Shaft rotation and nozzle location

C:  Anti-clock. rotation/

 

Left hand nozzle (seen from  

 

Shaft end)

Gear set capacity
(see pump capacity curves)

Standard model

Solenoid valve 
with cut-off

-  Light oil.

-  Nozzle low up to 45 l/h (approx.  

  460 000 kcal/h - 534 kW).

-  One or two-pipe system.

Pump operating principle

The oil pump has a built in solenoid 
valve which controls the regulator 
cut-off valve giving fast cut-off and 
cut-on function independent of the 
rotational speed.
The gear-set draws oil from the tank 

through the built-in ilter and transfers 

it to the valve that regulates the oil 
pressure to the nozzle line.
All oil which does not go through the 
nozzle line will be dumped through 
the valve back to the return line or, if 
it is a one-pipe installation, back to the 
suction port in the gear-set.

- Two-pipe operation

When the solenoid valve is non-activated, 

the by-pass channel between the 
pressure and return sides of the valve 
is open.
No pressure will then be built up to 
open the valve. It does not matter 
which speed the gear set has.

When the solenoid is activated, this 

by-pass channel will be closed and 
because of the full speed of the gear-
set, the pressure necessary to open 
the valve will be built up very rapidly
which gives a very sharp cut-on 
function.

- One-pipe operation

Bleeding on one-pipe is not automatic, 
and a pressure port must be opened 
to bleed the system.

Cut-off

When the burner stops, the solenoid 

opens the by-pass at the same moment 
which drains all the oil down to the return 
and the nozzle valve closes immediately. 
This gives a very sharp cut-off function.
The cut-on and off can be regulated 
regardless of motor speed and has 
an extremely fast response.

Exchange of ilter

Mounting/dismounting return plug

171 505 37  11-01

APPLICATIONS FOR SUNTEC AT2 45C

One pipe system

Two pipe system

When the solenoid is non activated, 

the torque requirement is low up to 
full motor speed.

C

45

2

AT

By-passed oil 
returned to tank, 
or to suction

Oil under pressure

Oil under suction

To nozzle

Pressure 
gauge port

By-pass
plug

Gear set

Shaft seal

Back to suction

One pipe installation

Two pipe installation

Return

Vacuum 

gauge port

Suction

Low pressure 
adjustment

High pressure ad-
justment

Pressure 
outlet 
or pressure 
gauge port

Blocking solenoid 
valve open

Blocking solenoid
valve closed

By-pass solenoid 
valve open

By-pass solenoid 
valve closed

Содержание Bentone B 30 2A

Страница 1: ...Providing sustainable energy solutions worldwide 178 009 52 2014 01 21 Installation and maintenance instruction B 30 2A...

Страница 2: ......

Страница 3: ...on cable 6 Ignition transformer 7 Reset button 8 Electric panel 9 Cover inspection glass 10 Switch I II 11 Switch 0 I 12 Fan wheel 13 Motor 14 Nozzle assembly adjustment 15 Blast tube 16 Damper motor...

Страница 4: ...en used Burner tube Length of burner tube Incl lange A Measure B A 209 174 A 309 274 Burner tube Oil capacity Capacity Recommended nozzle Recommended Pump pressure Bar kg h kW Mcal h Angle Danfoss Mon...

Страница 5: ...consequently the air volume will then be reduced Condensation in chimney A modern burner works with less excess air and often also with smaller Maintenance Theboiler burnershouldbeexamined regularly...

Страница 6: ...eeig Low capacity Adjust the operating switch to high capacity II Reduce the air volume Turn orange cam towards 0 Increase the air volume Turn orange cam towards 90 Adjust the operating switch back to...

Страница 7: ...itch off power at the main switch and cut off the oil supply 171 305 74 07 01 Open the cover and disconnect the connecting pipes by loosening screw A Service of burner head 1 Loosenorswingouttheburner...

Страница 8: ...RIC EQUIPMENT Oil burner control LOA21 LOA24 Wiring diagram If the boiler is not equipped with wired contacts connect the enclosed contacts to terminals X4 and X6 in accordance with wiring diagram 1 2...

Страница 9: ...Operating switch high low capacity S3 Control thermostat S4 Temperature limiter S5 Micro switch for hinged door S6 Control thermostat high low S7 Main switch T1 Ignition transformer X1 Connection ter...

Страница 10: ...perating position and can now change between full load and low load 4 5 Operating position If the burner operation is interrupted by means of the main switch or the thermostat a new start takes place...

Страница 11: ...y can be disregarded Thetablesdonotinclude any lengths exceeding 100 m as experienceshowsthatlongerlengths are not needed The tables apply to a standard fuel oil ofnormalcommercialqualityaccording toc...

Страница 12: ...nel will be closed and because of the full speed of the gear set the pressure necessary to open the valve will be built up very rapidly which gives a very sharp cut on function One pipe operation Blee...

Страница 13: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Страница 14: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Страница 15: ...f magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocel...

Страница 16: ...nt conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suivan...

Страница 17: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 18: ......

Страница 19: ......

Страница 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: