4.4 List of the Parameters

The parameters for the process signal measurement unit can be roughly divided into three types: condition data which deal with basic functions
including sampling time; scaling data which control measurement including input range; comparator data which deal with comparator output; and
calibration data which relating to calibration with a sensor.

4.4.1 Condition Data

4.4.2 Scaling Data

4.4.3 Comparator Data

4.4.4 Calibration Data

5

Setting Examples and Use Examples

5.1 Scaling Data Setting Examples

Set digital liniter,analog output and decimal point by 4.4.2 scaling data.
Set it in below        of operation procedure diagram.
The digital limiter is the function that limits an input value to the relevant
set value even if a signal higher than or lower than the indicated value
set to DLHI or DLLO respectively is input. The setting condition is DLHI
> DLLO, and if this condition is not met, Err5 is caused, returning the
display to DLHI.

5.2 Analog output Scaling Setting Examples

The analog output sets the output value to the display value.

5.3 Comparator Data Setting Examples

High and Low Judgment Type

The high and low judgment type allows you to directly set judgment
values in numerical values, which are checked against the indicated
value for judgment. It allows setting of two stages of judgment points: HI
and LO.
* The setting conditions are (HI judgment value - HI hysteresis) > (LO
judgment value + LO hysteresis). If any of these conditions is not met,
Err0 is caused, returning the display to the HI judgment value setting.

Jog SW

0

P.L.

PH Selection

0

Average times

Average times of 

movements

Step wide

Display color type

HI display color

GO display color

LO display color

Display blank level

DZ backup

Linearize

TZ time

TZ correction range

Power on delay time

Protection level

Unit number indication

DZ control

0

0

0

1

1

1

1

0

0

0

0

0

0

3

0

0

P.SEL

0

Start/hold type

0

PH type

0

S/H delay time

0

Setting range or alternatives

Parameter name

Menu indication

Conversion rate (average times of internal sampling ; sampling time: approx. 1ms) is selected.

Major setting purpose and remarks

Selects the average times of movements .Filtering effects: Small<1(OFF)-2-4-8-16-32>Big

Selects the range of display changes to maintain image display consistency .

 (If this parameter is set to 5, the lowest digit will display either 0 or 5 only).
Selects automatic (red in the HI or LO mode or green in the GO mode ) or manual setting for display color type .

Selects red or green as display color at the time of HI judgment .*Only when CLR.T is MANU.

Selects red or green as display color at the time of GO judgment .*Only when CLR.T is MANU.

Selects red or green as display color at the time of LO judgment .*Only when CLR.T is MANU.

Selects the display brightness . <bright OFF-LV1-LV2-LV3-ON >turned off

Selects whether the jog SW is used or not .

Selects a type that operates when the PH function is turned on  (peak hold/valley hold/peak-valley hold).

Selects whether the digital zero value is backed up or not at the time when the unit is turned off .

Selects the number of patterns available for the pattern selection function .

Selects whether the linearize function is enabled /disabled and sets the number of correction points .

Selects whether the tracking zero function is enabled/disabled and sets the correction time (setup value/conversion rate).

Sets the time between the startup and actual start of measurements  (setup value x 1 second).

Sets the correction range of the tracking zero function .*Only when TR.T is set to a value other than  000.

Selects the protection level to prevent operation mistakes .High< LV3-LV2-LV1-LV0 >Low

Selects whether the code of a unit mounted at the time of startup is displayed or not .

Selects an operation type of start /hold (A: free run; B: one shot).

Sets the delay time at the time of startup  (setup value x 1 ms).

Selects an operation type of peak hold  (A: real-time display; B: results display).

Selects a control method of Digital Zero (SW: front key; TERM: external control terminal).

Initial value

(AVG)

(MAV)

(S.WD)

(CLR.T)

(HI.CL)

(GO.CL)

(LO.CL)

(BLNK)

(DZ.BU)

(LINE)

(TR.T)

(P.ON)

(PRO)

(U-NO.)

(S/H.T)

(PVH)

(PS)

(TR.W)

(S/H.D)

(PVH.T)

(DZ.C)

(J.SW)

Sets the upper limit of the displayable range .

(Any value equal to or exceeding the digital limiter HI setting will not be updated and kept at the setup value .

Selects an analog output range . 

Sets the relationship between indications and analog outputs . 

Sets the position of the decimal point .

Sets the lower limit of the displayable range .

(Any value equal to or below the digital limiter LO setting will not be updated and kept at the setup value .   

1

1

2

1

0

0

Analog output HI

Analog output LO

Decimal point

Analog output type

Digital limiter LO

Digital limiter HI

P.L. Setting range or alternatives

Parameter name

Menu indication

Major setting purpose and remarks

Initial value

(DLHI)

(DLLO)

(AOHI)

(AOLO)

(DP)

(A.OUT)

Each digit can be set 
independently

(SPIN) S pa n input value

2

(ZERO) Zero indication

2

(SNSR) S ensor pow er supply

1

(ZRIN) Zero input va lue

2

(SPAN) S pa n indication

2

Selects a sensor pow er supply .

Sets the rela tionship betw een input sig nals a nd their indica tions .

P.L. Setting range or alternatives

Parameter name

Menu indication

Major setting purpose and remarks

Initial value

0

5000

4mA

20mA

10V

2000

0

-2000

When the indication varies between 0 to 5000,
corresponding analog output values should be 4 to 20mA.

Analog output

Indication value

Example 1

Analog output HI (AOHI)

Analog output LO (AOLO)

:

:

5000

0

Example 2

When the indication varies between 200.0 to -200.0, 
corresponding analog output values should be 0 to 10V.

Analog output

Indication value

Analog output HI (AOHI)

Analog output LO (AOLO)

:

:

-2000

2000

Example 1

Above and below setup mode

GO

GO

HI

GO

LO

Indication values

Judgment

700

500

0

1000

400

900

200

LO judgment value

HI judgment value

Hysteresis range

* The hysteresis is effective either in the range lower than the HI judgment value or that higher than the LO 

judgment value.

Tolerance 

Judgment Type

The tolerance judgment type allows you to set a nominal value and its
tolerances (XX%) to make judgment on the basis of the judgment
values calculated from these values within the instrument. You can
set one nominal value and one tolerance values.
For example, if the nominal value is set to 1000 and tolerances 10%
respectively, internal judgment values are 1100 for HI judgment value,
900 for LO judgment value.

5.4 How to Switch the Sensor power

5V DC or 10V DC can select by 4.4.4 Calibration data. Initial value
become 5V DC.

5.5 Shift Data Setting Examples

The shift function allows you to arbitrarily shift the display without
changing the inclination of an input signal. A setting example below
shows how to shift the indicated value by 100 digits.

Example 2

Error judgment mode

GO

GO

HI

GO

LO

Indication values

Judgment

1000

900

0

1100

Nominal value

Hysteresis range

Upper side error

Lower side error

* Error is to be set as a percentage of the nominal value.
* The hysteresis is to be set as an x-th digit of the indication value.
* The hysteresis is effective either in the range lower than the upper side error or that higher than the 

lower side error.

1

1 Press multiple times

1

Mode

It is memorized.

Operation Method

Measurement operation

It is not displayed, except when the 

protecting level of the condition data is PL0.

Shift data setting

2

2

2

or

or

2

2

2

The digit is moved, and the digit 
that wants to change is selected.

Increase a value.

Decrease a value.

Enter

Return to measurement

HI judgment value

LO judgment value

HI logic

LO logic

HI hysteresis

LO hysteresis

Error 1

Nominal value

2

2

2

2

1

1

0

0

Comparator output type

1

Error 1 hysteresis

1

GO logic

0

Select either [above or below] or error comparator types.

Sets a HI judgment value. *Only when COM.T is O/U.

Sets a LO judgment value . *Only when COM.T is O/U.

Sets a nominal value. *Only when COM.T is ERR.

Sets an error. *Only when COM.T is ERR.

Sets a HI hysteresis value (smaller than the setup value.) *Only when COM.T is O/U.

Sets a LO hysteresis value  (larger than the setup value .) *Only when COM.T is O/U.

Sets an error hysteresis (smaller or larger than the setup values .) *Only when COM.T is ERR.
Sets a HI output logic (N.O.=normally open or N.C.=normally closed)

*Output when the power is OFF is always open .
Sets a GO output logic (N.O.=normally open or N.C.=normally closed)

*Output when the power is OFF is always open .
Sets a LO output logic (N.O.=normally open or N.C.=normally closed)

*Output when the power is OFF is always open .

P.L. Setting range or alternatives

Parameter name

Menu indication

Major setting purpose and remarks

Initial value

(LO-L)

(GO-L)

(HI-L)

(ER1.H)

(LO-H)

(HI-H)

(ERR1)

(N.VAL)

(LO-S)

(HI-S)

(COM.T)