background image

Step 2  Open Front Cover

 

1. Loosen, but 

DO NOT REMOVE

 (2) lower nylock nuts on hinge bolts. 

2. Remove (4) upper nuts and support cover while opening. 
3. Inspect burner head/end cone condition 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Annual Tune Up and 

Inspection 90+ Resolute

 

Oil Boiler

 

Please refer to owner and installation manual for complete details. 

Step 4  Clean Boiler 

 

Do Not Touch, Vacuum or Remove Chamber! 

Note:

  If there is 

heavy scale

 in last pass: 

1. Check for cold returns. 
2. Open by-pass valve fully. 
3. Set Energy Manager Option Switch 1 to “ON”. 
4. Check zone valve operation. 

Step 1  Initial Test (Draft Loss & CO

2

 

Make sure air box cover is in place before testing 

 

1.  Remove 1/8” brass plug from the “over fire” test port (2) next to the burner and the flue 

box (1) next to the puff switch. Check draft through the “over fire” test port (2) and at the 
flue box (1).  Use a 12” long piece of ¼” O.D. steel or copper tubing and insert it 
approximately 8” into the boiler.  Connect this tube to your test probe using a piece of 
hose. 

 

Clean boiler flue passage if the draft difference between the flue box (1) and “over fire” 
test port (2) is greater than .06” w.c. 

 

2.

Check CO

through the “over fire” test port (2).  Insert the 12” long steel or copper tube 

approximately 8” in through the test port. 

 

Refer to the section ‘Burner Operation’ for acceptable combustion readings. 

Step 5  Close Front Cover 

 

1. Install (4) upper nuts and washers. 
2. Tighten nuts (6) uniformly. 
3.  Check Vent Pipe. 
4.  Check Vent hood. 

Step 3  Inspect Flue Passage 

 

If passage is clean, no scale, then close cover and tighten all hardware evenly.  

Clean ONLY if dirty. 

DO NOT remove or touch combustion chamber for inspection or 

when cleaning boiler! 

 

 

 

Step 6  Remove Drawer Assembly 

 

1. Check Electrode Setting. 
2. Check Porcelain Condition. 
3. Check Nozzle for coking/heat. 
Replace nozzle if necessary.  

See installation manual

 