4.10 AC Wiring, Permanent Connection
1.
Run the AC wiring through the 1/2" EMT along the same path as the original AC line cord.
2.
Connect the AC wiring as follows:
•
Black wire = Line
•
White wire = Neutral
3.
Connect the ground wire (min. #14 AWG) to the safety ground stud on the chassis, and then to the AC input
block. The stud uses a 7mm nut.
4.
Secure the EMT connector.
CAUTION!
Do not apply power at this time. Connection to the building utility may only be performed by a
licensed electrician in accordance with the NEC and all applicable local codes and regulations.
Figure 8–AC mains connection
#10 ONT ground reference stud (2 PL)
Accepts #10 solid ground wire
NOTE:
The #10 ground studs are used only
when there is no other way to ground
the ONT to earth
Connect to safety ground stud
and then to the AC input block
(green)
Line (black)
Neutral (white)
To AC mains