A minimum S.G. of the electrolyte of 1.13 kg/l is to be checked at the end of the 
discharge. Discharged batteries must be recharged immediately and must not be 
left in a discharged condition:

This  also  applies  to  partially  discharged  batteries.  Discharged  batteries  can 
freeze.

TM

PerfectRail  DS batteries can be recharged with 50 Hz or HF charger. If you wish 
to  use  an  existing  charger  with  Wa,  WoWa,  IUIa,  WUIa…profile,  you  should 
check  that  the  profile  is  approved  by  our  Technical  Department.  Only  direct 
current  must  be  used  for  charging.  Only  connect  the  battery  to  the  correctly 
assigned charger, suitable for the battery size in order to avoid overloading of the 
electric cables and contacts, electrolyte overflow and unacceptable gassing of 
the cells. When gassing the current limits must not be exceeded according to 

 

DIN EN 50272-3. Before starting the charge, make sure of:

ź

the presence of the plugs.

ź

In the case of water refilling system, check the good condition of the filling up 
circuit and specific plugs, the water tube connection for the filling device (fast 
connection between the battery and the system with water supply).

When  charging,  proper  provision  must  be  made  for  venting  of  the  charging 
gases. Battery container lids and the covers of battery compartments must be 
opened  or  removed.  Keep  vent  plugs  closed.  With  the  charger  switched  off, 
connect  the  battery  ensuring  that  the  polarity  is  correct  (positive  to  positive, 
negative to negative). Now switch on the charger. In the case of automatic filling 
up, with manual command, press the push –button of the electro valve box to 
release the supply of demineralized water, at the end of charge. When charging 
the temperature of the battery rises by about 10°C, so charging should only begin 
if the electrolyte temperature is below 45°C. The electrolyte temperature of the 
battery should be at least +10 °C before charging, otherwise a full charge will not 
be achieved without specific settings of the charger. The charge is considered as 
achieved when the electrolyte S.G. and the battery voltage remain constant for 2 
hours.  During  the  recharge,  the  cells  emit  hydrogen  and  oxygen  gas.  It  is 
necessary to ensure ventilation in the room, especially during the recharge. All 
installations must comply with the current regulations in force in the country of 
operation.

It is applied further to a «normal» discharge of the battery (up to 80% of C5). It is 
not interrupted until the end of charge indication by the charger display. It is not 
necessary to recharge the battery immediately if after a use cycle, the residual 
capacity is still more or equal to 60% of its capacity.
In that case it is necessary to recharge the day after at the latest.

Equalizing  charges  are  used  for  insuring  the  service  life  and  to  maintain  the 
capacity.  They  are  necessary  after  deep  discharges  and  after  repeated 
uncompleted charges. They allow homogenization of the specific gravity of the 
electrolyte:

ź

to compensate the self-discharge due to the storage period

ź

to compensate the eventual lack of charge with normal charges.

ź

to quickly homogenize the electrolyte, following the addition of distilled or 
demineralized water.

ź

to compensate stratification, following partial charges without mixing of the 
electrolyte (not recommended).

To be carried out after a normal charge when a variation (differences more than
10 grams per litre) of specific gravity is recorded. It is carried out using a constant 
current with a low value near C5 /30 (C5 /20 max) and after a normal charge of the 
battery (end of charge, see 2.2). The recommended duration is 8 hours. The 
equalizing charge may be interrupted if the specific gravities are homogenized. 
When the nominal electrolyte specific gravity is not obtained after an equalizing 
charge, and when this low specific gravity is not the consequence of electrolyte 
overflowing, a recharge in completion with the equalizing charge can be carried 
out. It must be done with constant current, near C5 /60 A, and after a complete 
charge for 72 hours. Watch the temperature and a sufficient ventilation!

Should be carried out after a very deep discharge of the battery (> 80% C5) when 
the charger does not start the recharge due to an over discharge of the battery. It 
must carried out with constant current, near C5 /60, for 2 hours minimum. It is 
followed by a normal charge and equalizing charge (desulphation if necessary). 
The best result is obtained with the lowest value of current. In any case, stop the 
charge if the electrolyte temperature reaches 45°C

The electrolyte nominal S.G. is 1.29 kg/l at 25°C when in fully charged condition. 
According to temperature, S.G. correction, in respect to 25°C, will be applied:

Example: SG reading 1.282 at 36°C:
1.282+ (0,0007 X 11) = 1.289 at 25°C
The purity of the electrolyte must correspond to DIN 43530-2.

After a normal charge, measure:

ź

the total voltage

ź

the voltage per cell

ź

the  electrolyte  specific  gravity  on  several  cells  or  on  the  whole  battery.

NB: measure at the constant intensity of I=0.033 C5 or if the charger can do it, at

 

“equalizing charge”. The voltages for a new battery will be greater than or equal to
2.65 Volts per cell under I=0,033 C5.

ź

keep the battery, clean and dry in order to avoid self-discharging and current 
leakage.

ź

check: the condition of the plugs, cables and that all insulation  covers are in
place and in good condition.

If necessary, adjust the electrolyte level of each cell, only use demineralized or 
distilled water. The level must never be lower than the minimum level, in other 
words, always above the plates. It is carried out:

ź

at the end of charge and without over exceeding the maximum level if the
battery has standard filling plugs.

VERY IMPORTANT
In difficult conditions, high room temperature for example, the electrolyte level 
must be checked as often as necessary.
If there are traces of electrolyte-overflowing, in general, lead sulphate trails, wash 
the battery with clean water at low pressure, with the cells vent plugs in place and 
closed.

Carry out an end-of-charge control: measure and record the voltages of all blocs 
with the charger switched on. Measure and record the electrolyte S.G. of all blocs. 
If significant variations to the earlier measurements or big variations between the 
blocs or cells are noticed, please contact our Service. If the battery autonomy is 
not sufficient, check that the work required is compatible with the battery capacity, 
the battery condition (end of charge SG), and the settings of the charger.

Battery:  for  bolt  on  connectors,  check  the  torque  settings  of  the  terminal 
bolts/screws, the terminals must be covered with grease as protection against 
external corrosion. Charger: internal dust removal, check all connections (plugs, 
cables and contacts) and charging parameters.
At least once a year, the insulation resistance of the locos and of the battery must 
be checked by an electrical specialist.

The  test  on  the  insulation  resistance  of  the  battery  must  be  conducted  in 
accordance with DIN EN 1987-1. The average insulation resistance of the battery 
must not be lower than 50 Ω per Volt nominal voltage (DIN EN 50272-3)
For batteries up to 20 V nominal voltage the minimum value is 1000 Ω.

Batteries must always be stored and transported securely in the vertical position 
in  order  to  avoid  any  electrolyte  leakage.  Store  the  battery  in  a  fully  charged 
condition in a dry, clean and frost free area. Always disconnect the battery from 
the electric vehicle before storage. For easy recharge of the batteries, it is advised 
not to store without recharge for more than 3 months at 20°C and 2 months at
30°C.
The storage time is to be considered within the battery life expectancy.
To ensure the battery is always ready for use a choice of charging methods can be 
made:

ź

monthly equalizing charge according to 2.2.2

ź

float charge with 2.27 V x number of cells.

Back to the manufacturer!
Batteries with this sign must be recycled. 
Batteries which are not returned for the recycling process must be disposed of as hazardous waste!

2.4. Battery Check

3. Maintenance
3.1. Daily maintenance:

3.2. Weekly maintenance:

3.3. Monthly or quarterly maintenance:

3.4. Annual  maintenance:

4. Storage and Transportation

2.2. Charge

2.2.1 Normal charge:

2.2.2. Equalizing charge:

2.2.3. Desulphation charge:

2.3. Electrolyte

Discharge

Recharge

>40%

Every day

<40% 

Every second day

T °C

Correction per °C

If T °C > 25°C

- 0,0007 

If T °C < 25°C

 

+ 0,0007

Perfect

DS

Manual_

  Subject to revisions without prior notice.

Rail

_

01_EN_201

5

-

06

-V1