6021642 DIAM4200 2.5 to 20KVA rev 1-9.docx
II-34
II.3
ADJUSTING THE CCR
II.3.1 MULTI TERMINAL INDUCTANCE
Inductance are in the CCR to filter the input current. Position in the CCR.
One inductance per 5KVA module.
The inductance has 3 values available (L0, L1 and L2). L0 (the lower value) is selected by default. Depending of
the loop load, the output current can be unstable.
It can be necessary to increase the inductance value.
It is possible to select L1 or L2 inductance moving the cable connection according to the following drawing:
Keep the wire connected to pin 1 in place, move the wire on pin 2, 3 or 4.
All inductances in the CCR must be connected on the same tapping to balance current in all
modules.
Inductance value
LOW VALUE (defaultvalue)
MEDIUM VALUE
HIGH VALUE
Connections
1 & 2
1 & 3
1 & 4
Multi terminal inductance
Pin 1 connected to
the module.
Don’t move this
connection!