Elektrical connection 

The electrical connection must be implemented according to VDE 0100. For installation and
maintenance work, disconnection from the mains on all poles with at least 3 mm contact opening width
must be undertaken. The mains disconnection is to be secured against reconnection!

 

 
• 

Connection of AirUnit compact controller pro

5.1  Connection AirUnit(s) – controller

The connection of the devices occurs arranged in pairs at the plug connectors. In paired operation one device of a 
device pair operates in feed mode, the second assigned device in exhaust air mode The air flow direction of both 
devices is alternated at intervals. 
 
Maximum 4 

AirUnit ventilation units

 can be operated with the 

AirUnit compact controller pro

. Therefore 

maximum 2 

AirUnit ventilation units

 are to be connected in parallel on plug-in connector 

Fan 1

 and maximum 2 

AirUnit ventilation units

 on plug-in connector 

Fan 2

.

 
Those 

AirUnit

 

ventilation units

, which are connected on the plug-in connector 

Fan 1

 serve as exhaust fan regar-

ding to the function “summer mode”. 

AirUnit ventilation units

 which are connected to plug-in connector 

Fan 2

 

become supply fan in “summer mode”. If several units are used, cross ventilation can be provided, e.g. to convey 
cool outside air into the building during the night hours in summer.  
 
By using a single device, the AirUnit ventilation unit can be used as supply- or exhaust fan in “summer mode”.

The connection of the AirUnits to the connection line of the controller is implemented via a plug connector
contained within the scope of delivery of the ventilation units, as depicted previously. Please observe the polarity
feed / exhaust devices (see Fig. above)!

Ventilation device

Controller

+12 V – RED 

PWM – PURPLE

Gnd – BLUE

RED – +12 V 

PURPLE – PWM

BLUE – Gnd

Connecting terminal 

1

RS485-A

2

RS485-B

3

12V Bus

4

GND

5

12V

6

PWM A

7

GND

8

12V

9

PWM B

10

GND

Net terminal

1

L1

2

N

3

External Input L1´ 

must be in phase 

with L1!

Abluft

Zuluft

Содержание AirUnit Compact controller Pro

Страница 1: ...mfh systems modern floor heating mfh systems modern floor heating AirUnit Compact controller Pro Installation instructions operating manual...

Страница 2: ...ro 05 6 External digital input bath ventilation operation 06 7 Sensor operation 06 8 Settings ventilation mode 08 9 Operation amd display elements AirUnit compact controller pro 09 10 Service 10 11 Op...

Страница 3: ...use AirUnit with heat recovery are designed for controlled room ventilation The devices may only be used exclusively for the conveyance of air The conveyance of aggressive flammable or extremely dusty...

Страница 4: ...norms are considered as far as they are applicable for that device EN 61000 6 1 2007 EN 61000 3 3 2008 EN 61000 6 1 2007 EN 61000 6 3 2007 A1 2011 EN 60335 1 4 Installation AirUnit compact controller...

Страница 5: ...ilation units on plug in connector Fan 2 Those AirUnit ventilation units which are connected on the plug in connector Fan 1 serve as exhaust fan regar ding to the function summer mode AirUnit ventilat...

Страница 6: ...fset of exhaust volume flows for the operation bath ventilators The external input is connected in parallel to the bath fan Make sure that bath fan and ventilation unit are switched in the same phase...

Страница 7: ...ed or reduced If the air stages will be reduced manually the demand based ventilation system will be deactivated for a period of 60 minutes The number of the used sensors has to be set in accordance w...

Страница 8: ...of the room air In the second interval feed phase the fresh outside air is conveyed into the room via the ventilation unit The outside air similarly flows through the heat accumulator absorbs the pre...

Страница 9: ...es the device is controlled in sensor operation Constant illumination of this display indicates that inspection cleaning of the filter insert of the ventilation unit is due The maintenance of the filt...

Страница 10: ...r insert to dry completely prior to reinsertion into the ventilation unit dust deposits will occur immediately on a damp filter In order to ensure continued good filtration a filter replacement is nec...

Страница 11: ...EDs The LED for moisture protection represents the 10th digit of the operating hours The reduced ventilation led is the 100 digit The led for the nominal ventilation is the 1000 digit The Led for the...

Страница 12: ......

Отзывы: