7.6.11 Configuring and Monitoring the DC Emergency Generator
Set the parameter atiMgmtSysIoSelect 1.3.6.1.4.1.926.1.3.2.8.1.0 to a value of “4” (Generator). Alternatively, navigate to
‘Advanced Configuration’, ‘I/O – Environment’ and select “Generator Only” from the pull-down list.
The status of the Generator can be monitored through I/O – Environment web page or via the SNMP MIB
atiMgmtSysIoGenState 1.3.6.1.4.1.926.1.3.2.8.3.0.
Table 7-8, Generator Monitoring Values
I/O Port: Heater Mat Control Specifications
Value List
Description
atiMgmtSysIoGenState (1.3.6.1.4.1.926.1.3.2.8.3.0)
notInstalled(1)
This indicates that atiMgmtSysIoSelect has not been set to a value of 4 (Generator).
genOff(2)
The generator has been detected but it is not powering the load.
genRunning(3)
The generator is present, and it is powering the load.
genNotDetected(4) atiMgmtSysIoSelect has not been set to “4” (Generator) but the Generator is not detected.
atiMgmtSysIoGenTimePowering (1.3.6.1.4.1.926.1.3.2.8.3.0)
Time (Minutes)
Increments when atiMgmtSysIoGenState = 3; resets to “0” when atiMgmtSysIoGenState changes
to any other value
Both of the above parameters can be alarmed through the SCTE-HMS propertyIdent MIB