January, 2005 – Operators Manual 
ENERNET Corporation 

INSTALLING AND REMOVING NODES 

The Linking Procedure 

Installing a thermostat and RCN so that they will communicate with 
each other, “links” them together as an operational system.  When an 
RCN is linked to a thermostat, it will thereafter only respond to that 
specific thermostat.  In some cases a thermostat and RCN will be 
pre-linked in pairs by the factory.  If this is not the case or you are 
replacing a thermostat or RCN, or adding another RCN to an existing 
system, the following procedure is used: 

 

Installing Nodes 

Refer to Figure 7 for button location.  Press the 

SW4

 button.  The 

Install

 

Icon will flash - Press the 

UP 

button to toggle through the 

following two Icon choices: 

Install

  

……… Icon lighted  =    Install an RCN 

Remove 

……...

 

Icon lighted  =    Remove ALL RCNs 

Press 

HEAT/COOL

 to select.  The node number digit will flash.  

Use the 

UP

 button to set the node number you wish to install 0-7.  

Press the 

HEAT/COOL

 button to select the node number.  The

 

HEAT 

and/or 

COOL 

icon will now flash in the upper right hand 

corner of the display.  Press the 

UP 

button to toggle through the 

following three Icon choices: 

HEAT

  ……… Icon lighted  =   Install an RCN as heating only 

COOL

  ……… Icon lighted  =   Install an RCN as cooling only 

HEAT

  ……… Icon lighted 

COOL 

=   Install an RCN as heating & cooling 

Press the 

HEAT/COOL 

button when you have the icon you want.  

At this point all selections have been made and nothing on the 
display should be  blinking.  You are now ready to install a node.  
Press the SW9, 

LINK

 button on the back of the thermostat printed 

circuit board and within 5-seconds  activate a service request on the 
RCN you are installing by the following method: 

Plug Node RCN: 

Apply power by plugging it in. 

J-Box RCN:

 

Apply power or press Service Pin Button PB1.* 

PTAC RCN: 

Apply power or press Service Pin Button PB1. 

After a  delay of a  few seconds, a response of “good," or “bad” is 
displayed.  If bad, repeat the procedure.  Press the 

SW4

 button to 

return to normal operation. 

NOTE: 

The J-Box RCN is a line-voltage device.  Only a qualified technician 
should open the enclosure to access PB1.  All others should use the 
power up method only. 

 

Removing Nodes 

All Nodes Removal 

Unlike installing a node(s), the procedure to remove a node removes 
all nodes installed to the thermostat at once.  You cannot remove a 
single node. 
 
Press the thermostat 

SW4

  MODE  button.  The 

Install

 

Icon will 

flash.  Press the 

UP 

button to toggle between 

Install

 and

 

Remove

.  

Stop at 

Remove

 

and press 

HEAT/COOL

 to select. The node number 

will not blink because all RCN nodes are being removed.  Press PB1 
on the back of the thermostat board. 

Содержание T9000

Страница 1: ...ENERNET Corporation Copyright 2005 Model T9000 Wireless Thermostat Installation and User Guide ...

Страница 2: ...N 4 Figure 5 Three Button Cluster 4 SETTING THE CLOCK 4 PROGRAMMING YOUR THERMOSTAT 5 RUN BUTTON 6 CHANGING TEMPERTATURE WHILE RUNNING A PROGRAM 6 IMPORTANT NOTE 6 INSTALLING AND REMOVING NODES 7 The Linking Procedure 7 Installing Nodes 7 Removing Nodes 7 All Nodes Removal 7 Setting Min Max Set Point 8 Figure 7 Internal Button 8 TROUBLESHOOTING FAQ 9 Figure 1 PTAC RCN Connection Diagram 12 Figure ...

Страница 3: ...ATER EDITIONS ENERNET CORPORATION MAY MAKE CHANGES AND IMPROVEMENTS TO THE PRODUCT S AND OR PROGRAMS DESCRIBED IN THIS PUBLICATION AT ANY TIME WITHOUT NOTICE IN NO EVENT WILL ENERNET CORPORATION BE LIABLE FOR DAMAGES INCLUDING LOST PROFITS LOST SAVINGS OR OTHER INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF OR INABILITY TO USE SUCH PRODUCT EVEN IF ENERNET CORPORATION OR AN APPROVED ...

Страница 4: ...n are typically not provided The second part of The T9000 system is called a Remote Control Node or RCN An RCN interfaces with the desired HVAC equipment and communicates with its thermostat using unlicensed 900MHz radio frequency energy At the time of installation the T9000 thermostat can be linked to more than one RCN A thermostat and RCN that have been linked will not interfere with or be affec...

Страница 5: ... the thermostat display when the thermostat batteries are within a week or two of being exhausted The T9000 is designed to accept either alkaline or 1 5 volt lithium batteries such as the Energizer PHOTO L91 Lithium AA Standard alkaline batteries such as Duracell AA will perform well The Energizer L91 lithium battery cost more but will run the thermostat somewhat longer The T9000 operates with eit...

Страница 6: ...i e replacing Lithium with Alkaline or Alkaline with Lithium Remove old batteries and wait for the front display to go blank Install new batteries reset the time and programs FOUR BUTTON HOTEL CONFIGURATION The T9000 can be ordered in a four or seven button configuration Typically in hotel applications users do not need access to programming or clock functions Buttons for those functions are there...

Страница 7: ...ill use the buttons marked CLOCK UP DOWN and HEAT COOL STEP ONE Press the CLOCK Button The hour digits will flash Press the UP or DOWN button to change to the proper hour Note that AM PM will change as you roll the hour past 12 Be sure to set the hour properly for AM or PM Press the HEAT COOL button to keep the hour you ve just set and to move to minutes STEP TWO The Minute digits will now be blin...

Страница 8: ...E Press the PROGRAM button to put the thermostat into the programming mode The display will blink all of the day of the week icons Pressing the UP or DOWN button will toggle between weekday icons and the weekend icons Ensure the display is blinking the one you want to program Press HEAT COOL STEP TWO The Morning period will be blinking Use the UP or DOWN button to toggle through Morning Day Evenin...

Страница 9: ...at is currently in When in the manual mode there will be no time period icon displayed In manual you can adjust to the desired temperature using the UP and DOWN buttons and the thermostat will maintain the temperature you set until you manually change it again CHANGING TEMPERTATURE WHILE RUNNING A PROGRAM Even when your thermostat is running in its program mode you can change the temperature to wh...

Страница 10: ...n lighted Install an RCN as cooling only HEAT Icon lighted COOL Install an RCN as heating cooling Press the HEAT COOL button when you have the icon you want At this point all selections have been made and nothing on the display should be blinking You are now ready to install a node Press the SW9 LINK button on the back of the thermostat printed circuit board and within 5 seconds activate a service...

Страница 11: ... button configuration models these buttons are on the front of your thermostat see Figure 5 Simultaneously press the PROGRAM and RUN buttons the thermostat will display the HEAT icon and set point temperature Use the UP or DOWN buttons to set the maximum heating set point you wish to allow Next press the HEAT COOL button to set the Max heating temperature and bring up the COOL icon With the COOL i...

Страница 12: ... The thermostat will also automatically try to communicate within a maximum of ten minutes from the last attempt If communication is successful the antenna icon will turn back on Coincidental RF interference could be cause for a temporary loss of communication In virtually all such cases the interference is temporary The thermostat will attempt to re establish communication with its RCN s within a...

Страница 13: ...ntrolled to within a degree or two of your desired set point Studies have shown you can save up to 12 just through precision temperature control You can maximize savings if you also program your thermostat to automatically turn the temperature up or down while you are away or asleep See the PROGRAMMING section of this guide for exact details The display on my thermostat is blank What happened A bl...

Страница 14: ...ation mode has no effect PB1 is only used when removing nodes that have previously been linked to the thermostat NOTE Refer to the INSTALLING AND REMOVING NODES section of this manual for detailed instructions If you need assistance installing or removing an RCN contact your distributor or call ENERNET Corporation for technical support I see solar cells on the T9000 does it need light to operate W...

Страница 15: ...January 2005 Operators Manual ENERNET Corporation 12 Figure 1 PTAC RCN Connection Diagram ...

Страница 16: ...January 2005 Operators Manual ENERNET Corporation 13 Figure 2 J Box RCN Electric Heat Example ...

Страница 17: ...January 2005 Operators Manual ENERNET Corporation 14 Figure 3 J Box RCN Fan Coil Example ...

Страница 18: ...January 2005 Operators Manual ENERNET Corporation 15 Figure 4 Plug RCN Fan Coil Example ...

Отзывы: