4. The chase nipple provided can be pushed into a standard  1/2”  

The MPC-50H can be attached to the fixture or junction box using the
back box and chase nipple or directly to the fixture surface via the two

screw holes provided in the sensor (See Figure 3 below).

Figure 3

Back box mounting 

This requires a standard 1/2” knockout for the chase nipple.The Sensor

mounts to the back box with a bayonet type fitting requiring a slight 

twist of the units to separate them or lock them into place.The box 

comes ready for side mounting(See Figure 4). It can be modified

for rear mounting as follows:

1. Pop out the cap in the rear 1/2'' knockout.
2. Un-snap the chase nipples from the side mount and snap into the

rear mounting hole.

3. Use the cap to close the side mount hole. 

knockout in a metal fixture [max of 1 mm (0.04”) thick metal] 
without the need for the included internal nut. The nut can be 
used for added security if necessary.

 

  Note: There is a 60-second warm-up period when power is

first applied, LED flashes

If the sensor detects occupancy during the warm-up, the time delay 
will increase.

If no occupancy is detected during the warm-up,the light turns OFF
after the initial 60-second warm-up period.

The sensors are factory preset to allow for quick installation in most 

applications.After test is finished,adjust the potentiometer according 

PIR Sensor

Surface

Mounting
Screw Hole

DIP Switches

Detection
Indicator LED

CDS

Light Level

Adjustment Trimpot

Surface

Mounting

Screw Hole

Check sensor mounting place, verify the sensor can detect motion

Warning:Turn off the power at the circuit breaker before 

WARRANTY INFORMATION  

 installing.

LED does not blink:

from human body. If not , the LED will not blinks.

LED blinks but lights do not turn ON: 

1.Make sure the wire connections are correct. Red load wire lead to

load light, and check the connection security.

2.Make sure that power to the sensor has been ON continuously for

at least one minute. Wait for the warm-up period to end,and if LED

flashes,the load has not turn on,then go to next step.

3.Cover the light sensor lens to simulate darkness.If the light turns

ON,the light level setting needs to be adjusted.If set for minimum,

more than 2fc of ambient light causes the lights to be held OFF. 

4.Check security of the light fixture.

Lights will not turn OFF:

1.If there is no motion from people or equipment in the sensor’s view

but the LED blinks, look for any nearby source of infrared energy

(heat) in motion,such as turbulent air from a heating or cooling 

Mount the sensor so that it’s lens is below the edge of the fixture

and does not directly view the lamps.

Move the air supply away from the sensor,or move the sensor.

2.Verify time delay set in switches 2-4.The time delay can be set 

 from 15 seconds to 30 minutes. Ensure that the time delay is 

 set to the desired delay and that there is no movement within 

the sensor’s view for that time period.

3.Check sensor wire connections,verify load and neutral wires

are secure.

Sensitivity setting: DIP switch 1

1.  50%,sensor’s coverage is smaller, just about half of the widest range.
2. 100%,the maximum range of MPC-50H-L1 coverage is 2800 square

feet,while for MPC-50H-L2 coverage is 1200 square feet. 

Time delay: DIP switch 2,3,4 

The sensor will hold on the lights on as long as occupancy is detected. 
The time delay countdown starts when no motion is detected.After no

motion is detected for the length of the time delay, the sensor will turn 

the lights off.

The MPC-50H has 4 DIP switches under the cover.They are used to

set sensitivity and time delay feature settings.

Time Delay

2

Test/15 Seconds

5 Minutes

10 Minutes

15  Minutes

20  Minutes
25  Minutes
30  Minutes

3

4

Sensitivity

100%

50%

1

DIP SWITCH SETTING

=OFF   =ON      Factory setting

 -04-                                                                                              -05-                                                                                            -06- 

to the ambient request specification,such as sensitivity and time delay.

Back Box

Alignment

Guides

OR

MPC-50H

Lens

Figure 4

supply.

Our company warranties this product to be free of defects in materials

 and workmanship for a period of two (2) years.There are no obligations

or liabilities on the part of our company for consequential damages arising

 out of, or in connection with, the use or performance of this product or

 other indirect damages with respect to loss of property, revenue or 

 profit, or cost of removal, installation or reinstallation.