WirelessHART Fieldgate SWG70
Commissioning
E Hauser
33
7
Commissioning
NOTICE!
• We recommend that you first set up the Fieldgate SWG70, the WirelessHART Adapters
and the HART devices on a test bench and test the network.
The Fieldgate SWG70 can be set up in the following ways:
• Via the Ethernet connection using the Web server
• Via the Ethernet connection using FieldCare and Fieldgate-DTM
• Via the RS-485 connection using FieldCare and Fieldgate-DTM
The structure of the parameter blocks and the parameters in the Fieldgate DTM and the Web
server in the Fieldgate are identical.
Web server
The Fieldgate SWG70 has an integrated Web server.
You can set up the Fieldgate and the associated WirelessHART network via the Web server.
See Chapter 7.1 for details on setting up the Fieldgate SWG70 via the Web server.
FieldCare
You can set up the Fieldgate and the associated WirelessHART network via FieldCare. In
addition, you can also configure the WirelessHART Adapters SWA70 and the connected
devices via FieldCare.
A prerequisite is that the WirelessHART Adapters and devices already use the same join key
and network identifier as Fieldgate SWG70 and have joined the network. Configure
connected WirelessHART Adapters and field devices via the relevant DTMs.
NOTICE!
• It is advisable to configure the adapters and connected HART devices via a direct
connection. See Operating Instructions BA00061S/04/en. If FieldCare accesses the
devices via the Fieldgate SWG70 DTM, the response times may be considerably longer
than for a direct connection.
See Chapter 7.1 and Chapter 7.3. for details on setting up the Fieldgate SWG70 via
FieldCare.