If something is wrong with your ventilation unit:

• 

Read the chapter “ADJUSTMENTS” on page 10. 

• 

If the unit is giving an alarm, look for a solution in 
the table “TROUBLESHOOTING” on page 16.

TROUBLESHOOTING

WARNING

WARNING:

 If in doubt about any of the 

procedures please contact your local service 

representative.

Alarm Description

Alarm
limit

Symptoms

Possible reason

Action

Notes

FILS

Service 

reminder.

4 or 6
months

Time for regular 

maintenance.

Change filters.

Press any 

button for 5 

seconds to 

acknowledge.

Err

Sensor 

malfunction.

A sensor is short- or open 

circuited.

Check the connections 

and wiring of sensors.

- - - -

Downloading.

eWind panel is 

downloading data from ESC 

main board.

Normal at start-up. 

Otherwise check the 

eWind connection cable.

oFFE

Stop mode.

Ventilation off.

Ventilation unit is 

commanded to stop mode 

by an external control 

system.

AL1

Water heater 

coil in danger 

of freezing.

+8 °C

Supply air cold.

Water coil has frozen / is 

about to freeze:

•  Circulation pump has 

stopped.

•  Heat exchanger is not 

rotating.

•  Actuator of the water coil’s 

control valve is faulty.

•  Extract fan has stopped.

 

Restart the pump.
 

Replace the motor or the 

belt.
Replace the actuator.
 

Find out why / replace 

the fan.

The unit will 

not start before 

the alarm 

condition has 

been removed 

and the alarm 

acknowledged 

by pressing 

any button on 

the operating 

panel.

AL2

Supply air 

after HRW is 

cold.

+5 °C

Supply air cold.

Heat exchanger is not 

rotating:

•  Drive belt is broken.
•  Drive belt is slipping. 

•  Heat exchanger motor has 

broken down.

 

Replace the drive belt.
Clean or change the belt 

and the heat exchanger.
Replace the heat 

exchanger motor.

The ventilation 

unit enters the 

malfunction 

status, which 

means that the 

extract air fan 

is at minimum 

speed and the 

supply air fan 

has stopped.

The alarm is 

automatically 

acknowledged 

after the fault 

condition is 

removed.

AL3

Supply air 

cold.

+10 °C 

Supply air cold.

Extract fan has stopped.

Replace the fan.

Extract filter is blocked.

Replace filter.

Ventilation is adjusted 

incorrectly / not adjusted 

at all.

Readjust/adjust 

ventilation according 

to the ventilation 

system design, using 

appropriate measuring 

tools.

Heat insulation for the 

ducts is inadequate.

Check the thickness of 

the insulation in supply 

and extract air ducts and 

add insulation, if needed.

Ventilation unit fan speed is 

incorrect.

Always use the fan 

speed specified by 

the ventilation system 

designer (even in winter).

Содержание eWind

Страница 1: ...User instructions ENG 25 01 2016 Enervent eWind...

Страница 2: ...2 Copyright Ensto Enervent 2016 Unauthorized copying and lending are prohibited Approvals and version history Revision Date Description of change Approved by 0 0 2016 01 25...

Страница 3: ...Using ventilation in cold season 8 ENHANCED FEATURES 8 Information view 8 eWind Info list 8 Measurements view 9 eWind Measurements list 9 Service reminder view 9 Time to service 9 Settings view 10 ADJ...

Страница 4: ...he primary function of the unit The unit is also used for recovering heat energy from extracted air Depending on the model it can be used for cooling supply air during summertime It can also be used f...

Страница 5: ...ure display 3 Mode button 4 Eco button 5 Temperature button Button display Description Mode display Current use mode Temperature display Target supply air temperature Mode button Selection of use mode...

Страница 6: ...ntilation unit runs normally in the Home mode To select 1 Press the Mode button to scroll to mode 2 The ventilation system adjusts itself to the new setting Home mode with boosted ventilation 3 When e...

Страница 7: ...w the system to make slight changes to the defined temperature and ventilation values to save energy In Eco mode the system will not react to temperature changes as quickly as in normal mode but waits...

Страница 8: ...you increase the risk of ice build up in your ventilation unit This risk is higher during extreme freezing out conditions and with high indoor humidity extensive shower use and lots of drying laundry...

Страница 9: ...C TE45 ESW only Other models show 0 12 r7 Pre heated outside air temperature CHG AGH electrical pre heater C TE02 Only if equipped with CHG AGH or electrical pre heater 32 r8 Relative humidity of extr...

Страница 10: ...supply air Ventilation is not sufficient If the ventilation is not sufficient 1 Make sure the filters are clean and do not need to be replaced If the filters are dirty replace them as instructed in c...

Страница 11: ...The error code is visible in the display All units are stopped AB fault tolerant The error code flashes in the display in 2 second intervals The exhaust fan runs in minimum speed Service Text FILS is...

Страница 12: ...der prompt FILS when the service period has expired Acknowledge the FILS service reminder after maintenance by pressing any button on the eWind operating panel for 5 seconds NOTE When performing a mai...

Страница 13: ...e is switched off NOTE For LTR series units The power cuts off when the service hatch is opened 1 Open the service hatch 2 Remove the filter from the ventilation device 3 Remove the filter fabric from...

Страница 14: ...angers NOTE Visit the HelpCenter on our webpage www enervent fi for videos showing the maintenance tasks To replace DANGER DANGER Turn off the ventilation unit by switching off the main power supply b...

Страница 15: ...ating the exchanger Leave the holders on the heat exchanger 8 Loosen the U beam on one side of the heat exchanger by removing the screws under the U beam rubber gasket 9 Unscrew the hexagonal screw of...

Страница 16: ...d Restart the pump Replace the motor or the belt Replace the actuator Find out why replace the fan The unit will not start before the alarm condition has been removed and the alarm acknowledged by pre...

Страница 17: ...nit service hatch is open Close the service hatch TE30 temperature sensor is faulty Repair or change the sensor AL7 Supply air hot Fire hazard 55 C Supply air hot Fire hazard Check for any heat source...

Страница 18: ...18...

Страница 19: ...19 User instructions EN...

Страница 20: ...sto com www enervent com Enervent eWind ECO C 3 sec 120 min Quick guide for user ENG Acknowledge the FILS service reminder after maintenance by pressing any button on the eWind operating panel for 5 s...

Отзывы: