WirelessHART Fieldgate SWG70
Electrical Installation
E Hauser
25
4. Connect the Ethernet cable to the terminal block labeled "Ethernet" according to the
following table.
5. Screw the housing cover on the housing.
6. Tighten the cable gland with appropriate torque. See Chapter 5.5 "Cable glands and
7. Switch on the power supply.
5.3.2
Connecting the "EtherNet/IP" version to Ethernet
The Ethernet cable with a D-coded M12 connector is connected to the M12 socket of the
Fieldgate housing.
Fig. 5-4: Fieldgate with M12 socket in the middle
1. Switch off the power supply.
2. Plug the D-coded M12 connector into the Ethernet socket of the Fieldgate. See
3. Tighten the coupling nuts on the M12 connector. The Fieldgate is connected to the
Ethernet network.
4. Switch on the power supply.
Computer
Fieldgate
Pin Numbering
Connector
Crossover cable
Normal cable
Pin 1
TX+
RX+
Pin 2
TX–
RX–
Pin 3
RX+
TX+
Pin 4
T2
T2
Pin 5
T2
T2
Pin 6
RX–
TX–
Pin 7
T1
T1
Pin 8
T1
T1
1 Ethernet terminal block wired internally to M12
socket
2 M12 socket, D-coded for connection to an
Ethernet or Ethernet/IP network
1 2 3 4 5 6 7 8
KL7
KL8
KL9
KL10
A
B
SHD
RS485
T1
T2
ON
OFF
SHD
A
B
SHD
RS485
ET
T1
T2
RX– RX+ TX–
TX+
SHD
ETHERNET
KL11