background image

Manual and Configuration

Enertex® KNX IP Secure Router    

Enertex

®

 Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - Deutschland - 

[email protected]

Содержание Enertex KNX IP Secure Router

Страница 1: ...Manual and Configuration Enertex KNX IP Secure Router Enertex Bayern GmbH Ebermannst dter Stra e 8 91301 Forchheim Deutschland mail enertex de...

Страница 2: ...t claim to be complete or correct Inhalt Security Notes 3 Assembly and connection 3 Comissioning 3 Boot 3 Displays 3 Reset 4 Functional Overview 4 ETS Parameter 4 Terms 4 ETS 5 6 6 and ETS 5 7 0 5 Ver...

Страница 3: ...short time At the end of the boot process the IP address of the device is shown in the display If the IP address assignment is done via DHCP server the boot time is extended accordingly As soon as KN...

Страница 4: ...communication and programming mode Power indicator OLED display for status messages parameter displays etc Special functions Configuration via ETS and Telnet SNTP server Measurement of the TP bus volt...

Страница 5: ...A simple TCP server on port 23 that enables direct text based communication with the IP device Telnet is a de facto standard used at the window level e g with Putty is addressed Secure Mode If the dev...

Страница 6: ...his click on Topology directly above Dynamic Folders see Figure 1 you will find the settings for the Multicast of the Backbone Network latency see Figure 1 can be changed if the routing is over a larg...

Страница 7: ...all parameters are then transmitted in encrypted form although e g Tunnel connections are still unencrypted Secure Tunnelling If activated the tunnel connections can only be established via KNX Secure...

Страница 8: ...property Multicast Address Is given by the backbone configuration see Figure 1 Device specific parameters General Figure 4 General settings of the device Name Options Description Text The ETS has man...

Страница 9: ...hibit programming from TP side off on See parameter dialog Max number of telegrams to KNX TP 5 50 See parameter dialog Standard tunnel preferred IP Enertex devices offer the possibility for standard t...

Страница 10: ...controlled by default with a connection timeout of 1 second This may be too short for connections over the Internet UDP Connection Timeout 1 0 8 0 sec Tunnel X should preferably be used for communicat...

Страница 11: ...scription Physically addressed filter block route The physically addressed telegrams e g actuator programming may be routed blocked or filtered via the routing This affects all communication related t...

Страница 12: ...ng Groups 14 and 15 are grouped together to form a block Main Group 16 to 31 filter block route Group telegrams can be routed blocked or filtered via the routing The groups 16 and 31 are here combined...

Страница 13: ...or filtered via the routing With this function the parameter dialog can be opened for this purpose Extended Group Address Filter For both directions in addition to the block oriented filtering of grou...

Страница 14: ...inactive filter block forward Group telegrams of this main group can be routed blocked or filtered via the routing If the filter is not active the behavior of the parameters of Figure 8 and Figure 9...

Страница 15: ...mask 255 255 255 0 tpconfig Show KNX parameters KNX bus state up KNX address 15 15 000 Serial number 00 a6 00 00 00 01 tpconfig help set Set KNX parameters via the telnet interface Set the TP address...

Страница 16: ...KNX Number of telegrams that could not be sent to the KNX bus TX tunnel re req Number of telegrams that had to be repeated in the tunnel connections TP bus voltage Current bus voltage at the time of...

Страница 17: ...unaddr setall tunaddr help KNX address of a tunnel read tunaddr or change e g tunaddr 1 15 15 240 set all tunnel addresses consecutively from a certain start address tunaddr setall 15 15 15 or reset t...

Страница 18: ...programming the secure mode this is a security risk factory_reset Reset to factory settings and reboot die Test hardware watchdog Executes reset reboot reboot logout end Telnet Session Latest document...

Страница 19: ...r 2 Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other materials provided with the distribu...