GENERAL INSTRUCTIONS

Adjustment of burner

The burner is from the factory pre-set 
to an average value that must then be 
adjusted to the boiler in question.
All burner adjustments must be made 
in accordance with boiler manu-facturers 
instructions. These must include the 

checking  of  fl ue  gas  temperatures, 

average water temperature and CO

2

 

or O

2

 concentration.

General instructions

The installation of the gas burner 
must be carried out in accordance 
with current regulations and standards. 
The installers of gas burners should 
therefore be acquainted with all regu-
lations and ensure that the installation 
complies with the requirements. The 
installation, mounting and adjustment 
should be made with the greatest 
care and only the correct gas should 
be used.

Operating instructions

The operating instructions accom-
panying the burner should be left 
in a prominent position in the boiler 
room.

Instructions

The user should be thoroughly 
instructed in the function of the gas 
burner and the whole installation. 
The supplier must instruct the user.

Inspection and maintenance

Daily inspection is advisable.

Start up

After  the  burner  has  been  fi tted  to 

the boiler and the electric connection, 
the leakage control, the venting and 
the electric function test have been 
carried out, the burner will be ready 
for start-up.

Howerer, study the sections dealing 
with adjustments of multi-bloc, com-
bustion air and combustion head.
Open the ball valve and switch on the 
main switch. If the burner starts the 
actual adjustment can be made.

Adjustment of burner head

The burner is equipped with an adjust-
ment device changing the po si tion of 
the brake plate in the burner head. This 
is used to adjust the cor rect pressure 
drop over the com bus tion device in 
order to obtain a good pulsation free 
combustion. 

Which position to use depends on 
input and overpressure in the boiler.

172 305 28  07-01

A general rule is that the lower capacity 
the smaller the opening between 
brake plate and combustion device.

Commissioning of installation

Control of the combustion. The com-
bustion quality is checked by means 

of a fl ue gas analysis device. Adjust 

the burner to appr. 20% excess air 

in accordance with the table. Check 

the fl ue gas temperature. Calculate 

the effi ciency. Check also the actual 

gas volume on the gas meter so that 
the correct input is achieved.

Service

Service should only be carried out 

by qualifi ed personnel. Replacement 

parts should be of the same make and 
approved by the same authorities as 
the original. If the burner is converted 

to fi re another gas quality it must be 

re-commissioned. If town gas is to be 

fi red the combustion head must be 

converted and the gas train adjusted 
to suit (e.g.a larger gas armature or a 
different spring in the governor may 
be required).

Gas quality

CO

2

lambda 1,2

0

2

%

max. CO

2

%

Natural gas

10,0

3,5

11,9

LPG

11,5

3,5

13,9

Содержание Bentone BG 300

Страница 1: ...Providing sustainable energy solutions worldwide 178 024 73 3 2016 12 06 Installation and maintenance instruction BG400...

Страница 2: ......

Страница 3: ...5 Multibloc 6 Flame cone 7 Connecting pipe 16 Motor 17 Ignition electrode 18 Transformer 19 Ionization electrode 20 Inner assembly 21 Nozzle 22 Brake plate 8 Air dampe 9 Air intake 10 Gas pressure swi...

Страница 4: ...a min output Nm3 h 1 Gas volume at a max output Nm3 h 1 Max inlet pressure mbar Rated inlet pressure mbar Natural gas LPG Natural gas LPG Natural gas LPG Natural gas LPG 400 60 318 6 2 3 31 8 12 2 10...

Страница 5: ...TECHNICAL DATA 172 215 30 07 01 175 240 M10 Dimensions of ange 140...

Страница 6: ...essure switch maxi 6a Main valve 6b Safety valve 1 7 Valve proving system 9 Air pressure switch 10 Gas burner control Pos 5b 7 Components not required according to EN 676 1 Requiredover1200kWaccording...

Страница 7: ...ed ange and gasket to the boiler If new xing holes must be drilled use the xing ange as a pattern Removal of valve unit from burner Remove the plug in contact from the multi bloc Loosen the union nut...

Страница 8: ...nclosed In case the twin thermostat is in series on incoming phase L1 a loop between the terminals T1 and T2 is necessary Mains connection in accordance with local regulations M1 Burner motor S3 Main...

Страница 9: ...eration LME 11 permits a maximum of three start attempts if the start cycle is uninterrupted Continuous Off Red Yellow Green Colour code table for multi coloured signal lamps Light diodes Status Colou...

Страница 10: ...5 3 s Connecting signal ampli er Alarm control table Red ashing code on signal lamp LED Possible causes Flashing 2 x No ame at End of TSA Defective or obscured ame monitor Defective or obscured fuel v...

Страница 11: ...etestpressureinthesystemshould be 1 5x max inlet pressure or min 150 mbar If any leakage locate the source by means of soapy water or a leak location spray After tightening repeat the test Electric fu...

Страница 12: ...MEASURES AND CHECKS BEFORE START UP 172 205 78 07 01 INNER ASSEMBLY Town gas INNER ASSEMBLY Natural gas LPG INNER ASSEMBLY Biogas UV detector Natural gas LGP 2 5 8...

Страница 13: ...h Net calori c value Gas quality kWh Nm3 kJ Nm3 kcal Nm3 Natural gas 10 3 37 144 8 865 Propane 26 0 93 647 22 350 Butane 34 3 123 571 29 492 Town gas 4 9 17 653 4 213 Bio gas 7 0 25 219 6 019 V Gas vo...

Страница 14: ...ustment knob d use the protective cover as a tool to the desired start gas flow Turn to the right the start gas flow is reduced Turn to the left the start gas flow is increased Max inlet pressure 360...

Страница 15: ...rer study the sections dealing with adjustments of multi bloc com bustion air and combustion head Open the ball valve and switch on the main switch If the burner starts the actual adjustment can be ma...

Страница 16: ...educe the opening turn the knob to the left Toincreasetheopening turnthe knob to the right The adjustment of the position of the brake plate affects the air ow It is thereforealwaysnecessarytomakea ne...

Страница 17: ...e Decide on pressure at which the gas switch should switch off Set this pressure by means of the valve Carefully turn the knob see gure until the gas pressure switch switches off The value shown on th...

Страница 18: ...ubles Trouble free operation is dependent onthreefactors electricity gasandair supply Should there be any changes intheratiobetweenthesethreefactors there is a risk of break downs It has been proved t...

Страница 19: ...Remedy The burner does not start No gas Check that all gas cocks are open No voltage Check fuses thermostats and electrical connections The burner motor fails to start The thermal protection has lock...

Страница 20: ...ities The ignition electrodes are disturbing the ionisation current Adjust the ignition electrodes repole the ignition transformer if necessary Bad earthing Arrange for proper earthing Phase and neutr...

Страница 21: ...ormern Bad combustion Bad draught conditions Check the chimney The flue gas temperature is too high The boiler is overloaded Reduce the quantity of gas The CO2 content is too low Check the boiler with...

Страница 22: ...ormern Bad combustion Bad draught conditions Check the chimney The flue gas temperature is too high The boiler is overloaded Reduce the quantity of gas The CO2 content is too low Check the boiler with...

Страница 23: ...le marquage CE de conformit Ljungby Sweden 141127 27 11 14 ENERTECH AB Bentone Division Box 309 SE 341 26 Ljungby Sweden H kan Lennartsson Enertech AB declares that the above mentioned products compl...

Страница 24: ......

Страница 25: ...ample room ther mostat if any 4 Check that the gas pressure to the burner is sufficient 5 Check that the electric fuses have not blown 6 Make a new attempt to start the burner and check the counter of...

Страница 26: ...ure ment Before After ppm C A mbar mbar Small flame Large flame Measures Date Nm3 gas h Governor O2 CO Flue gas temp Ionisa tion current Pressure Efficiency Fire room Chimney Measure ment Before After...

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: