ENFORCER Power Supplies/Chargers
SECO-LARM U.S.A., Inc.
3
1.
Mount the PC board in the desired location or enclosure to be easily accessible for future servicing.
2.
Set the DC power output voltage:
a.
The ST-1206-1.5AQ is set at 12VDC by default. For 6VDC, cut the wire
loop (see Wiring Diagram, pg. 2) and insulate the wire leads.
b.
For ST-2406 series, set the desired DC output voltage (6, 12, or
24VDC) of the power supply using the DIP switch as in Table 1 for
ST-2406-3AQ, or Table 2 for all other ST-2406 series.
IMPORTANT:
Disconnect power before changing these DIP switch
settings (Note the default voltage output setting is 12VDC).
3.
Connect a transformer with appropriate specifications (See Table 3 below)
Table 3:
Output
voltage
ST-1206-1.5AQ
ST-2406-2AQ
ST-2406-3AQ
ST-2406-5AQ
ST-2406-7AQ
ST-2406-10AQ
6VDC
12VAC/20VA
12VAC/20VA
ST-UV16-W50Q
16VAC/50VA
ST-UV16-W100Q
16VAC/100VA
ST-UVDA-W180Q
24~28VAC/180VA
ST-UVDA-W180Q
24~28VAC/180VA
12VDC
ST-UV16-W50Q
16VAC/50VA
ST-UV16-W50Q
16VAC/50VA
ST-UVDA-W100Q
24~28VAC/100VA
ST-UV16-W100Q
16VAC/100VA
ST-UVDA-W180Q
24~28VAC/180VA
ST-UVDA-W180Q
24~28VAC/180VA
24VDC
N/A
ST-UV24-W50Q
24VAC/50VA
ST-UVDA-W100Q
24~28VAC/100VA
ST-UVDA-W180Q
24~28VAC/180VA
24~28VAC/210VA
28VAC/350VA
4.
Connect the wires to their respective terminals (see "Wiring Diagram," pg. 2).
Installation:
Table 1 (ST-2406-3AQ):
Voltage
SW1
SW2
6V
ON
ON
12V
ON
OFF
24V
OFF
OFF
1.
Before connecting any external devices, temporarily
power up the unit and measure the DC output
voltage at the device connection point to avoid
damage to devices. If voltage drop is large, adjust
the voltage using the output voltage trimpot (except
ST-1206-1.5AQ, see Fig.1). Then disconnect power
before connecting external devices.
2.
See ST-2406 Series LED status indicators in Table 4.
3.
The ST-1206-1.5AQ comes with a 3A fuse. The ST-2406-2AQ, ST-2406-3AQ, and ST-2406-5AQ models
come with a 5A fuse. The ST-2406-7AQ and ST-2406-10AQ models come with a 10A fuse. Use only the
correct fuses to prevent short circuits and damage to the power supplies/chargers or the alarm access
control panel.
4.
The automatic low-battery cutoff will cut power when battery voltage drops below 20% of the set output
voltage (ST-2406-3AQ only).
Warning:
1.
Installation and servicing must be performed by qualified service personnel.
2.
The power supply must be installed in accordance with all national and local electrical codes.
3.
Do not use a higher AC input than recommended (rated max. 28VAC).
4.
DISCONNECT THE POWER SUPPLY BEFORE CHANGING THE DIP SWITCH SETTINGS OR
PERFORMING ANY TYPE OF SERVICE. There are no user serviceable parts inside.
5.
Do not touch any exposed metal parts, electrical, or electronic components as these parts may become
very hot under load
6.
DO NOT USE METAL SPACERS TO MOUNT THE POWER SUPPLY'S PC BOARD.
7.
Connect these power supplies/chargers only to a rechargeable backup battery. Use of a non-rechargeable
backup battery could result in damage to the power supply/charger or the alarm access control panel.
Table 2 (other ST-2406 series):
Voltage
SW1
SW2
6V
ON
OFF
12V
OFF
OFF
24V
OFF
ON
Notes:
Table 4 (ST-2406 Series):
Green LED Red/Blue LED Status
ON
ON
Normal
OFF
ON
No VAC input
ON
OFF
No VDC output
OFF
OFF
No VAC input and VDC output
Fig. 1
Output voltage
trimpot