INSTALLATION, USE AND
MAINTENANCE
SUNWAY STRING BOX
LT 1500V 24 INPUTS
Rev. 02 - Error! Unknown document property
name.
41 / 43
Figure 20: Maximum dimensions of the cable lugs to be used for the output cables
11.6.3. Connection of functional earth cables
Description
Value
Cables
1
Tightening torque
Nm
3,2-3,7
Max cross-section of the conductor (minimum |
maximum)
mm
2
1.5 | 35
Cable stripping
mm
18
Outer diameter of the cable (minimum | maximum)
mm
9 | 17
Cable gland
M25
Table 14: Functional earth cable
11.6.4. SPDs
Technical specifications for SPDs are provided in the table below.
Technical Specifications
Value
Rated voltage of system
V
1500
Maximum voltage of system
V
1500
Rated discharge current
kA
15
Response time
ns
25
Residual current
mA
< 1
Configuration
Y connection of 3 SPDs as varistors
UP level of protection (L-L / L-PE)
kV
5
Removable cartridges
Yes
UL94 Fire resistance
V-0
EN 50539-11 category
Type 2
Table 15: SPDs technical specifications