Page 17
Installation and Operation Requirements - Solution 2.3
ENGLISH
3.1.3 With Heat Shield AC02762 and Lowered Ceiling
To reduce the clearances of an appliance using a single wall pipe connector, the use of a heat
shield certified with the single wall pipe connector to be used as close as 6" from combustible
materials must be used. Only in this case, the same clearances as a certified double wall pipe
connector can be used . Refer to the booklet in the screen options to obtain the dimensions to
be respected.
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
USA
A
5" (127 mm)
5" (127 mm)
B
6" (152 mm)
6" (152 mm)
C
5" (127 mm)
5" (127 mm)
L
80" (203 cm)
80" (203 cm)
Ve
Ho
L
DISTANCES
18
FROM PIPE CONNECTOR
WITH DOUBLE WALL PIPE CONNECTOR
Canada
USA
D
8 ¼" (210 mm)
8 ¼" (210 mm)
E
15 ¼" (387 mm)
15 ¼" (387 mm)
F
14 ½" (368 mm)
14 ½" (368 mm)
A
B
E
D
CAN
48"
122 cm
US
36"
92 cm
48"
Flush
F
F
C
If the clearance reduction is on the same side as the door handle, position the stove at
a minimum of 6 inches from the side wall (clearance B), otherwise it may be located at
the clearance shown in the table above.
18
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances
above mentioned.