore di energia termica Avvitare a mano e poi continuare ad avvitare con una chiave a gancio fino al completo arresto Ruotare l unità elettronica in modo che possa essere letta facilmente oppure rimuoverla e fissarla nel pu...

Страница 6: ...icie piana rivolta verso la parete Fissare l unità elettronica al supporto Si consiglia di separare l unità elettronica dal contatore d acqua Nei seguenti casi l unità elettronica deve essere sempre separata dal contatore d acqua misuratori di energia termica per applicazioni di raffrescamento misuratori di energia termica per applicazioni di riscaldamento raffrescamento misuratori di energia term...

Страница 7: ...illi antimanomissione in corrispondenza dei punti di installazione contatore d acqua e sonde di temperatura 7 Messa in servizio Riaprire lentamente le valvole di intercettazione Assicurarsi che non ci siano perdite dai raccordi Verificare i seguenti punti Le valvole di intercettazione sono aperte Il calibro del contatore è adeguato all impianto L impianto di riscaldamento è intasato i filtri sono ...

Страница 8: ...ha 3 ingressi impulsi sono indicati i rispettivi valori2 4 Volume totale in m 5 Data corrente alternata all ora 6 Messaggio di errore formato binario ed esadecimale alternati 7 Registro tariffario 1 valore alternato al registro tariffario e ai parametri 8 Registro tariffario 2 valore alternato al registro tariffario e ai parametri 9 Contatore impulsi 1 valore dell impulso alternato alla lettura de...

Страница 9: ...to dalla data di fabbricazione alternati con i giorni di funzionamento dalla data in cui il valore dell energia ha superato i 10 kWh 7 Indirizzo M Bus 8 Numero di matricola 9 Versione firmware Menù 3 Menù dei dati statistici 1 30 Valori quindicinali data alternata a calorie frigorie volume valore del registro tariffario 1 valore del registro tariffario 21 Se lo strumento ha 3 ingressi impulsi sono...

Страница 10: ...zione Mantenere premuto il pulsante per 2 3 secondi Dopo 2 secondi il display visualizza in basso a sinistra una penna che indica la modalità di modifica v figura sotto Quando compare la penna rilasciare il pulsante Il pittogramma del parametro da modificare inizia a lampeggiare Premere brevemente il pulsante per visualizzare l opzione successiva Per confermare l opzione selezionata mantenere prem...

Страница 11: ... sono necessari una testina ottica e il software Device Monitor forniti su richiesta L interfaccia ottica viene attivata dall invio automatico di un header conforme alla orma EN 13757 3 La velocità di trasmissione è di 2400 baud Dopo l invio dell header la comunicazione con lo strumento rimane attiva per 4 secondi Dopo ogni comunicazione valida lo strumento resta attivo per altri 4 secondi poi il ...

Страница 12: ...e applicare il sigillo adesivo antimanomissione numerato sul sigillo precedente Ogni sigillo numerato è abbinato a un adesivo con un codice a barre che può essere utilizzato a scopo di riferimento 10 3 Sostituzione della batteria La batteria deve essere sostituita solo da personale tecnico autorizzato Utilizzare solo batterie originali del fabbricante Smaltire le batterie sostituite in accordo all...

Страница 13: ...issione numerati Ogni sigillo numerato è abbinato a un adesivo con un codice a barre che può essere utilizzato a scopo di riferimento Rimuovere il tappo cieco a sinistra con lo strumento di fronte e inserire il cavo dell alimentatore Il cavo dell alimentatore A ha due connettori Collegare un connettore all attacco sul lato sinistro della scheda Collegare l altro connettore all attacco sulla scheda...

Страница 14: ...ne 4 H 08 Sonda di temperatura 2 cortocircuito 1 nella posizione 5 H 04 Sonda di temperatura 2 rottura del cavo 1 nella posizione 6 H 02 Sonda di temperatura 1 cortocircuito 1 nella posizione 7 H 01 Sonda di temperatura 1 rottura del cavo 1 nella posizione 8 La sonda di temperatura 1 è la sonda di temperatura di destra con lo strumento di fronte Esempio Sonda di temperatura 2 rottura del cavo Mess...

Страница 15: ...ata Non viene effettuato il conteggio I registri del volume e dell energia non vengono aggiornati In generale il cavo che collega l unità elettronica al contatore d acqua è danneggiato Contatore d acqua a ultrasuoni presenza di aria nell impianto il contatore d acqua è sporco Contatore d acqua meccanico La scansione del volume non funziona correttamente H 08 H 04 H 02 H 01 Sonda di temperatura 2 o...

Страница 16: ...allazione e uso o derivanti da vizi o difetti dell installazione saranno addebitati all installatore Si consiglia di utilizzare un cavo telefonico J Y ST Y 2 x 2 x 0 8 mm La struttura della rete M Bus lunghezza e diametro dei cavi deve essere compatibile con la velocità di trasmissione 2400 Bd degli strumenti collegati 1 2 1 M Bus norme standard e letteratura di riferimento IEC 60364 4 41 2005 12 ...

Страница 17: ...isattivato Valori accettati 1 247 se l indirizzo Slave automatico ID è attivato set to 1 l indirizzo M Bus impostato sul calorimetro verrà utilizzato per la comunicazione dei dati 1 4 Interfacce wireless Maddalena offre le seguenti interfacce radio Interfaccia M Bus wireless EN 13757 3 4 cfr capitolo 1 4 1 Interfaccia di comunicazione LoRaWAN cfr capitolo 1 4 2 Informazioni generali sull interfacc...

Страница 18: ...ile stimata della batteria 10 anni Modo di trasmissione S1 T1 C1 unidirezionale T1 unidirezionale Periodo di trasmissione 00 00 24 00 8 00 18 00 Intervallo di trasmissione 10 secondi 240 minuti 120 secondi misuratori di energia termica per applicazioni di riscaldamento Giorni della settimana Lunedì domenica Lunedì venerdì Settimane 1 4 5 1 4 5 Mesi 1 12 1 12 Data di attivazione della radio 01 01 3...

Страница 19: ...essiva della crittografia radio La crittografia AES può essere attivata anche in un momento successivo all installazione Può essere attivata in due modi a Con il pulsante mantenere premuto il pulsante fino a quando viene visualizzato il menù 6 Premere brevemente il pulsante ancora una volta per visualizzare la seconda voce AES off v figura Per attivare la modalità di modifica premere nuovamente il...

Страница 20: ...vaco OTC per ulteriori informazioni consultare le istruzioni operative dell app Elvaco OTC https www elvaco se Image GetDocument en 269 elvaco otc app manual english pdf b Interfaccia ottica tramite software di configurazione Sensus Device Monitor dalla versione 2 22 per ulteriori informazioni consultare le istruzioni operative del software Device Monitor Il software può essere ordinato separatame...

Страница 21: ... 2007 08 Impianti elettrici utilizzatori di bassa tensione Parte 4 44 Prescrizioni per la sicurezza Protezione contro le interferenze elettromagnetiche IEC 60364 5 51 2005 04 Installazioni elettriche di edifici Parte 5 51 Scelta e installazione di apparecchiature elettriche Norme comuni IEC 60364 5 54 2011 03 Impianti elettrici utilizzatori di bassa tensione Parte 5 54 Scelta e installazione di ap...

Страница 22: ...egli emettitori impulsi dotati di uscita open collector I fili conduttori non devono entrare in contatto l uno con l altro durante l installazione altrimenti verranno conteggiati degli impulsi La lunghezza massima consentita per i cavi è pari a 10 metri Durante la configurazione dello strumento può essere necessario azzerare la lettura degli strumenti collegati e il valore degli impulsi Per azzera...

Страница 23: ...di commutazione 27 mA Resistenza di contatto ON massima 74 Ω Resistenza di contatto OFF minima 6 MΩ Tempo di chiusura 100 ms Intervallo tra gli impulsi 100 ms 1 6 2 Collegamento a 4 fili Colore Collegamento Giallo IA1 Verde IA1 Marrone IA2 Bianco IA2 2 Installazione successiva di un interfaccia di comunicazione aggiuntiva Durante l installazione dell interfaccia di comunicazione aggiuntiva osserva...

Страница 24: ...licatamente la linguetta verso l alto a 90 v figura sotto Ora la cover è sganciata su un lato Ripetere l operazione nell altro foro e rimuovere la cover Installare l interfaccia sul lato destro della scheda dell unità elettronica v figura sotto Rimuovere i tappi ciechi dei passacavi che si trovano a destra tenendo l unità elettronica di fronte e inserire i cavi dell interfaccia nei pressacavi Chiu...

Страница 25: ... rimuovere l interfaccia aprire la cover come illustrato nella figura sotto sollevarla da un lato e contemporaneamente esercitare una leggera pressione sull altro lato In questo modo la linguetta A farà da leva e solleverà l interfaccia Ora è possibile rimuovere l interfaccia v figura sotto A2 1 ...

Страница 26: ...la configurazione wireless M Bus radio off wireless M Bus radio on LoRa on LoRa off valore impulso uscita impulsi 1 o o 3 Visualizzazione in base alle interfacce collegate e alla configurazione crittografia radio AES off crittografia radio AES on LoRa in attesa LoRa connessa valore impulso uscita impulsi 2 4 Realizzazione del manuale Engelmann Sensor GmbH Rudolf Diesel Str 24 28 69168 Wiesloch Bai...

Страница 27: ...ns must be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2014 30 EU The identification plate of the instrument and the seals must not be removed or damaged otherwise the guarantee and the approved application of the instrument are no longer valid To achieve measurement stability of the meter it is necessary that the ...

Страница 28: ... inlet flow 3 2 Pictograms type of meter on type identification label Heat meter Cooling meter 4 Mounting the Flow Sensor 4 1 Mounting of SensoStar E SensoStarQ and SensoStar U Flush the pipes professionally taking care not to damage any system components Then close all the shut off valves Open the nearest draining valve for pressure release Drain the closed off pipe section Loosen the coupling ri...

Страница 29: ... best position for read out or detach it and mount it nearby 4 3 Installation of SensoStar T in a fix installed single pipe connection piece The multi jet flow sensor type MSH TE1 has an M62x2 thread as described in EN ISO 4064 4 EN 14154 2 TE1 interface for Techem heat meters and must be installed without an adapter Mounting the flow sensor type MSH TE1 in a single pipe connection piece Flush the...

Страница 30: ... off pipe section Take into account the direction of flow check the connection piece Remove the overflow flange or the old heat meter from the connection piece using a wrench Remove all old gaskets Check sealing surfaces and threads for imperfections or dirt If necessary debur or clean with a suitable cleaning liquid Place the new profile gasket into the connection piece with the flat surface faci...

Страница 31: ... with a suitable cleaning liquid Lubricate the external thread M77x1 5 of the flow sensor and the O ring 66 35x2 62 with a thin layer of food safe silicon grease Screw in the heat meter tightly by hand and then tighten additionally with a suitable wrench to the mechanical end stop metal to metal Rotate the calculator to the best position for read out or detach it and mount it nearby Use the enclos...

Страница 32: ...pport anticlockwise until you can release it Then attach the wall support at the desired place with the flat surface towards the wall We always recommend detaching the calculator from the flow sensor However it is important to note that the calculator must be detached for the following versions Cooling and heat cooling meters high temperature heat meter versions SensoStar U temperature range up to...

Страница 33: ...nd temperature sensors against manipulation by securing with the seals and sealing wires 7 Start of Operation Slowly open the shut off valves Check that there are no leaks Check the following points Are all shut off valves open Is the meter of the right size Is the heating heating cooling system clear dirt filters not clogged Is the temperature sensor installed in the flow sensor correctly sealed ...

Страница 34: ...e meter has 3 pulse inputs their values follow 2 4 Total flow volume in m 5 Current date alternating with time 6 Information message alternating binary and hexadecimal display 7 Tariff register 1 value alternating with tariff register no and criteria 8 Tariff register 2 value alternating with tariff register no and criteria 9 Pulse counter 1 pulse value alternating with reading2 10 Pulse counter 2...

Страница 35: ...eration days since manufacture alternating with days of operation after reaching an energy value 10 kWh 7 M bus address 8 Serial number 9 Firmware version Level 3 Statistics Loop 1 30 Semimonthly values date alternating with heat energy cooling energy volume value tariff register 1 value tariff register 2 1 If the meter has 3 pulse inputs their values follow 2 Level 4 Maximum Values Loop 1 Maximum...

Страница 36: ... select the respective item in the parametrizing loop and then push the button once again for 2 3 seconds As an aid after 2 seconds the editing pen will be displayed bottom left in the LCD see below picture As soon as it appears you have to let go of the button Then the current display will start blinking By pressing the push button briefly you can switch to the next option By pressing the push bu...

Страница 37: ...or software are necessary The optocoupler and Device Monitor are available as accessory equipment The optical infrared interface will be activated by automatically sending a header according to EN 13757 3 Baud rate 2400 baud Then you can communicate with the meter for 4 seconds After every valid communication the meter is open for another 4 seconds Afterwards the display is deactivated The number ...

Страница 38: ...mmets Close the calculator Protect the calculator against unauthorized opening using one of the numbered adhesive seals enclosed to the modules stick it upon the seal destroyed The added bar code label can be used for the purpose of documentation 10 3 Exchanging the battery The meter s battery is easy to exchange by authorized technical personnel our replacements only Replaced batteries must be di...

Страница 39: ...ls enclosed The added bar code label can be used for the purpose of documentation The battery is a backup in case of a power outage The power pack cable A has two connectors plug the one connector onto the contact fingers on the left hand side of the PC board Then feed the cable through the meter s leftmost cable feedthrough viewed from the front after removing the blind grommet The other connecto...

Страница 40: ...e 1 at third place H 10 Error in flow measurement system 1 at fourth place H 08 Temperature sensor 2 short circuit 1 at fifth place H 04 Temperature sensor 2 cable break 1 at sixth place H 02 Temperature sensor 1 short circuit 1 at seventh place H 01 Temperature sensor 1 cable break 1 at eighth place Temperature sensor 1 is the right temperature sensor viewed from the front Example Temperature sen...

Страница 41: ...ontaminated flow sensor Mechanical flow sensor Scanning is not functioning properly H 08 Temperature sensor 2 short circuit No energy calculations The register for energy is not being updated no new data is being stored Sensor cable damaged H 04 Temperature sensor 2 cable break No energy calculations The register for energy is not being updated no new data is being stored Sensor cable damaged H 02...

Страница 42: ...e observed The installation has to be performed by authorized skilled persons If the regulations and the information in the installation and operating instruction manuals are not strictly followed or if the installation is shown to be faulty any resulting expenses will be charged to the company responsible for the installation Recommended type of cable Telephone cable J Y ST Y 2x2x0 8mm It is impo...

Страница 43: ...d Baud rate 1200 2400 4800 9600 14400 19200 38400 56000 57600 115200 1 3 2 Default factory settings Communication parameters 9600 bps 8N1 data format 8 data bits none parity 1 stop bit Update Rate Data from Meter 600 s Modbus Slave ID 1 Automatic Slave ID 0 deactivated Acceptable values 1 247 If the automatic Slave ID is activated set to 1 the M Bus address which is set in the meter is used for co...

Страница 44: ...flow temperature temperature difference long telegram for walk by read out energy heat cooling energy pulse input 1 to pulse input 3 total volume information message 15 monthly or 30 semimonthly values compact mode Encryption AES Advanced Encryption Standard key length 128 bits 1 4 1 2 Radio configuration Parameter Possible settings Factory setting Battery lifetime estimated 10 years Mode S1 T1 C1...

Страница 45: ...mpact telegrams alternately During installation mode at least one meter of the version being installed inlet or outlet flow heat or heat cooling pulse inputs display units must be read out with the Engelmann Read out Software walk by The format of the telegram will be stored locally in the PC in an xml file After completion of the installation mode only compact telegrams will be transmitted 1 4 1 ...

Страница 46: ...rder to guarantee the set battery life Eco Mode 10 or 6 years You can find more information in the Manual LoRa Module For pulse input option the telegram type Engelmann must be selected 1 4 2 3 Activation of the radio interface The radio interface is deactivated by default and can be activated in one of the three following ways a NTC interface via Elvaco OTC App further information is available in...

Страница 47: ...ion is shown to be faulty any resulting expenses will be charged to the company responsible for the installation 1 5 1 Relevant norms standards literature pulse inputs IEC 60364 4 41 2005 12 Low voltage electrical installations Part 4 41 Protection for safety Protection against electric shock IEC 60364 4 44 2007 08 Low voltage electrical installations Part 4 44 Protection for safety Protection aga...

Страница 48: ...rument When setting up the meter it may be necessary to adjust the meter reading of the instruments connected and the pulse value using the Device Monitor software The maximum lenghth of the pulse cable is 10 meters For transmitting the values of the pulse inputs via radio transmission must be set using the Device Monitor software if the meters were not already ordered with the transmission of the...

Страница 49: ...6 2 Pin assignments 4 wire cable Color Connection Yellow IA1 Green IA1 Brown IA2 White IA2 2 Retrofitting with an Additional Communication Interface During installation of the retrofitting module observe the ESD requirements according to EN 61340 5 1 This means that on location an antistatic wrist strap with an integrated 1 MΩ resistor has to be used which must be connected to a proper spot This i...

Страница 50: ... Repeat this with the other opening Now the upper housing piece can be taken off Plug the interface module on the right side of the PC board see picture 3 The cables are to be fed through the rightmost cable feedthroughs into the calculator after removing the blind grommets Close the calculator Protect the calculator against unauthorized opening using one of the numbered adhesive seals enclosed to...

Страница 51: ...ge Errors excepted To remove a module the upper housing piece must be carefully pressed against the rear panel of the lower housing piece during opening the calculator Thus the two rear snap fits of the upper housing piece lever out the module of the PC board see picture 4 ...

Страница 52: ...le and setup wireless M Bus radio off wireless M Bus radio on LoRa on LoRa off pulse value pulse output 1 or 3 Display depending on plugged module and setup radio encryption AES off radio encryption AES on LoRa pending LoRa connected pulse value pulse output 2 4 Imprint Engelmann Sensor GmbH Rudolf Diesel Str 24 28 69168 Wiesloch Baiertal Germany E Mail info engelmann de www engelmann de 5 Contact...

Страница 53: ...u froid Respecter les règles techniques des équipements électriques Le produit est conforme aux exigences essentielles contenues dans la directive européenne sur la compatibilité électromagnétique directive CEM 2014 30 EC Les signes relevant de l étalonnage du compteur ne doivent pas être endommagés ou enlevés sinon la garantie et l approbation expirent Pour assurer la stabilité de la mesure du co...

Страница 54: ... dans le flux de retour Installation dans le flux allé 3 2 Pictogrammes de type du compteur sur l étiquette d identification Compteur de chaleur Compteur de froid 4 Montage du capteur de débit 4 1 Montage des SensoStar E SensoStarQ et SensoStar U Purger les conduits selon les règles reconnues de la technique Ensuite fermez les vannes Ouvrez les vannes de vidanges pour enlever la pression Videz la ...

Страница 55: ...e que la lecture de l écran soit idéale 4 3 Montage du compteur SensoStar T dans un raccordement monotube TECHEM Le débitmètre à jets multiples MSH TE1 dispose d une connexion M62x2 externe selon la norme EN ISO 4064 4 EN 14154 2 TE1 et doit être installé sans adaptateur Montage du débitmètre de type MSH TE1 dans un raccordement monotube Purgez les conduits selon les règles reconnues de la techniq...

Страница 56: ...z le sens du flux voir sur raccordement monotube MINOL Retirer le couvercle du raccordement ou l ancien compteur à l aide d une clé compteur à l aide d une clef appropriée Retirez l ancien joint et nettoyez la surface d étanchéité et le filetage Si nécessaire nettoyez avec un liquide de nettoyage approprié Placez le nouveau joint profilé avec la surface plane vers le haut Graissez le filetage exté...

Страница 57: ...ttoyage approprié Graissez le filetage extérieur M77x1 5 du débitmètre et le joint torique 66 35x2 62 avec une fine couche de graisse de silicone autorisée pour le contact avec des produits alimentaires Visser le nouveau compteur fermement à la main puis serrez avec une clé adéquate jusqu à la butée métal sur métal Tournez ou placez le calculateur de tel manière que la lecture de l écran soit idéa...

Страница 58: ...rt mural tenez l anneau sous le calculateur et tournez le dans le sens inverse des aiguilles d une montre Puis placez le avec sa surface plane contre le mur à l endroit désiré Il est recommandé de détacher le calculateur dans ces cas même obligatoire Compteurs de froid et hybride chaleur froid Compteur de chaleur haute température SensoStar U température jusqu à 130 C Compteurs de chaleur froid po...

Страница 59: ...rifiez l étanchéité Protéger le compteur et ces sondes contre les manipulations en apposant les scellés et le fil pour sceller 7 Mise en service Ouvrir lentement les valves Vérifiez l étanchéité Vérifiez les points suivants Toutes les vannes sont elles de nouveau ouvertes Est ce que la dimension du compteur de chaleur est bien choisie Vérifiez si le système de chauffage refroidissement est libre l...

Страница 60: ...d impulsion 2 4 Volume total en m 5 Date actuelle alternante avec heure actuelle 6 Message d information affichage en alternance binaire et hexadécimal 7 Registre tarifaire 1 en alternance avec le N du registre tarifaire et ces critères 8 Registre tarifaire 2 en alternance avec le N du registre tarifaire et ces critères 9 Compteur d impulsions 1 valeur d impulsions en alternance avec consommation2...

Страница 61: ...rnance avec jours de fonctionnement après la saisie d un consommation 10 kWh 7 Adresse M bus 8 Numéro de série 9 Version du logiciel Niveau 3 Boucle statistique 1 30 Valeurs semi mensuelles Alternant date relevé de compteur chaleur froid volume valeur registre tarifaire 1 valeur registre tarifaire 2 1 Suivant le interface aussi les valeurs de trois entrées d impulsion 2 Niveau 4 Boucle des valeurs...

Страница 62: ...correspondant dans la boucle de paramétrage puis appuyez à nouveau sur le bouton pendant 2 3 secondes Le stylo édition sera affiché en bas à gauche sur l écran LCD voir image ci dessous Dès qu il apparaît vous devez lâcher le bouton Ensuite l affichage en cours commence à clignoter En appuyant sur le bouton brièvement vous pouvez passer à l option suivante En appuyant sur le bouton plus longtemps ...

Страница 63: ...evice Monitor L optocoupleur et le Device Monitor sont disponibles en accessoire L interface infrarouge optique sera activée en envoyant automatiquement un en tête conformément à EN 13757 3 Vitesse de transmission 2400 baud Ensuite vous pouvez communiquer avec le compteur pendant 4 secondes Après chaque communication valide le compteur est ouvert encore 4 secondes Ensuite l affichage est désactivé...

Страница 64: ...rmez le calculateur Après installation du module l ancien scellé doit être impérativement remplacé par un nouveau scellé numéroté livré avec le module à coller sur l ancien scellé L autocollant joint portant le code barres peut être utilisé en guise de documentation 10 3 Changer la pile La pile peut être changée par le personnel autorisé N utilisez que nos piles originales Les piles usagées doiven...

Страница 65: ...urant Le câble du bloc d alimentation A dispose de deux prises branchez le connecteur noir sur les doigts de contact sur le côté gauche de la carte PC Puis passez le câble à travers le passe câble du compteur le plus à gauche vu de l avant après avoir enlevé l obturation L autre prise est à mettre sur la connexion femelle sur la platine prise de la pile Seul un personnel certifié est autorisé à co...

Страница 66: ...empérat 2 1 à la cinquième place H 04 Câble sonde 2 détériorée 1 à la sixième place H 02 Court circuit sonde de températ 1 1 à la septième place H 01 Câble sonde 1 détériorée 1 à la huitième place Sonde de température 1 est la sonde de température sortant à droite vu de face du calculateur Exemple Détérioration du câble de la sonde de température 1 Message Pile faible Réinitialiser Electronique dé...

Страница 67: ...de débit à ultrasons L air dans le système débitmètre encrassé Capteur de débit mécanique Balayage ne fonctionne pas correctement H 08 Court circuit sonde de température 2 Pas de calcule de la consommation Le registre de l énergie n est pas mis à jour Câble de la sonde endommagé H 04 Câble sonde 2 détériorée Pas de calcule de la consommation Le registre de l énergie n est pas mis à jour Câble de l...

Страница 68: ...allation n est pas correcte les frais qui en résultent seront facturés à la société responsable de l installation Type de câble recommandé Câble téléphonique J Y ST Y 2x2x0 8mm Il est important de s assurer que la topologie du réseau M Bus longueurs de câble et sections transversales convient à la vitesse de transmission 2400 Bd des instruments terminaux 1 2 1 Normes pertinentes Standards Document...

Страница 69: ... Valeurs compatibles 1 247 Si l ID esclave automatique est activé réglé sur 1 l adresse M Bus définie dans le compteur est utilisée pour la communication 1 4 Interfaces radio sans fil Engelmann propose les interfaces radio suivantes Interface wireless M Bus EN 13757 3 4 voir paragraphe 1 4 1 Interface de communication LoRaWAN voir paragraphe 1 4 2 Informations générales sur l interface radio Evite...

Страница 70: ...gramme court conforme à AMR OMS Spec_Vol2_Primary_v301 et _v402 télégramme long pour lecture Walk By télégramme court AMR 1 4 1 3 Activation de l interface radio L interface radio est désactivée départ l usine Elle peut être activée comme suit a La fonction radio peut être activée en appuyant sur le bouton poussoir Fréquence 868 MHz Puissance de transmission jusqu à 14 dBm Protocole M bus sans fil...

Страница 71: ...pulsions afficheurs à l aide du logiciel de lecture Engelmann Le format du télégramme sera ainsi stocké localement dans le PC dans un fichier xml Après l achèvement du mode d installation seuls les télégrammes compacts seront transmis 1 4 1 4 Activation ultérieure du cryptage radio Le cryptage AES peut également être activé ultérieurement Il peut être activé comme suit a Le cryptage peut être acti...

Страница 72: ... 1 4 2 3 Activation de l interface radio L interface radio est désactivée par défaut et peut être activée de l une des trois manières suivantes a Interface NTC via l application Elvaco OTC de plus amples informations sont disponibles dans le mode d emploi de l application Elvaco OTC https www elvaco se Image GetDocument en 269 elvaco otc app manual english pdf b Interface optique via le logiciel d...

Страница 73: ... responsable de l installation 1 5 1 Normes pertinentes Standards Documents des entrées des impulsions IEC 60364 4 41 2005 12 Installations électriques basse tension Partie 4 41 Protection pour la sécurité Protection contre les chocs électriques IEC 60364 4 44 2007 08 Installations électriques basse tension Partie 4 44 Protection pour la sécurité Protection contre les perturbations de tension et l...

Страница 74: ...seront comptées dans l instrument Lors de la configuration du compteur il peut être nécessaire de régler la lecture du compteur des instruments connectés et la valeur de l impulsion à l aide du logiciel Device Monitor La longueur maximale du câble d impulsion est de 10 mètres Pour être en mesure de transmettre des valeurs impulsionnelles par radio vous devez paramétrer la transmission radio avec l...

Страница 75: ...ure 100 ms Intervalle entre impulsions 100 ms 1 6 2 Affectation du câble à 4 fils Couleur Connexion Jaune IA1 Vert IA1 Brun IA2 Blanc IA2 2 Modification avec une interface de communication Lors de l installation du module d adaptation respecter les exigences ESD protection électrostatique conformément à la norme EN 61340 5 1 Cela signifie que sur le lieu de montage du compteur il faut porter un br...

Страница 76: ... avec l autre ouverture Maintenant la partie supérieure du boîtier peut être retirée Incérez le module d interface sur le côté droit de la platine voir image 3 S il a des câbles passez les à travers les orifices en bas à droite du boitier après avoir enlevé les opercules nécessaires Refermez le calculateur Après installation du module l ancien scellé doit être impérativement remplacés par un nouve...

Страница 77: ...retirer un module ouvrir le calculateur comme décrit ci dessus Tout en ouvrant le calculateur pressez méticuleusement l arrête supérieure du couvercle contre l arrête supérieur du boitier partie noire Ainsi les deux fixations à l arrière du couvercle soulèvent le module de la platine voir image 4 ...

Страница 78: ...r 2 Affichage en fonction du module branché et de la configuration radio éteinte OFF radio branchée ON LoRa on LoRa off valeur d impulsions de la sortie d impulsions 1 oder 3 Affichage en fonction du module branché et de la configuration cryptage radio AES éteint OFF cryptage radio AES branché ON LoRa pending LoRa connected valeur d impulsions de la sortie d impulsions 2 4 Impressum Engelmann Sens...