background image

o

J4 

is the 

R

SI

 S

AFE

 S

TATUS

 I

NPUT

.  These are dry contacts which can receive external commands.

An external switch or relay can send a “Safe” signal to 

J4 

from another location.



Open (all connections):  Not “Safe”



Closed (any connection):  “Safe” (Rapid Shutdown)

o

J5 

is the 

A

UX

 A

FCI

 S

TATUS

 O

UTPUT

.  These are dry contacts which report AFCI status.  The 

J5

contacts can activate a local alarm or send status messages to the Web or other OutBack devices.



Open:  Normal



Closed:  Arc fault event



30 Vdc or 15 Vac @ <2 A

o

J6 

is the 

A

UX

 R

SI

 E

XTERNAL

 I

NPUT

.  These are dry contacts in series with the 

R

APID

 S

HUTDOWN

switch.  These (normally-closed) connections control a 24-Vdc rapid shutdown circuit.  Opening any
contacts constitutes a rapid shutdown command.  An external switch or relay can serve as another
rapid shutdown device if connected to the 

J6 

contacts from another location.



Closed:  

J6 

 

R

APID

 S

HUTDOWN

 switch; normal operation (

S

OLAR

 O

N

)



Open:  

J6 

device or 

R

APID

 S

HUTDOWN

 switch; rapid shutdown state (

S

OLAR

 O

N

)

RSI

Application with FireRaptor MLPE

900-00268-01-001 REV A

 

©2020 OutBack Power.  All Rights Reserved.

RSI Connections

The RSI is equipped with terminal connections for power, input 
signals, and output signals.

Power Terminals

o

J1

 provides power to the RSI itself.  To power the RSI, an isolated

Class 2 DC power supply (24 Vdc ± 3%, up to 1.5 Adc) must be
used.  Power supply negative (–) connects to pin 3 (black).  Power
supply positive (+) connects to pin 4 (red).  This wire must be
protected by an appropriately-sized overcurrent protection device.

o

J2 

provides power to all PV combiners.  In the illustration below,

pins 3 and 4 (black and red) connect to a junction box which leads
to the 

P

WR

 

port on the FireRaptor combiners.

Accessory Terminals

o

J3 

is the 

A

UX

 R

SI

 C

OMMAND

/S

TATUS

 O

UTPU

t.  These are dry contacts

which report RSI status.  The 

J3 

contacts can activate a local alarm

or send status messages to the Web or other OutBack devices.



Open:  Rapid Shutdown (

S

OLAR

 O

FF

)



Closed:  Normal (

S

OLAR

 O

N

)



30 Vdc or 15 Vac @ <2 A

J2 

1

    

2

    

3

    

4

J1 

1

    

2

    

3

    

4

J3

J4

J5

J6

System Wiring

o

Install the PV modules in series strings using the FireRaptor MLPE devices (OBFRS-01).

 Connect these strings to the combiner.



The 

S

TR

 

(string) terminals are used for series string connections.  The 

P

AN

 

(panel) terminals are used for PV module connections.  The 

P

WR

 I

N

 

and 

O

UT

 

terminals

receive and distribute power from the 

J2 

power supply in the RSI (which is powered by the class 2 power supply).  It can power up to 114

 

OBFRS-01 devices per RSI.



One string is depicted. The FWPV4-FH600 combiner can receive up to 4 strings.

o

Connect the combiner output to the charge controller.  To use the integrated FM100 arc fault protection, 

this must utilize approved PV circuit breakers such as

those on the GSLC.

o

Connect the RSI J3 terminals to the charge controller’s rapid shutdown terminals.  The “daisy chained” terminals may be connected to other charge controllers
or to the inverter’s on/off circuit.

o

Connect the Class 2 power supply to the RSI J1 terminals.

PV and OBFRS-01 (first in string)

PV and OBFRS-01 (last in string)

FWPV4-FH600 Combiner

FM100-AFCI 

Charge Controller

RSI (internal)

Junction Box

PV String 2
PV String 3
PV String 4

To daisy-chained 

charge controllers or 

inverter on/off circuit 

(optional)

GS Load Center (GSLC)

OBFRS-SIGCAB1.8F Extension Cable

5

6

9

1

0

STR

+

STR

PA

N  

+

PA

N  

PW

R

 IN

PW

R

 OU

T

STR

+

STR

PA

N  

+

PA

N  

PW

R

 IN

PW

R

 

OUT

STR

+

STR

PA

N  

+

PA

N  

PW

R

 IN

PW

R

 OU

T

Class 2 

Power Supply

IMPORTANT:  J4 

If safe status input devices are not installed, a jumper must be installed on 

J4

.  With no connections, 

the 

S

OLAR

 O

FF

 (“safe”) indicator will not light even if the 

R

APID

 S

HUTDOWN

 switch is 

O

FF

IMPORTANT:  J5 

The AFCI status signal that triggers the 

J5

 output is not functional unless this product is used 

with the ICS Plus PV combiner.

IMPORTANT:  J6 

The factory-installed 

J6

 jumper must remain in place if an external switch is not connected.  

Leaving these contacts open will cause a continuous shutdown. 