7.0 Installation, continued
75
704-939-B10-001 Rev. A5 (06/2019)
7.6.7 I/O Port: Heater Mat Control
atiMgmtSysIoSelect = 3,5
A battery heater mat controller may be managed though the following set of parameters within the ‘atiMgmtSysTempMgr’
MIB branch.
Table 7-5, I/O Port: Heater Mat Control Specifications
I/O Port: Heater Mat Control Specifications
Parameter
Access Values
Description
atiMgmtSysTempCtrl
1.3.6.1.4.1.926.1.3.2.4.1.0
RW
1 = Off
2 = Switch on Timer
Starts or stops the heater mat activation timer
atiMgmtSysTempStatus
1.3.6.1.4.1.926.1.3.2.4.2.0
R
1 = Contact Open
2 = Contact Closed
The heater mat is activated when this parameter
reports “2”
atiMgmtSysTempTimer
1.3.6.1.4.1.926.1.3.2.4.7.0
RW
0..1440 (Default = 30)
The number of minutes the heater mat will stay
on when timer is started
atiMgmtSysTempCountdown
1.3.6.1.4.1.926.1.3.2.4.8.0
R
0..1440
Number of minutes remaining on timer
atiMgmtSysTempStatusInvert
1.3.6.1.4.1.926.1.3.2.4.9.0
RW
1 = No invert (default)
2 = Invert
The manufacturer of the mat control block
created some models where the polarity is
reversed (Open vs closed). If these devices are
deployed then this parameter will need to be set
to “2”
The Heater Control MIBs will continue to report regardless of atiMgmtSysIoSelect value, but the Web page will only
display Heater Control status if atiMgmtSysIoSelect is set to “3” or “5.”