Section 2: Installation Introduction

Introduction

This geothermal heat pump provides heated water and chilled 
water as well as optional domestic water heating capability. 
Engineering and quality control is built into every geothermal 
unit. Good performance depends on proper application and 
correct installation.

Notices, Cautions, Warnings, & Dangers:

“NOTICE” Notification of installation, operation or 
maintenance information which is important, but which is NOT 
hazard-related.

“CAUTION” Indicates a potentially hazardous situation or an 
unsafe practice which, if not avoided, COULD result in minor or 
moderate injury or product or property damage. 

“WARNING” Indicates potentially hazardous situation which, if 
not avoided, COULD result in death or serious injury.  

“DANGER” Indicates an immediate hazardous situation which, 
if not avoided, WILL result in death or serious injury.  

Inspection

Upon receipt of any geothermal equipment, carefully check 
the shipment against the packing slip and the freight company 
bill of lading. Verify that all units and packages have been 
received. Inspect the packaging of each package and each unit 
for damages. Insure that the carrier makes proper notation of 
all damages or shortage on all bill of lading papers. Concealed 
damage should be reported to the freight company within 15 
days. If not filed within 15 days the freight company can deny 
all claims.

Note: Notify Enertech Global, LLC shipping department of all 
damages within 15 days. It is the responsibility of the purchaser 
to file all necessary claims with the freight company.

Un-packaging 

Enertech units are mounted to wooden pallets for easy 
handling during shipment and installation. Units are protected 
during shipment with durable cardboard corner posts, top and 
air coil panels. Shrink wrap is applied covering the entire unit 
and attachment to the pallet.

Upon receipt of the unit carefully remove the shrink wrap. 
Using a box cutter slit the shrink wrap on the cardboard top 
and corner posts. Use caution to not damaged the finished 
surface of the unit. Keep all cardboard or other packaging 
material for safe storage and transport to the job site prior to 
installation. 

Remove the front compressor section service panel to locate 
technical documents; manuals, bulletins or instructions and 
accessory items; HWG piping kits, supply/return duct flange 
kits or condensate tubing kits prior to installation.

⚠ 

CAUTION 

Do not operate the geothermal heat pump unit during 

building construction phase.

Unit Protection

Protect units from damage and contamination due to 
plastering (spraying), painting and all other foreign materials 
that may be used at the job site. Keep all units covered on 
the job site with either the original packaging or equivalent 
protective covering. Cap or recap unit connections and all 
piping until unit is installed. Precautions must be taken to 
avoid physical damage and contamination which may prevent 
proper start-up and may result in costly equipment repair.

Storage

All geothermal units should be stored inside in the original 
packaging in a clean, dry location. Units should be stored in 
an upright position at all times. Units should not be stacked 
unless specially noted on the packaging.

Removal and Disposal

All Geothermal units removed from service should have 
all components, oils, antifreeze and refrigerants properly 
disposed of according to local and national environmental 
recycling codes, regulations, standards and rules.

Pre-Installation

Special care should be taken in locating the geothermal unit. 
Installation location chosen should include adequate service 
clearance around the unit. If units are being placed on racking, 
the unit must be placed on a solid foundation. All units should 
be located in an indoor area where the ambient temperature 
will remain above 55°F and should be located in a way that 
piping and ductwork or other permanently installed fixtures do 
not have to be removed for servicing and filter replacement.

Содержание WD240

Страница 1: ...Installation OperationsManual WD 20 30 TON MODELS WATER TO WATER HEAT PUMPS Revision D 20D814 10NN 20D814 10NN...

Страница 2: ...10 Section 6 Antifreeze Antifreeze Overview 11 Antifreeze Percentages by Volume 12 Section 7 Controls Features 13 Sequence of Operation 17 Section 8 Wiring Diagrams WD 240 Series WD 240 Series Wiring...

Страница 3: ...9 Hot W ater C onfiguration 10 Return Air O ptions 11 Discharge Air O ptions 12 Blow er O ptions 13 Exchanger O ptions 14 15 Standard two stage dual single stage compressors Section 1 Model Nomenclat...

Страница 4: ...the unit carefully remove the shrink wrap Using a box cutter slit the shrink wrap on the cardboard top and corner posts Use caution to not damaged the finished surface of the unit Keep all cardboard o...

Страница 5: ...Board Logic Board operates the compressor and protects unit by locking out when safety switches are engaged It also provides fault indicator s Terminal Strip Provides connection to the thermostat or...

Страница 6: ...ain above 55 F and should be located in a way that piping and ductwork or other permanently installed fixtures do not have to be removed for servicing and filter replacement Electrical All wiring line...

Страница 7: ...F 25 F 20 F 15 F 10 F 100 F 110 F 115 F 120 F 125 F 130 F SCROLL COMPRESSOR OPERATING CONDITIONS WATER TO WATER HEATING MODE OPERATION Source Entering Water Temperature 70 F 65 F 60 F 55 F 50 F FAILUR...

Страница 8: ...V Physical Dimensions 20 30 Ton Series Model Ground Hydronic Inlet Outlet Inlet Outlet 20 Ton 2 0 MPT 2 0 MPT 2 0 MPT 2 0 MPT 30 Ton 2 0 MPT 2 0 MPT 2 0 MPT 2 0 MPT Physical Data 20 Ton 30 Ton Compres...

Страница 9: ...0 0 101 2 113 9 150 7 380 3 173 0 ea 25 0 ea 0 0 0 0 50 0 56 3 80 8 575 3 132 0 ea 23 7 ea 0 0 0 0 47 4 53 3 70 WD240 Model Voltage Code HWG Option 60 Hz OR 50 Hz6 Power Compressor Notes 1 All line a...

Страница 10: ...nstallation Potential Problem Chemical s or Condition Range for Copper Heat Exchangers Cupro Nickel Heat Exchanger Ranges Stainless Steel Heat Exchanger Ranges Scaling Calcium Magnesium Carbonate Less...

Страница 11: ...des The following are some general observations about the types of brines presently being used Methanol Wood grain alcohol that is considered toxic in pure form It has good heat transfer low viscosity...

Страница 12: ...precautions may result in fire injury or death Never work with 100 alcohol solutions Notes 1 Consult with your representative or distributor if you have any questions regarding antifreeze selection or...

Страница 13: ...be achieved in two ways 1 A manual toggle switch to select the heating or the cooling hydronic control Aquastat or 2 A cooling thermostat which powers the coil of a single pole double throw relay to...

Страница 14: ...mpressor electrical box This module provides advanced diagnostics and protection See chart on next page for Warning and Alert Codes as well as the DIP Switch Settings for these modules Additional info...

Страница 15: ...INDICATES THAT THE DISCHARGE GAS TEMPERATURE IS ABOVE 220 F 9 THE L TERMINAL CONTROLS A FAULT LED AT THE THERMOSTAT OR DRIVES AN AUXILLIARY FAULT RELAY 10 UNITS THAT DO NOT CONTAIN A FLOW SWITCH WILL...

Страница 16: ...e test mode the LCT SCT sensors will be checked for the proper location based on temperature Sensors are swapped if LCT SCT in cooling or LCT SCT in heating This fault will only show up in the test mo...

Страница 17: ...f the two compressors to avoid nuisance low pressure lockouts Heating 1st Stage Y1 The Accessory A terminal output is energized after the random start timer 10s 20s expires to provide time for externa...

Страница 18: ...18 Enertech Global IOM WD Models Section 8 Wiring Diagrams WD 240 Series Wiring Diagram...

Страница 19: ...19 IOM WD Models Enertech Global Section 8 Wiring Diagrams WD 360 Series Wiring Diagram...

Страница 20: ...rce Water Pressure Out Source Water Pressure Drop F F F F F F Heat of Rejection Extraction BTU HR BTU HR F F F F F F Cooling Heating F F F F F F Heating F F F Heating V A GA A Source Water Temp Differ...

Страница 21: ...al readings listed in the Unit Electrical Data table 5 Check the source water temperature in and out at the P T ports use insertion probe Allow 10 minutes of operation before recording temperature dro...

Страница 22: ...65 3 1 3 2 3 2 3 2 3 1 3 1 3 2 3 5 4 0 3 1 3 1 3 4 3 8 4 4 3 4 3 6 4 0 4 4 5 1 70 3 6 3 7 3 7 3 7 3 6 3 6 3 7 4 0 4 5 3 5 3 6 3 9 4 3 5 0 3 9 4 2 4 5 5 0 5 8 30 0 8 0 8 0 9 1 0 0 9 0 9 1 0 1 0 1 2 0 8...

Страница 23: ...mb Antifreeze is generally required for all closed loop geothermal applications Extreme Southern U S locations are the only exception Open loop well water systems cannot use antifreeze and must have e...

Страница 24: ...make the project easier to complete ECM Temporary Motor Replacement ECM Motor Troubleshooting Troubleshooting a TXV Compressor Troubleshooting Variable Speed Flow Centers Return Conversion for a XT or...

Страница 25: ...loosen pump Take off pump and see if there is an obstruction in the pump If pump is defective replace For pressurized systems check loop pressure Repressurize if necessary May require re flushing if t...

Страница 26: ...a sure record the am p s volts suction discharge pressure Y es Y es If the com p ressor still w o n t pum p rep lace com pre ssor A dd re frigerant to the system N o C heck th e opera tion of the reve...

Страница 27: ...19 24 19 24 18 22 9 12 Superheat Subcooling Conditions Typical R 410A Unit Superheat Subcooling Values Section 10 Troubleshooting Refrigeration Troubleshooting System Faults Mode Discharge Pressure Su...

Страница 28: ...E ____________________ SHIP TO HOMEOWNER ADDRESS Form submitter Ifdifferent than company OTHER NOTES _______________________________________________________________________________ ___________________...

Страница 29: ...aller Company Name ________________________________________________________________________________ City _____________________________State Prov __________ Email ______________________________________...

Страница 30: ...IOM WD Models Revision Table Date Description of Revision Page WD240 360 Wiring Diagram updated 18 19 06JUL2020 WD 240 360 Rev D Nomenclature added 3 WD 240 360 IOM created ALL Section 11 Warranty Fo...

Страница 31: ...31 IOM WD Models Enertech Global This Page Intentionally Left Blank...

Страница 32: ...e most up to date information please visit our website or contact our Customer Service department at info enertechgeo com Statements and other information contained herein are not express warranties a...

Отзывы: