Waterpilot FMX11
Electrical connection
Hauser
15
6
Electrical connection
6.1
Connection conditions
L
WARNING
Supply voltage might be connected!
Risk of electric shock!
‣
Switch off supply voltage.
• The supply voltage must match the supply voltage specified on the nameplate.
• The cable must end in a dry room or a suitable terminal box. The terminal box (IP66/
IP67) with GORE-TEX® filter from Hauser is suitable for outdoor installation.
The terminal box can be ordered separately as an accessory (order number: 52006152).
• Connect the device in accordance with the following diagrams. Reverse polarity
protection is integrated in the Waterpilot FMX11. Changing the polarities will not result
in damage to the device. The device is not operational.
• A suitable circuit breaker should be provided for the device in accordance with IEC/EN
61010.
RD
GNYE
BK
)
)
2
3
1
4
A0040869
1
8 to 28 V
DC
2
4 to 20 mA
3
Resistance (R
L
)
4
Waterpilot FMX11
6.2
Connecting the measuring device
6.2.1
Supply voltage
8 to 28 V
DC
6.2.2
Cable specification
Connecting cable
Hauser recommends using shielded, twisted-pair two-wire cables.
• Commercially available instrument cable
• Terminals, terminal box: 0.08 to 2.5 mm
2
(28 to 14 AWG)