Enerco MR. HEATER MHVFB10LPI Скачать руководство пользователя страница 4

4

Installation instructions and Owner’s Manual

1. Find the volume of the space by multiplying room

length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.

(height) = 2592

If additional ventilation to adjoining room is supplied with

grills or openings, add the volume of these rooms to the

total volume of the space.
2. Divide the space volume by 50 cubic feet to deter-

mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. = 51.8

or 51,800 (maximum Btu/hr the space can

support)

 WARNING:

 If the area in which the heater may be

operated is smaller than defined as an unconfined

space or if the building is of unusually tight construc-

tion, provide adequate combustion and ventilation air

by the methods described in the 

National Fuel Gas

Code, NFPA 54/ ANSI Z223.1, 

Section 5.3 or

applicable local codes.

3. Add the Btu/hr of all the fuel-burning appliances in the

space such as, Vent–free heater, Gas water heater,

Gas furnace, Vented gas heater, Gas fireplace logs,

and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and

vents to the outdoors.
Example:
Gas water heater

40,000 Btu/hr

Vent Free  20,000 Btu/hr
Total

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support

with the actual amount of Btu/hr used.

Example: 51,800 Btu/hr (maximum Btu/hr the

space can support)
60,000 Btu/hr (Actual amount of Btu/hr

used)

The space in the above example is a confined space

because the actual Btu/hr used is more than the

maximum Btu/hr the space can support.

You must provide additional fresh air.  Your options

are as follows:

A. Rework worksheet, and the space of an adjoining

room.  If the extra space provides an unconfined

space, remove door to adjoining room or add ventila-

tion grills between the rooms.  See Ventilation Air

From Inside Building (Fig. 2)

B. Vent room directly to the outdoors.  See Ventilation Air

From Outdoors (Fig. 3).

C. Install a lower Btu/hr heater if lower Btu/hr size makes

room unconfined.

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an uncon-

fined space.  You will need no additional fresh air

ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined

space.  When ventilation to an adjoining unconfined

space, you must provide two permanent openings: one

within 12” of the ceiling and one within 12” of the floor on

the wall connecting the two spaces (see options 1 & 2 of

fig. 2).  You can also remove door into adjoining room

(see option3, fig 2). Follow the National Fuel Gas Code

NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion

and Ventilation for required size of ventilation grills or

ducts.

 Figure 2

WARNING:

 Rework worksheet, adding the space of

the adjoining unconfined space. The combined space

must have enough fresh air to supply all appliance in

both spaces.

Figure 3.

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation

grills or ducts. Connect these items directly to the

outdoors or spaces open to the outdoors.  These include

attics* and crawl spaces. Follow the National Fuel Gas

Ventilation

Grills into

Adjoining

Room -

Option 1

Ventilation Grills into

Adjoining Room -

Option 2

12”

12”

Or remove

door into

Adjoining

Room -

Option 3

INLET

AIR

OUTLET

AIR

VENTILATION CRAWL SPACE

TO CRAWL

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED

ATTIC

OUTLET AIR

Содержание MR. HEATER MHVFB10LPI

Страница 1: ...r service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provi sions for adequate combustion and ventilation air must...

Страница 2: ...or anemia those under the influence of alcohol and those at high altitudes Propane LP Gas Propane LP gas is odorless An odor making agent is added to propane LP gas The odor helps you detect a Propan...

Страница 3: ...r The information on pages 3 through 5 will help you classify your space and provide adequate ventilation Unusually Tight Construction If your home meets all of the three following criteria you must p...

Страница 4: ...esh air Your options are as follows A Rework worksheet and the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining room or add ventila tion grills betwe...

Страница 5: ...ff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase a CSA AGA certified equipment shutoff valve from your dealer SeeAccessories page 17 This heater may also be ins...

Страница 6: ...bracket to wall studs 1 Drill holes at marked locations using 9 64 drill bit 2 Place mounting bracket onto wall Line up holes on each end of bracket with hole drilled in wall 3 Insert mounting screws...

Страница 7: ...ing gas pressure to between 11 and 14 inches of water If you do not reduce incoming gas pressure heater regulator damage could occur Install external regulator with the vent pointing down as shown in...

Страница 8: ...S FOR USE WITH HOSE CONNECTED TO A REMOTE CYLINDER MAXIMUM SIZE 20 LBS This Heater may be used in a Recreational Enclosure or Temporary Construction Work Enclosure with a Remote Refillable Propane Cyl...

Страница 9: ...is on 3 Push in gas control knob and slightly turn clockwise to the OFF position see figure 16 Note Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 4 Wait five 5...

Страница 10: ...ck pilot flame pattern and burner flame pattern often PILOT FLAME PATTERN Figure 17 show a correct pilot flame pattern Figure 22 shows an incorrect pilot flame pattern The incorrect pilot flame patter...

Страница 11: ...should also be followed 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes 2 Inspect burner and pilot for dust and dirt 3 Blow air through the port slots and ho...

Страница 12: ...d 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Manifold pressure is too low 2 Burner orifice is clogged When Piezo ignitor knob is turned there is n...

Страница 13: ...line have gas line checked by local gas company 3 Observe minimum installation clearances see Figure 4 page 5 4 Clean burner orifice see Cleaning and Maintenance on page 11 or replace burner orifice...

Страница 14: ...supply original replacement part s call Enerco Group Inc s 800 on the back of this manual TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting if so contac...

Страница 15: ...lector Front 1 8 70324 Valve Piezo Assembly 1 13 70357 Pressure regulator 1 14 70370 Steel Panel 1 15 70327 Steel Panel Mounting Bracket 1 16 70366 ODS Pilot Assembly 1 1 1 19 70396 Heat Shield Top 1...

Страница 16: ...lacement parts Failure to use original factory parts voids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the un...

Отзывы: