95
Professional installation instructions
Parameter list
Parameter
Description
Factory
setting
Note
Modbus
register
Field
setting
c1
Extract fan speed, mode 1,
control range: 20–100 %, step: 1 %
36 %
Away mode
102
c2
Supply fan speed, mode 1,
control range: 20–100 %, step: 1 %
35 %
Away mode
100
c3
Extract fan speed, mode 2,
control range: 20–100 %, step: 1 %
56 %
Home mode
52
c4
Supply fan speed, mode 2,
control range: 20–100 %, step: 1 %
55 %
Home mode
51
c5
Extract fan speed, mode 3,
control range: 20–100 %, step: 1 %
83 %
Max. power also during humidity- and
carbon dioxide boosting
74
c6
Supply fan speed, mode 3,
control range: 20–100 %, step: 1 %
80 %
Max. power also during humidity- and
carbon dioxide boosting
72
c7
Extract fan speed, mode 4,
control range: 20–100 %, step: 1 %
100 %
Manual boosting
68
c8
Supply fan speed, mode 4,
control range: 20–100 %, step: 1 %
100 %
Manual boosting
67
c9
Time limit for manual boosting (mode 4)
control range: 0...4 h, step: 1 h
2 h
Setting time limit of 0 h disables mode
4 and activates 3 speed external control
66
c10
Extract fan speed, fireplace/range hood
mode
control range: 20–100 %, step: 1 %
40 %
55
c11
Supply fan speed, fireplace/range hood
mode
control range: 20–100 %, step: 1 %
50 %
54
c12
Time limit for fireplace mode/selection of
range hood mode
control range: 0...15 min step: 1 min
10 min
Setting time limit of 0 min replaces the
fireplace mode with the range hood
mode.
56
c13
Heat recovery defrosting on or off
Off
Coil 55
c14
Service reminder interval
4 or 6 months
4
Register value in days
538
c15
CHG/AGH preheating and AGH precooling,
on or off
On
Coil 58
c16
CHG/AGH external temperature TE01, below
which the preheating is used
control range: 0…10 °C, step 1 °C (for
preheating)
5 °C
592
c17
CHG/AGH preheating is not in use when the
outdoor air temperature (TE01) rises above
value (c16) + (c17)
control range: 1…5 °C, step 1 °C
1 °C
593
c18
CG cooling or CHG precooling on/off
On
Applies to CG and CHG heat
exchangers
Coil 52
c19
Outdoor temperature TE01, above which
precooling/cooling is allowed
17 °C
164
c20
AGH outdoor temperature, above which the
earth duct is used
control range: 15…25 °C, step 1 °C, (for
precooling)
20 °C
629
c21
AGH precooling is not in use when the
outdoor air temperature (TE01) drops below
value (c20-c21)
control range: 1…5 °C, step 1 °C
2 °C
630
c22
Temperature setting for air temperature after
the electric preheating
control range: –10…–20 °C, step: 1 °C
–15 °C
591
Содержание eWind Pinion
Страница 13: ...13 Ammattilaisen asennusohje Wifi moduulin asennus 1 2 A B A 3 4...
Страница 24: ...24...
Страница 25: ...25 Ammattilaisen asennusohje...
Страница 28: ...28 Pinion eWind Pinion Premium eWind Installationsanvisningar f r ventilationsaggregat Svenska...
Страница 39: ...39 Installationsanvisningar f r yrkesfolk 1 2 A B A 3 4 Installation av Wifi modulen...
Страница 50: ...50...
Страница 51: ...51 Installationsanvisningar f r yrkesfolk...
Страница 54: ...54 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pinion eWind Pinion Premium eWind...
Страница 65: ...65 Installasjonsinstrukser for fagfolk 1 2 A B A 3 4 Installasjon av Wifi modulen...
Страница 76: ...76...
Страница 77: ...77 Installasjonsinstrukser for fagfolk Pinion Premium eWind E ON...
Страница 80: ...80 Pinion eWind Pinion Premium eWind Installation instructions for the ventilation unit English...
Страница 91: ...91 Professional installation instructions Installation of the Wifi module 1 2 A B A 3 4...
Страница 102: ...102 102...
Страница 103: ...103 Professional installation instructions 103...