background image

4

Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

The space in the above example is a confined 

space because the actual Btu/hr used is more than 

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 

are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfined 

space, remove door to adjoining room or add venti

-

lation grills between the rooms. See Ventilation Air 

From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfined. 

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an uncon-

fined space. You will need no additional fresh air 

ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 

space. When ventilation to an adjoining unconfined 

space, you must provide two permanent openings: one 

within 12” of the ceiling and one within 12” of the floor 

on the wall connecting the two spaces (see options 1 

& 2 of fig. 2). You can also remove door into adjoin

-

ing room (see option3, fig 2). Follow the National Fuel 

Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for 

Combustion and Ventilation for required size of ventila

-

tion grills or ducts.

 Figure 2

  WARNING:

 Rework worksheet, adding the space 

of the adjoining unconfined space. The combined 

space must have enough fresh air to supply all ap

-

pliance in both spaces. 

installed in that space, and an unconfined space as a 

space whose volume is not less than 50 cubic feet per 

1,000 Btu per hour (4.8 m

3

 per kW) of the aggregate 

input rating of all appliances installed in that space. 

Rooms communicating directly with the space in which 

the appliances are installed*, through openings not fur

-

nished with doors, are considered a part of the uncon-

fined space.

*Adjoining rooms are communication only if there 

are doorless passageways or ventilation grills be

-

tween them.

DETERMINING THE TYPE OF HEATER 

LOCATION SPACE:

Use this method to determine if you have a confined or 

unconfined space.

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with door

-

less passageways or ventilation grills between the 

rooms.

1. Find the volume of the space by multiplying room 

length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  

 

(height) = 2592

If additional ventilation to adjoining room is supplied 

with grills or openings, add the volume of these rooms 

to the total volume of the space.
2. Divide the space volume by 50 cubic feet to deter

-

mine the maximum Btu/hr the space can support.

Example:  2592 cu.ft. (volume of space) / 50 cu.ft. =  

 

51.8 or 51,800 (maximum Btu/hr the space  

 

can support)

 WARNING:

 If the area in which the heater may be 

operated is smaller than defined as an unconfined 

space or if the building is of unusually tight con

-

struction, provide adequate combustion and ventila

-

tion air by the methods described in the 

National 

Fuel Gas Code, NFPA 54/ ANSI Z223.1, 

Section 

5.3 or applicable local codes. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 

heater, Gas furnace, Vented gas heater, Gas fire

-

place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and 

vents to the outdoors.

Example:

Gas water heater  40,000 Btu/hr

Vent Free   20,000 Btu/hr

Total 

 

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the   

 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

Ventilation 

Gills into 

Adjoining 

Room - Op-

tion 1

Ventilation Gills into Ad-

joining Room - Option 2

12”

12”

Or remove 

door into 

Adjoining 

Room - 

Option 3

Содержание HSBF10LP

Страница 1: ...hone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Fresh ...

Страница 2: ...onoxide than oth ers These include pregnant women persons with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes Propane LP Gas Propoane LP gas is odorless An odor making agent is added to propane LP gas The odor helps you detect a Propane LP gas leak However the odor added to propane LP gas may be present even though no odor exists Make certain you r...

Страница 3: ...WARNING This heater shall not be installed in a confined space or unusually tight construction un less provisions are provided for adequate combus tion and ventilation air Read the following instruc tions to insure proper fresh air for this and other fuel burning appliances in your home ESTABLISHING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code NFPA 54 ANSI Z223 1 Sec...

Страница 4: ...ances are installed through openings not fur nished with doors are considered a part of the uncon fined space Adjoining rooms are communication only if there are doorless passageways or ventilation grills be tween them DETERMINING THE TYPE OF HEATER LOCATION SPACE Use this method to determine if you have a confined or unconfined space Note the space includes the room in which you install heater pl...

Страница 5: ... connection Sediment trap Tee joint Pipe wrench A CSA AGA certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge con nection Purchase a CSA AGAcertified equipment shutoff valve from your dealer See Accessories page 17 LOCATING HEATER This heater is designed to be mounted on the wall The heater can also be located on a non combustible floor away from a wall by...

Страница 6: ...will be located Make sure mounting bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provide greater clearances from the floor and joining wall 2 Mark screw locations on wall see figure 7 3 Remove tape and mount bracket from wall Figure 7 Attaching to Wall Stud For attaching mounting brac...

Страница 7: ...d locations using 9 64 drill bit 5 Re place heater onto mounting bracket 6 Place spacers between bottom mounting holes and wall anchor or drilled hole 7 Hold spacer in place with one hand With the other hand insert mounting screw through bottom mounting hole and spacer Place tip of screw in opening of wall anchor or drilled hole 8 Tighten both screws until heater is firmly se cured to wall Do not ...

Страница 8: ...it is within reach for cleaning A sediment trap traps moisture and con taminants This keeps them from going into heater If sediment trap is not installed or is installed improperly heater may not run correctly IMPORTANT Hold pressure regulator with wrench when connecting it to gas piping and or fittings CHECKING GAS CONNECTIONS WARNING Test all gas piping and connections for leaks after installing...

Страница 9: ...d it must be replaced with type AWG 105o C wire or its equivalent except as indicated WARNING Electrical Grounding Instructions This heater is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged into a properly grounded three prong receptacle OPERATING YOUR HEATER NON THERMOSTAT MODELS IR10LP BF10LP FOR YOUR SAFETY READ BEFORE LIGHTING WARNING ...

Страница 10: ...ht pilot If needed gently keep rotating control knob back and forth while depressed until pilot lights 7 Keep control knob depressed in for ten 10 seconds after lighting pilot If pilot goes out repeat steps 4 5 6 and 7 If pilot does not stay lit refer to Troubleshoot ing pages 14 15 Also contact a qualified service person or gas supplier for repairs If control knob does not pop up when released co...

Страница 11: ...o repair it call a qualified service technician or gas supplier Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been underwater Immediately call a qualified service technician to inspect the appliance and to re place any part of the control system which has been underwater LIGHTING INSTRUCTIONS 1 STOP Read the all safety information included ...

Страница 12: ...the heater Note The LED temperature indicator DOES NOT oper ate with or control the thermostat setting of the heater TO TURN OFF GAS TO APPLIANCE Shutting Off Heater 1 Turn control knob clockwise to the OFF posi tion 2 Turn off all electrical power to the appliance if servicing is to be preformed 3 Turn off equipment shutoff valve SHUTTING OFF BURNER ONLY PILOT STAYS LIT 1 Turn control knob clockw...

Страница 13: ...urner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 psig This can be done by using a vacuum cleaner in the blow position using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could damage the burner or pilot assembly In addition the directions that follo...

Страница 14: ...ol valve damaged 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Manifold pressure is too low 2 Burner orifice is clogged When ignitor button is pressed in there is no spark at pilot ODS pilot lights but flame goes out when control knob is released When ignitor button is pressed in there is a spark at the ODS pilot but no ignition Burner does not li...

Страница 15: ... after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line have gas line checked by local gas company 3 Observe minimum installation clearances see Figure 4 page6 4 Clean burner orifice see Cleaning and Maintenance on page 13 or replace burner orifice 1 Turn heater off when using furniture polish wax carpet cleane...

Страница 16: ...5cm 36 915cm Sides 6 152cm 10 5 267cm 10 5 267cm Floor min to top of carpet 2 51cm 2 51cm 2 51cm Fabric flammable objects 36 915cm 36 915cm 36 915cm BF6LP BF10LP BF20LPT BF30LPT BTU Available 6 000 10 000 20 000 30 000 Type of Gas LP Gas Only LP Gas Only LP Gas Only Ignition Piezo Battery ignitor 1 AA Battery ignitor 1 AA Pressure Regulator Setting 10 Inches of Water 10 Inches of Water 10 Inches o...

Страница 17: ...17 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater ...

Страница 18: ...18 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater ...

Страница 19: ...19 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater ...

Страница 20: ...20 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater ...

Страница 21: ...21 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater ...

Страница 22: ...Type of gas used Natural Gas Purchase date Usually we will ask you to return the defective part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealer of this product If they can t supply original replacement part s call Enerco Group Inc s 800 on the back of this manual TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting if so contact Enerco ...

Страница 23: ...23 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater Notes ...

Страница 24: ...h the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear of parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such costs related to repairing a defective heater will be the responsibility of the ...

Отзывы: