INSTALLATION INSTRUCTIONS

DESCRIPTION

 

WIRING DIRECTIONS

 

3

WARNING

Turn the POWER OFF at the circuit breaker 

before installing the sensor

Read and understand these instructions before installing.  This device is 

intended for installation in accordance with the National Electric Code and 

local regulations.  It is recommended that a qualified electrician performs this 

installation.  Make sure to turn off the circuit breaker or fuse(s) and make sure 

power is off before wiring the device.

Use copper wire only.

The M

P

W

-

L

 provides a 

150

° coverage pattern. The coverage shown represents 

walking motion at 

mounting height of 

10

 feet. For building spaces with lower 

levels of activity or with obstacles and barriers, coverage size may decrease.

The  MPW-L passive infrared (PIR) occupancy sensors turn lighting on and off 

based on occupancy and ambient light levels. The light  level feature keeps lights 

from turning on if the ambient light level is sufficient. The sensors can be 

configured to turn lighting on, and hold it on as long  as PIR technology detects 

occupancy. After no movement is detected for the selected time delay, the lights 

switch off. 

The M

P

W

-L operates on 24V supplied by the MPP-24 Power Packs (Not 

Included)

C0VERAGE

M

P

W

-

L

150

° 

Passive Infrared

 • Low Voltage 

Occupancy Sensor

SPECIFICATIONS

 

Adjust

able

 Time Delay.......................

.

.......................

.

.............. 

30

 Sec.  to 30 Min.

Operating Temperature .............................

.

......................32°to 131°F (0°to 55°C)

PIR Adjustment..................................

.

.......................

........

..............

..

25% to 100%

Adjustable 

Light Level ..................................

........

.................

..

....

100 Lux -daylight

Voltage ..................................................................

........................

............ 

24VDC

        

Current Consumption

.............................................

..................

.....................

4

0mA

Power Supply

......................................

..........

.

MPP-24 Power Pack (Not Included)

PIR

 Coverage........................

.

...........................................................

.........

..

.

9

00ft

 

2

Black

Red

Blue

Control Out

+24V

Common

5. Restore power at circuit breaker or fuse, wait

6.

Remove the small cover plate.

7.

Locate the adjustment knob on the control panel to perform test
and adjustment.(illustrated as Figure

 

3

. )

8.

Replace the small cover plate after testing and adjustment.

 one

 minute.

b. attach sensor switch to the mounting yoke with wires

3. Mount device up to walls or ceilings.
4. Gently position wires in wall/octagon box,

a. attach sensor switch to the box, and fix it to the wall/ceiling .

with two screws.

through its certral hole, and fix the yoke to the wall/ceiling.

1. Make sure that the power has been turned OFF at the circuit breaker.

2. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to

Common, Red lead to +24V, Blue lead to Control Out.

Wiring Diagram:

Figure 2

SETTINGS ADJUSTMENT

1

Figure 1

PIR coverage 50ft

Figure 

3

Mounting Yoke

Detection LEDs

Red=PIR

PIR Lens

Control Panel Cover

TIME

LIGHT

RANGE

Ambient Light Level Adjustment Trimpot

Default position: Daylight (100% at position 4)

Adjustable: Clock wise 

TIME Adjustment Trimpot

Default position: Time (Test at position 1)

Adjustable: 5 sec. to 30 mins (clockwise) 

PIR Adjustment Knob

Default position: Center

Note: Turn toward right for greater room space.

      Turn toward left to avoid false alert in smaller room and near 

 the door way or heat source.  