enervent Pallas HP Скачать руководство пользователя страница 4

4

GENERAL

Enervent Pelican HP, Pegasos HP and Pallas HP are 

air handling units that consists of (among other 

components) a rotating heat recovery wheel and an 

extract air heat pump.  Units are designed to recover 

heat energy from the extract air which is blown out of 

the building. Units also cool the supply air depending 

the adjustments and circumstances. Units are not 

designed to function as a primary heat source of the 

building. 

NOTE!

NOTE:

 For the heat pump to work properly the 

extract air must be warm enough (extract air to 

unit must be at least +20 °C). 

Because the integrated extract-air-source heat pump 

does not require a separate outdoor unit, it is also 

suitable for sites where the installation of outdoor 

units is restricted by regulations on façades. The unit 

is suitable for both new buildings and renovation 

projects. 

MAINTENANCE

For maintenance see Enervent eAir Installation 

instructions.

NOTE!

NOTE: 

The heat pump in the ventilation 

unit may contain more than 2.39 kg of R410A 

HFC refrigerant. The European Union's F-gas 

Regulation No 517/2014 states that the 

operators of equipment containing more than 

2.39 kg of R410A HFC refrigerant are responsible 

for maintaining a service record of such 

equipment and carry out annual refrigerant 

leakage checks by qualified personnel.

NOTE!

NOTE:

 : Ventilation units equipped with 

Emerson© EC3-D73 Digital superheat controller 

(concerns Pegasos and Pallas HP units) contains 

a VRLA battery= valve regulated rechargeable 

lead-acid battery. The battery must NOT be 

disposed of with other commercial waste. 

Instead, it is the user’s responsibility to pass it 

to a designated collection point for the safe 

recycling of batteries.

READ ME FIRST

This document is intended for everyone involved 

in installation of Enervent ventilation units. The 

equipment described in this manual is to be installed 

by skilled persons only, according to the instructions 

given in this manual, Enervent eAir Installation 

Instructions, and local law and regulations. Failure to 

comply with instructions in this manual and Enervent 

eAir Installation Instructions will void the warranty of 

the equipment, and possibly result in harm to people or 

property. 

The equipment described in this manual is not to be 

used by persons (including children) with reduced 

physical, sensory or mental capabilities, or lack of 

experience and knowledge, unless they have been 

given supervision or instruction concerning use of the 

equipment by a person responsible for their safety.

NOTE!

NOTE: 

The Unit must not be tilted more than 

45° during transport.

WARNING!

WARNING:

 Before operating the heat pump 

in the Pallas HP models, remove the transport 

support for the compressor mounting plate 

as indicated in the picture below. Pull the rod 

completely out from the compressor mounting 

plate to disengage the transport support.

WARNING!

WARNING:

 Airflow calibration must be done 

before engaging the heat pump. In Pegasos and 

Pallas HP eAir units the heat pump is engaged 

from inside the electrical connection box: Circuit 

breaker F1.

Содержание Pallas HP

Страница 1: ...27 12 2016 Enervent HP Technical Data and additional information to Enervent eAir Installation Instructions EN...

Страница 2: ...2...

Страница 3: ...3 Installation manual EN Contents READ ME FIRST 4 GENERAL 4 MAINTENANCE 4 TECHNICAL DATA 5 SERVICE RECORD FOR HEAT PUMP UNIT 6 WIRING DIAGRAMS 7 CONTROL DIAGRAM 14...

Страница 4: ...units contains a VRLA battery valve regulated rechargeable lead acid battery The battery must NOT be disposed of with other commercial waste Instead it is the user s responsibility to pass it to a des...

Страница 5: ...Pelican HP pre filled by component supplier Pegasos HP 1 2 l Pallas HP 1 9 l Netto Weight of the Unit Pelican HP 149 5 kg Pegasos HP 244 6 kg Pallas HP 445 6 kg Superheating control fuse F3 Pegasos an...

Страница 6: ...at Pump Unit Location of the Heat Pump Unit Street address Postal Code City Country Unit system identification Unit Model Serial Number Refrigerant Type Refrigerant amount Test done by Date Test passe...

Страница 7: ...7 Installation manual EN WIRING DIAGRAMS...

Страница 8: ...8...

Страница 9: ...9 Installation manual EN...

Страница 10: ...10...

Страница 11: ...11 Installation manual EN...

Страница 12: ...12...

Страница 13: ...13 Installation manual EN...

Страница 14: ...14 CONTROL DIAGRAM...

Страница 15: ...15 Installation manual EN MD ELECTRICAL CABINET UNIT...

Страница 16: ...16 MD ELECTRICAL CABINET UNIT...

Страница 17: ...17 Installation manual EN MD ELECTRICAL CABINET UNIT...

Страница 18: ...18 ELECTRICAL CABINET UNIT...

Страница 19: ...19 Installation manual EN ELECTRICAL CABINET UNIT...

Страница 20: ...20 ELECTRICAL CABINET UNIT...

Страница 21: ...21 Installation manual EN...

Страница 22: ...22...

Страница 23: ...23 Installation manual EN...

Страница 24: ...Enervent Oy Kipin tie 1 FI 06150 PORVOO Phone 358 207 528 800 enervent enervent com www enervent com...

Отзывы: