178 032 32-2    2016-05–19

Installation- and maintenance instruction

B 2

Содержание Bentone B 2 KA

Страница 1: ...Providing sustainable energy solutions worldwide 178 032 32 2 2016 05 19 Installation and maintenance instruction B 2...

Страница 2: ......

Страница 3: ...ustment _________________________________ 14 3 2 1 3 Pressure in front of the brake plate ________________ 14 4 BURNER SERVICING__________________________________________ 15 4 1 Cleaning the fan wheel...

Страница 4: ...always be kept in the vicinity of the installation site Ensure that the fresh air inlet to the room where the burner is located is always open The burner may only be installed by authorized personnel...

Страница 5: ...nt national standards of each respective country Condensation in the flue A modern burner works with lower surplus air and also often with smaller nozzles than older types This raises eficiency but al...

Страница 6: ...of the different types of boiler in existence with varying furnace geometries and furnace loads it is not possible to commit to any given spray angle or spay pattern Note that spray angles and spray p...

Страница 7: ...Protrusion from flange measurement B mm 147 122 197 172 1 2 2 Setting the ignition electrodes Proper setting of the electrodes is essential to ensure satisfactory operation of the burner If the spark...

Страница 8: ...ube mm Protrusion from flange measurement B mm 147 122 197 172 1 3 2 Setting the ignition electrodes Proper setting of the electrodes is essential to ensure satisfactory operation of the burner If the...

Страница 9: ...55 4 88 58 5 10 60 5 30 63 5 51 65 5 70 68 1 35 4 49 53 4 76 56 5 02 59 5 27 62 5 50 65 5 73 68 5 95 70 6 15 73 1 50 4 98 59 5 29 63 5 58 66 5 85 69 6 11 72 6 36 75 6 60 78 6 83 81 1 65 5 49 65 5 82...

Страница 10: ...10 Bentone B 2 General 8 9 10 11 12 16 15 14 13 1 2 3 4 5 7 6 1 5 Description...

Страница 11: ...Photoresistor 4 Electric contact X1 X2 see wiring diagram 5 Air damper 6 Oil pipe 7 Electrodes 8 Fan housing 9 Adjustment of nozzle assembly 10 Frame 11 Control box 12 Blast tube 13 Oil pump 14 Igniti...

Страница 12: ...are not subjected to tensile stress or sharp bending when swinging out the burner or removing it for service Fit the oil ilter so that the ilter cartridge can easily be replaced see Oil ilter Bentone...

Страница 13: ...60 70 80 90 100 110 120 130 8 10 12 14 16 50 60 70 80 90 100 110 120 130 1 10gph 1 25gph 1 50gph 1 75gph 2 00gph 2 25gph 2 50gph 2 75gph Burner output kW Fan pressure mbar Burner output kW Burner out...

Страница 14: ...0 100 110 120 130 1 1 5 2 2 5 3 3 5 4 4 5 50 60 70 80 90 100 110 120 130 8 10 12 14 16 50 60 70 80 90 100 110 120 130 1 10gph 1 25gph 1 50gph 1 75gph 2 00gph 2 25gph 2 50gph 2 75gph Burner output kW B...

Страница 15: ...nozzle assembly until a soot coeficient 0 5 1 is achieved increase the air to give a safety margin of 0 5 1 CO2 before soot is created To throttle more with the shrouded disc smaller reading on the n...

Страница 16: ...ssible 4 5 Removing the blast tube 1 Loosen the two fastening screws one turn 2 Turn to the right and withdraw the blast tube 4 6 Brake plate The preheater plug and the electrodes shall be placed on e...

Страница 17: ...lectric package Loosen the hexagon nut from the stud bolt Pull the electric package backwards and rotate it ca 90 clockwise When required the electric package can be suspended in the cables 4 9 Pump f...

Страница 18: ...al plug G 1 4 8 Return plug 9 Return line G 1 4 10 Pressure regulation 5 1 3 Filter replacement Cut off the power and shut off the oil Remove the pump cover with the aid of a 4 mm Allen key If necessa...

Страница 19: ...he case of a one pipe installation back to the suction connection in the gear wheel pump Two pipe system When the solenoid valve is not activated the return plug channel between the pressure side and...

Страница 20: ...rom occurring Turbulent lows can result in pressure losses and noise in the pipework A typical pipe system usually comprises pipe runs with 4 bends a non return valve a shut off valve and a pre ilter...

Страница 21: ...ction pipe G 1 4 8 Return plug 5 2 3 Venting Venting is only necessary in a one pipe system In two pipe systems the pump is automatically vented by the return pipe 5 2 4 Changing cartridge filter Unsc...

Страница 22: ...d is determined by the pressure set on the control valve P1 and by the size of the oil nozzle in the nozzle line The control valve P1 operates as follows When the oil attains opening pressure the port...

Страница 23: ...bles comprise theoretically calculated values where pipe dimensions and oil low are adapted to prevent turbulent lows from occurring Turbulent lows can result in pressure losses and noise in the pipew...

Страница 24: ...emperature the preheater thermostat closes sending the start signal to the burner During operation the output of the PTC element is adjusted automatically so that the temperature does not rise too hig...

Страница 25: ...25 Bentone B 2 General Alt 1 According to DIN 4791 Alt 2 Alt 3 Alt 4 7 ELECTRIC EQUIPMENT LMO1 2 4 7 1 Wiring diagram...

Страница 26: ...and the pre heating period begins This continues until the operating temperature is reached and the preheater thermostat closes The burner motor starts ignition sparks initiated and pre ventilation co...

Страница 27: ...after release 1 s 1 s 1 s Reaction time lame extinction 1 s 1 s 1 s Ambient temperature 5 60 C 5 60 C 20 60 C Min current with lame 45 A 45 A 45 A Max current when dark start 5 5 A 5 5 A 5 5 A Ingress...

Страница 28: ...blem by pressing and holding the reset button for 3 seconds The number of lashes below is repeated with a pause in between 2 lashes No lame signal when safety time expires 4 lashes False light during...

Страница 29: ...tive oil burner control or lame monitor No oil supply Too great a pressure drop at brake plate Too strong draught prevents lame forming No spark Check and replace fuse as necessary Investigate cause o...

Страница 30: ...s ci dessus sont conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direk...

Страница 31: ...start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If the burner starts b...

Страница 32: ...32 Bentone B 2 General...

Страница 33: ...33 Bentone B 2 General...

Страница 34: ...34 Bentone B 2 General...

Страница 35: ......

Страница 36: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...